Records from 2016 to 2026. Most recent: inspection, 26 January 2026.
Everything above is free. The detail below — the inspection history, the deficiency record, the operational controls and the documentation record — is Professional, $39 a month. Sign in.
Inspection history · 42
26 January 2026
Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 8301657
9 December 2025
Annual Inspection · Administrative Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 8279837
12 July 2024
Administrative Inspection
Administrative · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 7959112
3 February 2023
Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7730551
9 January 2023
Annual Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7620493
10 November 2022
Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7606168
17 October 2022
Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7588892
21 June 2022
Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7482729
17 May 2022
Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7480091
12 January 2022
Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7392054
19 July 2021
MTSA Verification · Administrative Inspection · Annual Inspection
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 7213317
8 July 2021
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7249465
30 March 2021
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7165675
17 March 2021
Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7175967
12 March 2021
Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7156575
20 January 2021
Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7127599
25 November 2020
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7195483
20 September 2020
Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7094083
8 September 2020
Deficiency Check · Administrative Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7053440
20 August 2020
Construction Oversight · Administrative Inspection
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 7162642
9 July 2020
Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7005061
15 June 2020
Deficiency Check · Damage Survey
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 6980987
11 June 2020
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6973896
10 February 2020
Administrative Inspection
Administrative · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 6906350
6 January 2020
Security Plan Review - VSP
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 6993622
4 October 2019
Annual Inspection · MTSA Verification
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 6829769
5 September 2019
MTSA Verification · Construction Oversight · Administrative Inspection · In-Service Inspection
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 6818985
18 October 2018
Administrative Inspection
Administrative · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 6576614
23 July 2018
MTSA Verification · COI Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 6487251
10 July 2018
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6474439
26 June 2018
Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 6538304
6 December 2017
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6319316
26 October 2017
MTSA Verification · Annual Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 6301605
18 July 2017
Administrative Inspection
Administrative · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 6212862
9 March 2017
Construction Oversight · Administrative Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6101732
20 February 2017
In-Service Inspection
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 6108679
15 December 2016
MTSA Verification
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 6063443
18 October 2016
Deficiency Check
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 6024367
15 September 2016
Administrative Inspection · Uninspected Other · Construction Oversight
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6001652
17 August 2016
Examination of Repairs
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5975260
3 June 2016
Annual Inspection
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 5896589
23 May 2016
Administrative Inspection · In-Service Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5901648
02 - Structural Conditions › N/A - No Subsystem › Hull damage impairing seaworthiness
Issued 24 September 2019
Resolved
AS REFERENCED IN USCG MSC LETTER C2-2000077 DTD
8JAN2020, DOUBLER PLATE LOCATED AT FW-SK 09-1 IS AN
UNSATISFACTORY PERMANENT REPAIR. IN ADDITION, PORTIONS
OF TRUSS ROW QD RUNNING FROM LEVEL TWO TO LEVEL THREE
ARE WASTED BEYOND ALLOWANCE. CROP AND RENEW WASTED
STRUCTURAL MEMBER SEGMENTS AS REQUIRED TO RESTORE
REFERENCED AREAS TO COMPLIANCE WITH NVIC 7-68. REPAIRS
ARE TO BE COMPLETED PRIOR TO COMMISSIONING OF NEWLY
INSTALLED LIFEBOAT.--NOTHING FOLLOWS--
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 24 March 2020
Resolved 5 May 2020
Resolution: Shell proved material condition / adequate strength of member with doubler and OCS OCMI granted allowance.
Fire Fighting › Structural Fire Protection - General › Structural Bulkhead Construction
Issued 22 February 2017
Resolved
6 of 10 fire doors in and btwn turbine rooms did not close all the way. Doors are fitted w/ self closing devices but did not latch under power of closer.
Condition: Improper/Lack of Maintenance
Due 1 March 2017
Resolved 24 February 2017
Resolution: Crew repaird doors. Barge Sup provided video of doors closing. Crew must now maintain doors.
Lifesaving › Lifeboat › Watertight Enclosure
Issued 22 February 2017
Resolved
Multiple lifeboats are not maintained in good condition and have missing or corroded and froze adjustable tools. #6 L/B has 4" of water in the bilge. Multiple boats have leaks about the boarding doors. Crew pumps out bilge immediately before CG inspections.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2017
Resolved 13 March 2017
Resolution: Received email stating that lifeboats have been repaired and restocked.
Lifesaving › Lifeboat › Exhaust Pipe
Issued 27 July 2016
Resolved
#6 lifeboat had a propulsion engine exhaust leak visually detected by smoke in the beam of a flash light and by small. A gas portable gas detector was placed in the top of the engine compartment and a CO level of 23ppm was detected within 10 seconds. OHSA PEL for CO is 50ppm. The specific location of the leak could not be determined with further examination of the engine.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 16 August 2016
Resolved 28 July 2016
Resolution: Rig's crew repaired leak and provided statement stating such. CG Inspectors verifed repair on 18 OCT.
Electrical › Electrical Distribution System (service) › Junction Box
Issued 3 June 2016
Resolved
Multiple exposed wires and cooroded mounts were found in the mud pump/module, lower level. Mud module has not been in service in 4 years; however, may be returned to service at any time if drilling operations are required.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 18 October 2016
Resolution: Rig's crew removed and/or properly terminated exposed wiring and repaired damaged mounts.
Fire Fighting › Structural - A Class Divisions › Doors
Issued 3 June 2016
Resolved
Multiple fire doors inside and outside of accomodations did not self close or latch, per facilities safety plan. Laundry room door was unable to close due to placement of driers.
Condition: Improper/Lack of Maintenance
Due 1 August 2016
Resolved 18 October 2016
Resolution: Rig's crew adjusted doors and they properly close.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 3 June 2016
Resolved
Multiple exterior emergency lights around all platform and on different levels were burnt out and not burning brightly.
Condition: Improper/Lack of Maintenance
Due 1 August 2016
Resolved 27 July 2016
Resolution: Platform crew surveryed and replaced needed lights and/or bulbs. Resolution was verified by USCG inspection team on 7/27/2016.