DIAMOND JO

Built
1991
Last inspected
16 January 2006
Controls
None recorded without a removal date

This record may be incomplete: the most recent inspection recorded for this vessel was 20 years ago. Maury shows what the Coast Guard recorded, not whether the vessel has been inspected since, is still in service, or what condition it is in. Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard.

Inspection record

Last inspected 16 January 2006
…with no type recorded24
Operational controls None recorded without a removal date
Years with a record 16 calendar years (1991–2006)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

WCZ4242
360775
Flag
UNITED STATES
Tonnage
861 - Convention (Subpart B), Net Ton 828 - Regulatory (Subpart C or D), Net Ton 2506 - Convention (Subpart B), Gross Ton 828 - Regulatory (Subpart C or D), Gross Ton
Maury page id
psix-360775
Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 1972 to 2026, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspected as a tow unit · 1

The Coast Guard recorded this vessel and the following in the same inspection activity — normally a tug and the barges in its tow. Only barges and towing vessels are in this archive, so any other vessel type in the same activity does not appear here: these lists are a floor, not a complete manifest.

DIAMOND JO II Towing Vessel · MISLE 360776 · 4 April 2000 · activity 127181

Inspection history · 132

16 January 2006 Administrative Inspection
Administrative · Marine Safety Center (MSC) · Activity 2567473
30 November 2005 Administrative Inspection
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 2543611
29 November 2005 Administrative Inspection
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 2542406
28 November 2005 Administrative Inspection
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 2541813
10 June 2005 Deficiency Check
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2456275
19 May 2005 Deficiency Check
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2456267
22 April 2005 Deficiency Check
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2456262
11 April 2005 Administrative Inspection
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 2331071
8 April 2005 Deficiency Check
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2456249
5 April 2005 Administrative Inspection
Administrative · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2456242
25 March 2005 Deficiency Check
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2456232
3 March 2005 COI Inspection
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2302620
3 November 2004 Type not recorded
No type recorded · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 2466735
28 October 2004 MTSA Verification
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2314730
15 June 2004 Administrative Inspection
Administrative · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2099541
18 May 2004 Administrative Inspection
Administrative · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2071585
1 April 2004 Deficiency Check
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2035520
10 March 2004 COI Inspection
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 2015583
22 January 2004 Quarterly Examination
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1990075
22 December 2003 Security Plan Review - ASP
Administrative · Marine Safety Center (MSC) · Activity 1977888
3 November 2003 Deficiency Check
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1941205
7 October 2003 Quarterly Examination
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1922919
1 July 2003 Quarterly Examination
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1832392
8 April 2003 Deficiency Check
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1770112
11 March 2003 COI Inspection
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1755202
5 February 2003 Internal Structural Exam · Underwater Inspection in lieu of Drydock · Quarterly Examination
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1740061
24 October 2002 Quarterly Examination
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1696088
28 August 2002 Deficiency Check
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1667590
10 July 2002 Re-Inspection
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1644276
4 June 2002 Deficiency Check
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1626265
12 April 2002 Deficiency Check
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1604105
11 March 2002 COI Inspection
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1492641
13 December 2001 Re-Inspection
Physical examination · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 1476285
26 October 2001 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1076057
28 September 2001 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1437958
13 July 2001 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1067893
28 June 2001 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1449486
15 June 2001 Administrative
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1065813
22 May 2001 Type not recorded
No type recorded · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1384773
21 March 2001 COI Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1456954
8 January 2001 Administrative
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1369959
5 October 2000 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1391448
21 June 2000 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1050918
21 June 2000 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1467684
4 April 2000 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 127181
31 March 2000 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1048944
17 March 2000 COI Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1453729
22 February 2000 Type not recorded
No type recorded · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1435040
30 December 1999 Administrative
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 812625
15 December 1999 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1391162
24 September 1999 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1449240
2 August 1999 Administrative
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 774302
1 July 1999 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1401033
17 March 1999 COI Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1429096
9 December 1998 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1445406
22 July 1998 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 12965
26 June 1998 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1461899
26 June 1998 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1472121
8 June 1998 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 111775
12 March 1998 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1105871
11 March 1998 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1121803
23 January 1998 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1115434
15 January 1998 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 774277
29 December 1997 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1117920
17 December 1997 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1414911
6 October 1997 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 184113
16 September 1997 Type not recorded
No type recorded · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1409751
16 September 1997 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1414860
16 September 1997 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1461074
25 June 1997 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1446506
15 April 1997 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1098647
31 March 1997 COI Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1374933
17 March 1997 COI Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1469503
12 March 1997 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1102234
6 March 1997 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1100110
7 February 1997 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1105179
16 January 1997 Administrative
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1099114
9 January 1997 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1390413
8 January 1997 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 228487
19 November 1996 Administrative
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 867857
11 November 1996 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 159574
24 September 1996 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1396597
11 July 1996 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1089738
20 June 1996 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1447597
30 April 1996 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1081285
14 March 1996 COI Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1398419
28 February 1996 Administrative
Administrative · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 885717
7 February 1996 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 873703
28 January 1996 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 72511
4 January 1996 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1425672
30 December 1995 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 178296
30 November 1995 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 134260
7 November 1995 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 32057
30 October 1995 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 171917
26 October 1995 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 205852
26 October 1995 Type not recorded
No type recorded · MSD QUAD CITIES · USCG Heartland District (CGD-H) · Activity 753633
18 October 1995 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 886062
2 October 1995 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 883280
27 September 1995 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 880911
11 September 1995 Hull Examination
Physical examination · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 885921
11 September 1995 Re-Inspection
Physical examination · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 1446249
19 May 1995 Type not recorded
No type recorded · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 56512
29 March 1995 COI Inspection
Physical examination · MSO MEMPHIS · USCG Heartland District (CGD-H) · Activity 1160929
17 November 1994 Deficiency Check
Physical examination · MSO MEMPHIS · USCG Heartland District (CGD-H) · Activity 869882
25 October 1994 Re-Inspection
Physical examination · MSO MEMPHIS · USCG Heartland District (CGD-H) · Activity 871524
25 April 1994 COI Inspection
Physical examination · MSO MEMPHIS · USCG Heartland District (CGD-H) · Activity 1171699
31 January 1994 Re-Inspection
Physical examination · MSO MEMPHIS · USCG Heartland District (CGD-H) · Activity 852135
18 November 1993 Re-Inspection
Physical examination · MSO MEMPHIS · USCG Heartland District (CGD-H) · Activity 1145946
15 October 1993 Hull Examination
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1459825
10 August 1993 Administrative
Administrative · MSO Mobile · USCG Heartland District (CGD-H) · Activity 845788
30 April 1993 Hull Examination · COI Inspection
Physical examination · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 1151775
6 April 1993 Administrative
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1150848
25 February 1993 Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 135195
2 February 1993 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1147400
4 November 1992 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 957526
25 October 1992 Type not recorded
No type recorded · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 97635
20 July 1992 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1255890
2 July 1992 Type not recorded
No type recorded · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1269400
21 April 1992 COI Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 944720
20 March 1992 Hull Examination
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 946670
26 February 1992 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 944316
16 January 1992 Type not recorded
No type recorded · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1271002
19 November 1991 Deficiency Check
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 938055
28 October 1991 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 941142
1 October 1991 Administrative
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1249272
12 August 1991 Re-Inspection
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 935987
17 July 1991 Administrative
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1249112
24 June 1991 Administrative
Administrative · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 904056
24 May 1991 Type not recorded
No type recorded · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1221351
26 April 1991 Hull Examination
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1218413
26 April 1991 Initial Certification
Physical examination · MSO ST LOUIS · USCG Heartland District (CGD-H) · Activity 1234380
5 April 1991 Type not recorded
No type recorded · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 907120

Deficiency record · 176

Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 3 March 2005 Resolved
Replace & demonstrate proper operation of the time delay for the CO2 system in the bow thruster room. 46 CFR 76.15
Due 18 March 2005
Resolved 18 March 2005
Resolution: Conducted operational test of time delay of the CO2 system with satisfactory results.
Electrical › Electrical Distribution System (emergency) › Circuit Breaker
Issued 3 March 2005 Resolved
Open, inspect, and clean (as needed) all electrical panels. 46 CFR 111.01
Due 18 April 2005
Resolved 22 April 2005
Resolution: Electrical panel cleaning found satisfactory.
Accommodation/Occupational Safety › Occupational Safety › Guards for Exposed Hazards
Issued 3 March 2005 Resolved
Install guards over pulleys/belts on the engine for the emergency generator. 46 CFR 58.01-20
Due 4 April 2005
Resolved 4 April 2005
Resolution: Guard was installed and found satisfactory.
Electrical › Electrical Distribution System (service) › Distribution Panel Bus
Issued 3 March 2005 Resolved
Provide a distribution panel with properly sized fuses for the 12 V feeder cable in the emergency generator room. 46 CFR 111.50-3 (f)
Due 18 April 2005
Resolved 22 April 2005
Resolution: Installation of distribution panel found satisfactory.
Fire Fighting › Automatic Sprinkler System › Pressure Tank
Issued 3 March 2005 Resolved
Conduct hydrostatic test of the sprinkler tank. 46 CFR 54.10-10
Due 1 June 2005
Resolved 1 June 2005
Resolution: Hydrostatic test conducted and found satisfactory.
Fire Fighting › Combustible Materials › Insulation
Issued 3 March 2005 Resolved
Provide documentation stating existing fire stop material (black, honey comb, spongy material) is CG approved and installed per manufacturer's instructions. 46 CFR 72.05-10(a)
Due 18 March 2005
Resolved 18 March 2005
Resolution: Received documentation stating the material used during the initial installation.
Accommodation/Occupational Safety › Potable Water System › General
Issued 3 March 2005 Resolved
Submit proposal for modifications to the sprinkler system attached to the city water system to meet state/local health codes. 46 CFR 76.23
Due 18 March 2005
Resolved 18 March 2005
Resolution: Received proposal to conduct necessary modifications to the potable water system.
Accommodation/Occupational Safety › Potable Water System › General
Issued 3 March 2005 Resolved
Provide report from a certified inspector on the results of the inspection to the sprinkler system and demonstrate proper operation of the system. 46 CFR 76.23
Due 10 June 2005
Resolved 10 June 2005
Resolution: Operational test of sprinkler system found satisfactory.
Fire Fighting › Structural - A Class Divisions › Store-rooms
Issued 3 March 2005 Resolved
Repair wire penetrations in the storage closet, main deck, to meet SFP requirements. 46 CFR 72.05(a)
Due 4 April 2005
Resolved 4 April 2005
Resolution: Wire penetrations repaired and found satisfactory.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 3 March 2005 Resolved
Submit proposal for repair and/or installation of additional emergency transitional lights to ensure adequate lighting of passageways & exits. 46 CFR 112.15
Due 4 April 2005
Resolved 4 April 2005
Resolution: Proposal received and found satisfactory.
Fire Fighting › Structural - A Class Divisions › Accommodation Spaces
Issued 3 March 2005 Resolved
Seal wireway deck penetrations beneath sloth machines to meet required SFP & make penetrations available for inspection to CG. 46 CFR 72.05-10
Due 10 June 2005
Resolved 10 June 2005
Resolution: Penetrations sealed and found satisfactory.
Accommodation/Occupational Safety › Potable Water System › General
Issued 3 March 2005 Resolved
Repair and/or replace hand sink strainer & ice bin tray in the main deck bar. 46 CFR 71.25-40
Due 4 April 2005
Resolved 4 April 2005
Resolution: Hand sink and ice bin tray replaced.
Electrical › Electrical Distribution System (service) › Wiring
Issued 3 March 2005 Resolved
Properly secure all cables in the overhead IAW with IEEE & NEC standards.
Due 15 May 2005
Resolved 19 May 2005
Resolution: Wire cables in overhead are properly secured.
Fire Fighting › Ventilation Systems › Ducts
Issued 3 March 2005 Resolved
Remove all dirt/dust in the overheads & air handling rooms & make all areas open for inspections by USCG.
Due 15 May 2005
Resolved 19 May 2005
Resolution: Inspection of overheads found satisfactory.
Fire Fighting › Ventilation Systems › Ducts
Issued 3 March 2005 Resolved
Remove old vent duct between the matrix (electrical/comms) room & restroom & seal shut opening to meet SFP bulkhead requirements
Due 18 April 2005
Resolved 22 April 2005
Resolution: Old vent was removed and bulkhead re-weld.
Fire Fighting › Structural - A Class Divisions › Accommodation Spaces
Issued 3 March 2005 Resolved
Conduct repairs to plate on the bulkhead in the first deck male restroom to meet SFP bulkhead requirements.
Due 18 April 2005
Resolved 22 April 2005
Resolution: Repairs to bulkhead found satisfactory.
Fire Fighting › Structural Fire Protection - General › Structural Bulkhead Construction
Issued 3 March 2005 Resolved
Submit proposal to repair/replace fire stop material in the wireways that transit through structural fire protection boundaries. Areas include, but not limited to matrix room, main vertical fire boundaries, etc. After proposal is approved & work completed, wire penetrations must be made available for inspection by USCG. Proposal must include fire stop material to be used.
Due 18 March 2005
Resolved 18 March 2005
Resolution: Received proposal to repair/replace fire stop material.
Fire Fighting › Structural Fire Protection - General › Hull Construction
Issued 3 March 2005 Resolved
Provide updated approved SFP drawing showing compartment access drawing for SFP that reflect current condition of the vessel.
Due 4 April 2005
Resolved 4 April 2005
Resolution: Received updated SFP drawing.
Electrical › Electrical Distribution System (service) › Outlet Box
Issued 3 March 2005 Resolved
Install ground fault interrupter (GFI) on receptacles within 6 ft of sources of liquids.
Due 18 April 2005
Resolved 5 April 2005
Resolution: Request for appeal was approved and requirement was removed.
Fire Fighting › Ventilation Systems › Ducts
Issued 3 March 2005 Resolved
Provide exhaust ducts for exhaust fans on the first deck - ducts must protrude beneath ceiling tiles.
Due 4 April 2005
Resolved 5 April 2005
Resolution: Request for appeal was approved and requirement removed from vessel.
Fire Fighting › Ventilation Systems › Ducts
Issued 3 March 2005 Resolved
Provide enclosure on top of each ventilation trunk in all air handler rooms.
Due 4 April 2005
Resolved 5 April 2005
Resolution: Request for appeal was approved and requirement was removed.
Electrical › Electric Generation Source (emergency)
Issued 10 March 2004 Resolved
Prove proper operation of emergency generator motor operated breaker. LEGACY COMPONENT DESC: Circuit Breaker
Condition: Unknown
Action required: 705 - Other - as specified
Due 10 April 2004
Resolved 31 March 2004
Resolution: MOB operational.
Fire Fighting › Portable CO2 Fire Extinguisher
Issued 7 October 2003 Resolved
Ensure all portable fire extinguishers are stowed on approved brackets.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 7 November 2003
Resolved 3 November 2003
Resolution: All portable fire extinguishers are stowed on approved brackets.
Electrical › Lighting (service) › Conductor
Issued 1 July 2003 Resolved
Port sidelight inoperative. Corrected on the spot.
Condition: Unknown
Due 1 July 2003
Resolved 1 July 2003
Resolution: Port sidelight sat.
Electrical › Electrical Distribution System (service)
Issued 11 March 2003 Resolved
Ensure electrical panels througout the ship are labeled properly. LEGACY COMPONENT DESC: Panelboard
Action required: 705 - Other - as specified
Due 11 April 2003
Resolved 8 April 2003
Fire Fighting › Structural - A Class Divisions
Issued 11 March 2003 Resolved
Ensure firedoors properly close on main deck port side. LEGACY COMPONENT DESC: Openings - Fire Doors
Action required: 705 - Other - as specified
Due 11 April 2003
Resolved 8 April 2003
Electrical › Electrical Distribution System (service)
Issued 11 March 2003 Resolved
Hardwire video camers on portside 1,2,3 decks. Remove plug outlet connection
Action required: 705 - Other - as specified
Due 11 April 2003
Resolved 8 April 2003
Fire Fighting › Portable Dry Chemical Fire Extinguisher
Issued 10 July 2002 Resolved
Repair/Replace mounting bracket for fire extinguisher on 2nd deck bar. LEGACY COMPONENT DESC: Mounting Bracket
Action required: 705 - Other - as specified
Due 10 August 2002
Resolved 28 August 2002
Fire Fighting › Means of Escape
Issued 10 July 2002 Resolved
Install door latches on door in evac room and aft chiller room LEGACY COMPONENT DESC: Doorways
Action required: 705 - Other - as specified
Due 10 August 2002
Resolved 28 August 2002
Lifesaving › Lifebuoys
Issued 11 March 2002 Resolved
Ensure life buoys stowage areas marked IAW 46 CFR 199.70 LEGACY COMPONENT DESC: Stowage
Action required: 705 - Other - as specified
Due 12 April 2002
Resolved 10 April 2002
Fire Fighting › Structural - A Class Divisions
Issued 11 March 2002 Resolved
Ensure latches on doors to weather decks are IAW 46 CFR 72.05-25 LEGACY COMPONENT DESC: Openings - Doors
Action required: 705 - Other - as specified
Due 30 April 2002
Resolved 1 May 2002
Fire Fighting › Structural - Horizontal Zones
Issued 11 March 2002 Resolved
Ensure piping penetrations are IAW NVIC 9-97 throughout the vessel.
Action required: 705 - Other - as specified
Due 12 April 2002
Resolved 10 April 2002
Fire Fighting › Structural Fire Protection - General
Issued 11 March 2002 Resolved
Ensure structural fire protectionis IAW NVIC 9-97 in the bow thrustuer room and forward and aft chiller rooms.
Action required: 705 - Other - as specified
Due 12 April 2002
Resolved 10 April 2002
Electrical › Electrical Distribution System (service)
Issued 11 March 2002 Resolved
Remove all extension chords located on the vessel. LEGACY COMPONENT DESC: Wiring
Action required: 705 - Other - as specified
Due 12 April 2002
Resolved 10 April 2002
Electrical › Electrical Distribution System (service)
Issued 11 March 2002 Resolved
Remove surge protectors where being used as an extension chord. LEGACY COMPONENT DESC: Wiring
Action required: 705 - Other - as specified
Due 12 April 2002
Resolved 10 April 2002
Accommodation/Occupational Safety › Occupational Safety
Issued 11 March 2002 Resolved
Submit draft autmated test procedures IAW 46 CFR 61
Action required: 705 - Other - as specified
Due 11 March 2002
Resolved 19 March 2002
Resolution: Per Subchapter F, vsl is not required to have automated test proceduresl
Electrical › Lighting (emergency) › Battery Operated Lantern
Issued 11 March 2002 Resolved
Replace/repair battery light in dimmer room
Due 11 April 2002
Resolved 11 March 2002
Fire Fighting › Miscellaneous Items
Issued 11 March 2002 Resolved
Ensure wiring is wrapped with metallic bands IAW NVIC 9-97
Due 11 March 2002
Resolved 11 March 2002
Electrical
Issued 28 September 2001 Resolved
Properly install cable and support and retention for cables in EVAC room.
Condition: Unknown
Due 28 September 2001
Resolved 28 September 2001
Electrical
Issued 28 September 2001 Resolved
Install approved receptable outlets on port and stbd main weather deck or remove cable w/improper outlet.
Condition: Unknown
Due 28 September 2001
Resolved 28 September 2001
Electrical
Issued 28 June 2001 Resolved
On third deck permenantly mount outlet box per 46 CFR 111.81-1
Condition: Unknown
Due 28 June 2001
Resolved 28 June 2001
Navigation
Issued 28 June 2001 Resolved
Prover proper operation of steering alarms
Condition: Unknown
Due 28 June 2001
Resolved 28 June 2001
Fire Fighting
Issued 28 June 2001 Resolved
In aft pump/chiller room insert approved fire stop material into all deck penetrations per 46 CFR 72; NVIC 9-97
Condition: Unknown
Due 28 June 2001
Resolved 28 June 2001
Electrical
Issued 5 October 2000 Resolved
Stuffing tube missing from EMT office.
Condition: Unknown
Due 5 November 2000
Resolved 8 January 2001
Engineering
Issued 5 October 2000 Resolved
flame screens missing or inappropriate
Condition: Unknown
Due 5 November 2000
Resolved 8 January 2001
Electrical
Issued 5 October 2000 Resolved
Stuffing tube missing for camera wiring in Daycare Center.
Condition: Unknown
Due 5 November 2000
Resolved 8 January 2001
Electrical
Issued 5 October 2000 Resolved
Fan and electronic device not hardwired in Dimmer Room.
Condition: Unknown
Due 5 November 2000
Resolved 8 January 2001
Electrical
Issued 5 October 2000 Resolved
Stuffing tube requires repacking.
Condition: Unknown
Due 5 November 2000
Resolved 8 January 2001
Lifesaving
Issued 5 October 2000 Resolved
Liferaft had outdated retro and unsecured oars.
Condition: Unknown
Due 5 November 2000
Resolved 8 January 2001
Electrical
Issued 5 October 2000 Resolved
Wiring under console on Bridge not supported correctly.
Condition: Unknown
Due 5 November 2000
Resolved 8 January 2001
Electrical
Issued 5 October 2000 Resolved
electric outlet cover damaged.
Condition: Unknown
Due 5 November 2000
Resolved 8 January 2001
Electrical
Issued 5 October 2000 Resolved
Wing nuts used to attach battery wiring.
Condition: Unknown
Due 5 November 2000
Resolved 8 January 2001
Lifesaving
Issued 5 October 2000 Resolved
Life ring light in-operative.
Condition: Unknown
Due 5 November 2000
Resolved 8 January 2001
Lifesaving
Issued 21 June 2000 Resolved
Place proper back plate on exhaust fan in dimmer room
Condition: Unknown
Due 21 July 2000
Resolved 26 July 2000
Lifesaving
Issued 21 June 2000 Resolved
Replace oars on liferaft.
Condition: Unknown
Due 21 July 2000
Resolved 26 July 2000
Electrical
Issued 21 June 2000 Resolved
Ensure proper operation of all emergency lights onboard._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 21 July 2000
Resolved 26 July 2000
Lifesaving
Issued 21 June 2000 Resolved
Place proper plaque on General alarms systems.
Condition: Unknown
Due 21 July 2000
Resolved 26 July 2000
Accommodation/Occupational Safety
Issued 17 March 2000 Resolved
INSTALL FAN GUARDS ON FANS LOCATED IN THE PORT AND STBD AIR HANDLER ROOMS ON THE SECOND DECK.
Condition: Unknown
Due 20 March 2000
Resolved 20 March 2000
Engineering
Issued 17 March 2000 Resolved
CONDUCT OPERATIONAL TESTS OF THE OVERSPEED AND REVERSE POWER ON GENS AND MAIN PROPULSIONS ENGINES PRIOR TO GETTING UNDERWAY WITH PASSENGERS.
Condition: Unknown
Due 17 March 2000
Resolved 17 March 2000
Fire Fighting
Issued 17 March 2000 Resolved
ADJUST FIRE SCREEN DOOR ON SECOND DECK TO ENSURE PROPER CLOSURE AND GAP.
Condition: Unknown
Due 20 March 2000
Resolved 20 March 2000
Lifesaving
Issued 15 December 1999 Resolved
REPLACE RETRO TAPE ON THE STBD SIDE NEAR THE PILOT HOUSE.
Condition: Unknown
Due 15 December 1999
Resolved 15 December 1999
Unknown
Issued 15 December 1999 Resolved
REPAIR LEAKING FRESH WATER LINE IN THE FWD CHILLER ROOM.
Condition: Unknown
Due 15 December 1999
Resolved 15 December 1999
Engineering
Issued 15 December 1999 Resolved
REPAIR LEAKING FUEL INJECTOR ON THE BOW THRUSTER ENGINE.
Condition: Unknown
Due 15 December 1999
Resolved 15 December 1999
Electrical
Issued 24 September 1999 Resolved
REPAIR EMERGENCY GENERATOR PRIOR TO CARRTING PASSENGERS UNDERWAY.
Condition: Unknown
Due 24 September 1999
Resolved 30 September 1999
Electrical
Issued 1 July 1999 Resolved
INSTALL INSULATION ON EXPOSED ELECTRICAL WIRING IN MARTIX ROOM.
Condition: Unknown
Due 1 July 1999
Resolved 9 July 1999
Electrical
Issued 1 July 1999 Resolved
SECURE OIL LEAK AND REMOVE OIL FROM DECK FROM THE #2 GENERATOR.
Condition: Unknown
Due 1 July 1999
Resolved 9 July 1999
Lifesaving
Issued 17 March 1999 Resolved
REPLACE WORN WIRE TO AFT RESCUE BOAT WINCH FOR RESCUE BOAT.
Condition: Unknown
Due 17 April 1999
Resolved 24 March 1999
Electrical
Issued 17 March 1999 Resolved
REPLACE "TEMP" ELEC CORD TO SIGN ON THIRD DECK WITH APPROVED MARINE GRADE WIRE.
Condition: Unknown
Due 24 March 1999
Resolved 24 March 1999
Documentation
Issued 17 March 1999 Resolved
UPDATE FIRE SAFETY PLAN TO REFLECT APPROVED MODIFICATIONS BY MSC.
Condition: Unknown
Due 17 March 1999
Resolved 24 March 1999
Lifesaving
Issued 17 March 1999 Resolved
REPLACE MISSING/WORN RETRO TAPE ON LIFERINGS.
Condition: Unknown
Due 17 April 1999
Resolved 24 March 1999
Electrical
Issued 17 March 1999 Resolved
REPLACE MISSING/BROKEN GLOBES TO LIGHTS IN AFT STEERING VOIDS.
Condition: Unknown
Due 24 March 1999
Resolved 24 March 1999
Electrical
Issued 17 March 1999 Resolved
MARK EMERGENCY SHUT OFF WITH ARROW SHOWING THE SHOWING THE "CLOSED" POSITION TO THE FUEL SHUT DOWN.
Condition: Unknown
Due 24 March 1999
Resolved 24 March 1999
Construction/Loadline
Issued 9 December 1998 Resolved
INSPECT AND THEN REPACK ALL UNSATISFACTORY STUFFED MAINDECK PENETRATIONS.
Condition: Unknown
Due 10 December 1998
Resolved 29 December 1998
Lifesaving
Issued 9 December 1998 Resolved
RESTRING OR REPLACE LINE CAGE TO THE BUOYANT APPARATUS.
Condition: Unknown
Due 10 December 1998
Resolved 29 December 1998
Engineering
Issued 9 December 1998 Resolved
INSTALL CHAFFING PROTECTION AROUND FUEL LINE ON EMERGENCY GENERATOR.
Condition: Unknown
Due 12 December 1998
Resolved 16 December 1998
Fire Fighting
Issued 26 June 1998 Resolved
Prove proper operation of generator room CO2 alarm prior to getting underway.
Condition: Unknown
Due 31 July 1998
Resolved 31 July 1998
Navigation
Issued 26 June 1998 Resolved
Replace burned out light bulbs for steering alarms.
Condition: Unknown
Due 31 July 1998
Resolved 31 July 1998
Engineering
Issued 26 June 1998 Resolved
Prior to getting underway, vessel will repair High Water/Low Oil alarm on Bow Thruster.
Condition: Unknown
Due 31 July 1998
Resolved 31 July 1998
Electrical
Issued 26 June 1998 Resolved
Provide cover for battery boxes aft of pilothouse.
Condition: Unknown
Due 31 July 1998
Resolved 31 July 1998
Electrical
Issued 26 June 1998 Resolved
Replace 6 "E" lights that are not functional.
Condition: Unknown
Due 31 July 1998
Resolved 31 July 1998
Electrical
Issued 26 June 1998 Resolved
REPLACE COVER ON AIR CONDITIONER UNIT WITHIN THE PILOT HOUSE.
Condition: Unknown
Due 3 July 1998
Resolved 9 July 1998
Electrical
Issued 26 June 1998 Resolved
REPAIR ALL DAMAGED E-LIGHTS.
Condition: Unknown
Due 3 July 1998
Resolved 9 July 1998
Deck/Cargo
Issued 26 June 1998 Resolved
REPLACE ALL DAMAGED PRESSURE GAUGES ON LINES FWD AND AFT OF CHILLER ROOM.
Condition: Unknown
Due 3 July 1998
Resolved 9 July 1998
Electrical
Issued 26 June 1998 Resolved
REMOVE ALL DEAD END WIRES IN BETWEEN TOW AND VESSEL.
Condition: Unknown
Due 3 July 1998
Resolved 9 July 1998
Construction/Loadline
Issued 26 June 1998 Resolved
WELD ANGLE ON PORT CHILLER ROOM VENT.
Condition: Unknown
Due 3 July 1998
Resolved 9 July 1998
Fire Fighting
Issued 11 March 1998 Resolved
PROVIDE PORTABLE CO2 BOTTLES AT EMERGENCY GENERATOR ROOM WHILE FIXED SYSTEMIS BEING RECHARGED.
Condition: Unknown
Due 11 March 1998
Resolved 11 March 1998
Lifesaving
Issued 15 January 1998 Resolved
VESSEL NOT TO GET UNDERWAY WHILE LIFERAFTS ARE BEING SERVICED.
Condition: Unknown
Due 15 January 1998
Resolved 15 January 1998
Fire Fighting
Issued 17 December 1997 Resolved
PROVE OPERATION OF FIRE/BILGE PUMP.
Condition: Unknown
Due 17 December 1997
Resolved 17 December 1997
Electrical
Issued 17 December 1997 Resolved
REPAIR LOOSE WIRING IN WATER HEATER BEHIND FIRST DECK BAR.
Condition: Unknown
Due 19 December 1997
Resolved 19 December 1997
Accommodation/Occupational Safety
Issued 17 December 1997 Resolved
PROVIDE PLACARD FOR GENERAL ALARM.
Condition: Unknown
Due 19 December 1997
Resolved 19 December 1997
Fire Fighting
Issued 17 December 1997 Resolved
PROVIDE PACKING GLAND IN THROUGH DECK FITTING IN AFT CHILLER ROOM PORT SIDE.
Condition: Unknown
Due 17 December 1997
Resolved 17 December 1997
Electrical
Issued 17 December 1997 Resolved
MOUNT JUNCTION BOX IN COMPUTER ROOM AND FAN ROOM MAIN DECK.
Condition: Unknown
Due 17 December 1997
Resolved 17 December 1997
Electrical
Issued 17 December 1997 Resolved
REMOVE PORTABLE WIRING 3RD DECK CAGE._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 19 December 1997
Resolved 19 December 1997
Engineering
Issued 16 September 1997 Resolved
REPLACE OR REPAIR HIGH TEMP ALARM FOR BOW THRUSTER. VESSEL IS TO REMAIN DOCKSIDE UNTIL REPAIRS ARE COMPLETE.
Condition: Unknown
Due 30 September 1997
Resolved 18 September 1997
Construction/Loadline
Issued 16 September 1997 Resolved
REPLACE GASKET FOR THE WATER TIGHT HATCH TO THE FORWARD CHILLER ROOM.
Condition: Unknown
Due 17 September 1998
Resolved 21 September 1998
Electrical
Issued 16 September 1997 Resolved
HARDWIRE OR REMOVE EXTENSION CORD TO NEON LIGHT ON TOP OF PILOT HOUSE._x001C_
Condition: Unknown
Due 17 September 1998
Resolved 21 September 1998
Engineering
Issued 16 September 1997 Resolved
VESSEL IS NOT TO SAIL UNTIL #2 GENERATOR FUEL LINE IS REPLACED. ALSO A FUEL LINE ON TTHE STBD PROP ENGINE IS TO BE REPLACED._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 September 1998
Resolved 21 September 1998
Electrical
Issued 16 September 1997 Resolved
SECURE 2 BATTERY BOXES IN THE DIMMER ROOM.
Condition: Unknown
Due 17 September 1998
Resolved 21 September 1998
Fire Fighting
Issued 16 September 1997 Resolved
REPACK FIRESTOP PACKING AROUND SODA LINE LEADING OUT OF LIQUEUR ROOM AND BELOW THE SECOND DECK BAR.
Condition: Unknown
Due 17 September 1998
Resolved 21 September 1998
Navigation
Issued 16 September 1997 Resolved
VESSEL IS NOT TO SAIL DURING NIGHT HOURS OR DURING TIMES OF LIMITED VISIBILITY UNTIL ALL NON FUNCTIONAL LIGHTS ARE REPAIRED.
Condition: Unknown
Due 17 September 1998
Resolved 21 September 1998
Engineering
Issued 16 September 1997 Resolved
REMOVE PAINT FROM FUEL STEM THAT WILL ALLOW FREE MOVEMENT OF VALVE.
Condition: Unknown
Due 17 September 1998
Resolved 21 September 1998
Electrical
Issued 25 June 1997 Resolved
REPAIR "E" LIGHTS ON THE AFT THIRD DECK AND ON THE SECOND DECK AFT PORT SIDE.
Condition: Unknown
Due 25 June 1997
Resolved 25 June 1997
Navigation
Issued 25 June 1997 Resolved
REPLACE BULB OR MAKE REPAIRS TO PRIMARY STBD RUNNING LIGHT AND TO THE SECONDARY LIGHT FOR THE STERN.
Condition: Unknown
Due 25 June 1997
Resolved 25 June 1997
Electrical
Issued 31 March 1997 Resolved
PROVIDE EMERGENCY LIGHTING FOR EMBARCATION AREA.
Condition: Unknown
Due 24 April 1997
Resolved 16 April 1997
Engineering
Issued 31 March 1997 Resolved
PROVIDE MACHINERY GUARD ON BOW THRUSTER.
Condition: Unknown
Due 24 April 1997
Resolved 16 April 1997
Electrical
Issued 31 March 1997 Resolved
TEST REVERSE POWER RELAY ON #2 GENERATOR.
Condition: Unknown
Due 24 April 1997
Resolved 16 April 1997
Engineering
Issued 31 March 1997 Resolved
PROVE OPERATION OF #2 MAIN DIESEL ENGINE PRIOR TO GETTING UNDERWAY WITH PASSENGERS.
Condition: Unknown
Due 24 April 1997
Resolved 16 April 1997
Engineering
Issued 31 March 1997 Resolved
PROVIDE MEANS TO TEST #2 MDE LOW LUBE OIL AND OVERSPEED TRIP.
Condition: Unknown
Due 24 April 1997
Resolved 16 April 1997
Electrical
Issued 31 March 1997 Resolved
PROVIDE MEANS TO TEST HIGH JACKET WATER TEMP. ON #3 GENERATOR.
Condition: Unknown
Due 24 April 1997
Resolved 16 April 1997
Electrical
Issued 17 March 1997 Resolved
PROVIDE COVERS FOR BATTERY BOXES AFT OF PILOT HOUSE.
Condition: Unknown
Due 24 March 1998
Resolved 1 April 1998
Electrical
Issued 17 March 1997 Resolved
REPLACE 6 "E" LIGHTS THAT ARE NOT FUNCTIONAL.
Condition: Unknown
Due 24 March 1998
Resolved 1 April 1998
Engineering
Issued 17 March 1997 Resolved
BEFORE GETTING UNDERWAY, THE VESSEL WILL REPAIR HIGHWATER TEMP /LOW OIL ALARM ON BOW THRUSTER.
Condition: Unknown
Due 23 March 1998
Resolved 1 April 1998
Fire Fighting
Issued 17 March 1997 Resolved
PROVE PROPER OPERATION OF EMERGENCY GENERATOR'S ROOM FIXED CO2 ALARM. THIS WILL BE REPAIRED PRIOR TO GETTING UNDERWAY.
Condition: Unknown
Due 22 March 1998
Resolved 1 April 1998
Navigation
Issued 17 March 1997 Resolved
REPLACE BURNED OUT LIGHT BULDS FOR STEERING FAILURE ALARMS.
Condition: Unknown
Due 24 March 1998
Resolved 1 April 1998
Fire Fighting
Issued 6 March 1997 Resolved
REMOVE COMBUSTIBLE MATERIAL IN BETWEEN TUG AND VESSEL.
Condition: Unknown
Due 6 April 1997
Resolved 12 March 1997
Electrical
Issued 9 January 1997 Resolved
REPAIR FUEL OIL LEAK ON #3 GENERATOR'S RETURN FUEL OIL LINE.
Condition: Unknown
Due 9 February 1997
Resolved 11 February 1997
Fire Fighting
Issued 9 January 1997 Resolved
PROVIDE ADEQUATE CLEARANCE AROUND #12 FIRE STATION.
Condition: Unknown
Due 8 February 1997
Resolved 11 February 1997
Fire Fighting
Issued 20 June 1996 Resolved
PROVIDE TWO INCH CLEARANCE UNDER CO2 BOTTLE AT LIQUOR LOCKER.
Condition: Unknown
Due 20 July 1996
Resolved 11 July 1996
Lifesaving
Issued 14 March 1996 Resolved
VESSEL NOT TO BOARD NO MORE THAN 1500 TOTAL PERSONS. VESSEL TO PROCURE LIFEFLOAT TO OBTAIN 1540 TOTAL PERSONS ON BOARD AS PER COI.
Condition: Unknown
Due 14 March 1996
Resolved 14 March 1996
Electrical
Issued 14 March 1996 Resolved
MOUNT EMERGENCY LIGHT ABOVE CO2 BOTTLES MAIN DECK FORWARD.
Condition: Unknown
Due 20 April 1996
Resolved 30 April 1996
Engineering
Issued 14 March 1996 Resolved
INSTALL EMERGENCY FUEL OIL SHUTDOWN VALVE TO BOW THRUSTER POWER UNIT.
Condition: Unknown
Due 20 April 1996
Resolved 30 April 1996
Fire Fighting
Issued 4 January 1996 Resolved
PROVIDE ADAPTERS FOR FIRE HOSES.
Condition: Unknown
Due 4 January 1996
Resolved 4 January 1996
Electrical
Issued 4 January 1996 Resolved
PROVIDE RUBBER MAT FOR EMERGENCY GENERATOR ROOM.
Condition: Unknown
Due 4 January 1996
Resolved 4 January 1996
Fire Fighting
Issued 4 January 1996 Resolved
PROPERLY MOUNT FIRE EXTINGUISHERS AT FIRST AND SECOND DECK BARS AFT AND IN THE ENGINEROOM IN BETWEEN THE GENERATORS.
Condition: Unknown
Due 4 January 1996
Resolved 4 January 1996
Navigation
Issued 4 January 1996 Resolved
REPAIR ANCHOR LIGHT FOR PROPER OPERATION.
Condition: Unknown
Due 4 January 1996
Resolved 4 January 1996
Electrical
Issued 4 January 1996 Resolved
PROVIDE LOUDER AUDIBLE ALARMS FOR MAIN GENERATORS.
Condition: Unknown
Due 4 January 1996
Resolved 4 January 1996
Engineering
Issued 2 October 1995 Resolved
PROVIDE REMOTE FUEL OIL CUT OFF VALVE IN BOW THRUSTER ROOM.
Condition: Unknown
Due 2 October 1995
Resolved 2 October 1995
Fire Fighting
Issued 2 October 1995 Resolved
PROVIDE A-60 INSULATION IN 2ND DECK AFT LIFE JACKET LOCKER.
Condition: Unknown
Due 2 October 1995
Resolved 2 October 1995
Electrical
Issued 2 October 1995 Resolved
PROVIDE PROPER WIRE TIES THROUGHOUT VESSEL.
Condition: Unknown
Due 2 October 1995
Resolved 2 October 1995
Electrical
Issued 2 October 1995 Resolved
PROVIDE WATERPROOF COVERS OVER DISTRIBUTION PANEL ON MAIN DECK.
Condition: Unknown
Due 2 October 1995
Resolved 2 October 1995
Fire Fighting
Issued 2 October 1995 Resolved
PROVIDE REMOTE CO2 VENTILATION MANUAL SHUTDOWN AND INSTRUCTIONS.
Condition: Unknown
Due 2 October 1995
Resolved 2 October 1995
Fire Fighting
Issued 2 October 1995 Resolved
LABEL FIRE ALARM BELLS.
Condition: Unknown
Due 2 October 1995
Resolved 2 October 1995
Electrical
Issued 11 September 1995 Resolved
REPAIR #2 GENERATOR MAIN BREAKER.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Fire Fighting
Issued 11 September 1995 Resolved
PROPERLY INSTALL AND WIRE SPRINKLER PUMP AIR VALVE COMPRESSOR.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Electrical
Issued 11 September 1995 Resolved
PROPERLY HANG ALL WIRING IN EMERGENCY GENERATOR COMPARTMENT.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Fire Fighting
Issued 11 September 1995 Resolved
REPAIR FIRE DAMPER 3RD DECK PORT SIDE AND FORWARD FOR COMPLETE CLOSURE.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Lifesaving
Issued 11 September 1995 Resolved
PROPERLY LABEL ALL RING BUOYS.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Fire Fighting
Issued 11 September 1995 Resolved
READJUST FIRE DOOR ON 2ND DECK AFT FOR PROPER CLOSURE.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Electrical
Issued 11 September 1995 Resolved
REPAIR AND MAKE AVAILABLE FOR TESTING ALL SAFETY ALARMS AND SHUDOWNS ON MAIN ENGINES AND GENERATORS.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Documentation
Issued 11 September 1995 Resolved
PROVIDE NEW STABILITY LETTER BASED ON DEADWEIGHT SURVEY CONDUCTED 07SEP95.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Fire Fighting
Issued 11 September 1995 Resolved
PROPERLY LABEL ALL FIRE HOSES & AXES.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Navigation
Issued 11 September 1995 Resolved
ADD EMERGENCY STEERING OPERATING PROCEDURES TO WEEKLY DRILL LIST.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Fire Fighting
Issued 11 September 1995 Resolved
READJUST FIRE DOOR ON 3RD DECK FOWARD OF ELEVATOR FOR PROPER CLOSURE.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Fire Fighting
Issued 11 September 1995 Resolved
PROPERLY NUMBER ALL PORTABLE FIRE EXTINGUISHERS.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Unknown
Issued 11 September 1995 Resolved
PROVIDE APPROVED PLANS FOR MODIFICATIONS TO PASSENGER ELEVATOR, DAY CARE ROOM, CO2 FIRE SUPPRESSION SYSTEM FOR BAR STORAGE ROOM, WIRING INSTALLATIONFOR HEATING SYSTEM.
Condition: Unknown
Due 11 September 1995
Resolved 11 September 1995
Fire Fighting
Issued 29 March 1995 Resolved
PERFORM ALL DRILLS AS SET FORTH IN 46 CFR SUBCHAPTER H IN PRESENCE OF MARINE INSPECTOR.
Condition: Unknown
Due 29 March 1995
Resolved 29 March 1995
Fire Fighting
Issued 29 March 1995 Resolved
PERFORM ANNUAL TESTS AND INSPECTIONS OF ALL FIXED AND PORTABLE CO2 FIRE EXTINGUISHING SYSTEMS.
Condition: Unknown
Due 29 March 1995
Resolved 29 March 1995
Electrical
Issued 25 October 1994 Resolved
PROVE PROPER AUTOMATIC SWITCHING OF ELECTRICAL LOAD TO EMERGENCY ELECTRICALSYSTEM. SYSTEM TO BE PROVED OPERATIONAL AND THIS ITEM CLEARED PRIOR TO EMBARKING PASSENGERS._x001C_ _x001C_
Condition: Unknown
Due 15 November 1994
Resolved 21 November 1994
Documentation
Issued 30 April 1993 Resolved
NO PASSENGERS ALLOWED ON BOARD VESSEL UNITL AN APPROVED STABILITY LETTER ISISSUED BY MSC._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 30 April 1993
Resolved 30 April 1993
Documentation
Issued 20 March 1992 Resolved
PRIOR TO 20APR92, PROVIDE THE COGNIZANT OCMI WITH APPROVED PLANS OR LETTER OF APPROVAL FROM CG MARINE SAFETY CENTER, FOR THE MODIFICATION OF THE SEA CHEST AND BOW THRUSTER SHELL CONNECTIONS, ALSO PROVIDE APPROVED DRAWINGS FOR THE NEW TRANSDUCER INSTALLATION AND SHELL CONNECTION.
Condition: Unknown
Due 20 March 1992
Resolved 20 March 1992
Documentation
Issued 16 January 1992 Resolved
WHEN THE VESSEL IS DOCKSIDE WITH PASSENGERS ON BOARD AND ELECTRICAL POWER IS SUPPLIED FROM SHORE POWER, THE MINIMIUM CREW SHALL BE: 1-MASTER,_x001C_ 1-UNLICENSED QUALIFIED ENGINEER, AND 3-DECKHANDS_x001C_ THIS MANNING LEVEL IS VALID THRU 31MAR92.
Condition: Unknown
Due 16 January 1992
Resolved 16 January 1992
Construction/Loadline
Issued 28 October 1991 Resolved
PROVIDE ADDITIONAL STRUCTURAL MEMBER UNDER CUT-OUT AREA IN DECK BEAM, IN WAY OF NEW POTABLE WATER LINE IN #4 AND #5 VOIDS.
Condition: Unknown
Due 28 October 1991
Resolved 28 October 1991
Lifesaving
Issued 26 April 1991 Resolved
PROVIDE ON BOARD CG APPROVED INFLATABLE LIFE RAFTS OR INFLATABLE BOUYANT APPARATUS TO ACCOMMODATE 10% OF MAXIMUM PERSONS ALLOWED ON BOARD, AS_x001C_ OUTLINED IN ST. LOUIS, OCMI LETTER DATED 11FEB91.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Unknown
Issued 26 April 1991 Resolved
PROVIDE A MEANS OF INTERIM MANEUVERABILITY ENHANCEMENT THAT IS ACCEPTABLE TO THE OCMI
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Unknown
Issued 26 April 1991 Resolved
REMOVE THE HOT WATER HEATER FROM THE EMERGENCY GENERATOR ROOM.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Electrical
Issued 26 April 1991 Resolved
SHOW PROOF THAT RUBBER MATS FOR EMERGENCY AND PUMP ROOM SWITCH BOARDS ARE CONSTRUCTED WITH NON-CONDUCTING TYPE OF MATERIAL, OR REPLACE MATS.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Electrical
Issued 26 April 1991 Resolved
VESSEL IS RESTRICTED TO DAYLIGHT OPERATION ONLY, UNTIL EMERGENCY LIGHTING IS OPERATIONAL.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Electrical
Issued 26 April 1991 Resolved
INSTALL ELECTRICAL PANEL BOX COVERS IN ALL AREAS ACCESSIBLE TO PASSENGERS. IF ELECTRICAL WORK CONTINUES WHILE PASSENGERS ARE ON BOARD, THE WORK AREA SHALL BE ROPED OFF, TO KEEP THE PASSENGERS AT A SAFE DISTANCE.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Documentation
Issued 26 April 1991 Resolved
PRIOR TO OPERATION OF THE VESSEL WITH THE SUBSTITUTE UNLICENSED ENGINEER, THEY SHALL DEMONSTRATE THEIR KNOWLEDGE AND ABILITY TO THE SATISFACTION COGNIZANT OCMI.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Engineering
Issued 26 April 1991 Resolved
INSTALL PRESSURE RELIEF VALVE ON THE AIR RECEIVER ON THE THIRD DECK UNDER THE PILOT HOUSE.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Electrical
Issued 26 April 1991 Resolved
WHILE THE VESSEL IS UNDERWAY OR HAS PASSENGERS ON BOARD, THE OILER SHALL REMAIN IN THE NEAR VICINITY OF THE EMERGENCY GENERATOR AND BE CAPABLE OF PROVIDING POWER TO THE EMERGENCY CIRCUITS WITHIN 01 MINUTE OF LOSING POWER.THIS SHALL REMAIN IN EFFECT UNTIL THE AUTOMATIC STARTER IS INSTALLED.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Fire Fighting
Issued 26 April 1991 Resolved
INSTALL A PRESSURE GAUGE ON THE DISCHARGE SIDE OF THE FIRE PUMP.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Engineering
Issued 26 April 1991 Resolved
INSTALL FUEL SHUT-OFF VALVE IN THE SUPPLY PIPING OF THE EMERGENCY GENERATORAT THE FUEL TANK.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Fire Fighting
Issued 26 April 1991 Resolved
INSTALL APPROVED MAGNETIC HOLDING DEVICES ON ALL FIRE SCREEN DOORS. ALL_x001C_ FIRE SCREEN DOORS SHALL REMAIN CLOSED WHILE PASSENGERS ARE ON BOARD UNTIL THE HOLDING DEVICES ARE INSTALLED.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Electrical
Issued 26 April 1991 Resolved
INSTALL MISSING COVERS ON SWITCH BOXES, JUNCTION BOXES, AND RECEPTACLE BOXES.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Electrical
Issued 26 April 1991 Resolved
INSTALL APPROVED FUEL HOSES ON EMERGENCY GENERATOR FUEL SYSTEM.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Electrical
Issued 26 April 1991 Resolved
LABEL ALL CIRCUIT BREAKERS IN ALL ELECTRICAL DISTRIBUTION, POWER, AND LIGHTING PANELS.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Unknown
Issued 26 April 1991 Resolved
PROVIDE AN EFFECTIVE BOW THRUSTER OR EQUIVALENT MEANS OF MANEUVERABILITY ENHANCEMENT WHICH IS CAPABLE OF BEING OPERATED FROM THE EMERGENCY SOURCE OFPOWER.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Construction/Loadline
Issued 26 April 1991 Resolved
MAKE ALL BULKHEAD AND DECK PENETRATIONS WATER AND SMOKE/FLAME TIGHT, USING APPROVED SEALANT. SEALANT SHALL MAINTAIN THE SAME OR GREATER INTEGRITY AS THE BULKHEAD OR DECK FIRE RATING, (IE. A-60 BULKHEAD WILL REQUIRE A-60 SEALANT).
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Accommodation/Occupational Safety
Issued 26 April 1991 Resolved
INSTALL DRAFT STOPS IN THE VENTILATION SYSTEM AS REQUIRED BY OCMI, PORT ARTHUR TX, LETTER H2-10170,
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Fire Fighting
Issued 26 April 1991 Resolved
AS PER OCMI ST. LOUIS LETTER 16710 OF 18 APRIL 1991, INSTALL A FIXED CO2 FIRE EXTINGUISHING SYSTEM WITH 100 POUND CAPACITY IN THE EMERGENCY GENERATOR ROOM.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Electrical
Issued 26 April 1991 Resolved
PROVIDE ACID RESISTANT BATTERY BOX FOR EMERGENCY GENERATOR STARTING BATTERY.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Electrical
Issued 26 April 1991 Resolved
PROVIDE SPRAY SHIELD UNDER PIPING RUN, OVER PUMP ROOM SWITCHBOARD.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Electrical
Issued 26 April 1991 Resolved
INSTALL ELECTRICAL CABLE RETENTION STRAPS IN ALL WIRE RUNS, NOT TO EXCEED 2FEET ON VERTICAL RUNS, AND 8 FEET ON HORIZONTAL RUNS.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Lifesaving
Issued 26 April 1991 Resolved
PROVIDE ON THE PASSENGER BARGE, TWO CG APPROVED RESCUE BOATS, OUTFITTED WITH THE REQUIRED EQUIPMENT AND LAUNCHING DEVICE AS OUTLINED IN ST. LOUIS, OCMI LETTER DATED 11FEB91.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991
Engineering
Issued 26 April 1991 Resolved
INSTALL BILGE ALARMS IN ALL COMPARTMENTS BELOW THE MAIN DECK, WITH INDICATORS IN THE PILOT HOUSE.
Condition: Unknown
Due 26 April 1991
Resolved 26 April 1991

Source. US Coast Guard records through 23 August 2026, retrieved 5 September 2026. Vessels the Coast Guard classes as Barge or Towing Vessel. Coverage and known gaps.

Maury does not score, rate, or grade vessels. What Maury does not do · Glossary · Correct a record.