Records from 2004 to 2026. Most recent: inspection, 29 January 2026.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 18 September 2025
Resolved
A device must be provided to automatically shut down power ventilation serving the protected spaceprior to release of the extinguishing agent into the space. Engine Room Halon fixed FF system did not shut down STBD Main Engine and #3 generator when tested.
46 CFR 118.410(b)(10)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 14 January 2026
Resolution: Attended vsl and witness satisfactory test of generator.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 18 September 2025
Resolved
Vessels contracted for, on, or after July 1, 1961 which carry more than 150 passengers shall meet the requirements of subpart 72.05 of subchapter H of this chapter. Rugs and carpets shall not pass throgh doorways. X4 class B doors on main deck and X2 class B doors on Casino Deck have improper carpet running under.
46 CFR 177.10-5(a)(Old T)
46 CFR 72.05-25(c)(5)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 October 2025
Resolved 14 January 2026
Resolution: Attested to repair.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 18 September 2025
Resolved
Vessels contracted for, on, or after July 1, 1961 which carry more than 150 passengers shall meet the requirements of subpart 72.05 of subchapter H of this chapter. All doors except those that are kept normally closed shall be of a type which are capable of release from a position at the door and control station. Multiple doors on casino and main deck did not close when released from control station.
46 CFR 177.10-5(a)(OLD T)
46 CFR 72.05-25(b)(9)(ii)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 October 2025
Resolved 14 January 2026
Resolution: Attested to reapir.
07 - Fire Safety › N/A - No Subsystem › Fire control plan
Issued 18 September 2025
Resolved
All observed unsafe practices, fire hazards, and other hazardous situations must be corrected and in a satisfactory condition. According to the approved fire control plan, the exit signs are to be lighted. During blackout, multiple signs did not illuminate.
46 CFR 115.830
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 October 2025
Resolved 14 January 2026
Resolution: Rectified def.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 26 March 2025
Resolved
A veessel must be operated in accordance with applicable laws and regulations and in such a manner as to afford adequate precaution against hazards that might endanger the vessel and persons being transported. MI attested to temporary repairs in lazzarette operational tests sat; to include, NDT of double plate, high level bilge alarms in engie room and lassarette and a functional test of lazzarette bilge suction. as a precautionary measure OCMI requires roving watch logged in bridge log book every 30 minutes to include lazarette rounds while underway with passengers. 46 CFR 122.100 - 705 (c) - 31 MAR 2025 (MIs to revisit vessel on that date)
Action required: 705 - Other - as specified
Resolved 14 May 2025
Resolution: Vessel O/O had vessel go to emergency drydock at Colonna Shipyard Norfolk Virginia for damage assessment and permanent repairs. Shipyard affected repairs on pitted, holed and wasted plate along port side aft keel cooler. Repairs effectively made & tested.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 18 September 2024
Resolved
Starboard Main Enggine Fuel Oil send line at multi-way valve at Racor Filter is chaffing against the deck plate. 46 CFR 119.455(b)(2)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 7 October 2024
Resolution: Recieved objective evidence from vessel for the deficiency being rectified. See narrative/documents.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 18 September 2024
Resolved
No. 3 Diesel Generator Crankcase/Valve Cover Re-breather hose chafing against turbo charger. 46 CFR 115.800(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 7 October 2024
Resolution: Recieved objective evidence from vessel for the deficiency being rectified. See narrative/documents.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 18 September 2024
Resolved
Port Main Engine Racor Filter portective bowl is missing. 46 CFR 119.455(b)(5)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 7 October 2024
Resolution: Recieved objective evidence from vessel for the deficiency being rectified. See narrative/documents.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 18 September 2024
Resolved
No. 1 Diesel Generator found with collant and oil leaks. Coolant leak found at bottom of expansion tank agains block. and oil leaks around oil sump. 46 CFR 115.800(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 11 October 2024
Resolution: recieved generator servicing report
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 18 September 2024
Resolved
Lifering bouy lights need battery, one was found broke. line needs to be dark UV Protective. 46 CFR 117.70(d)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 7 October 2024
Resolution: Recieved objective evidence from vessel for the deficiency being rectified. See narrative/documents.
10 - Safety of Navigation › N/A - No Subsystem › Magnetic compass
Issued 18 September 2024
Resolved
Vessels operating at night magnetic compast must be luminated. battery was dead in compass light. 46 CFR 121.402(c)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 7 October 2024
Resolution: Recieved objective evidence from vessel for the deficiency being rectified. See narrative/documents.
09 - Working and Living Conditions › 092 - Working Conditions › Holds and tanks safety
Issued 18 September 2024
Resolved
Soda Machine CO2 Bottle was found not secured to approved bracket for safety. Gally Stbd Side. 36 CFR 115.830(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 7 October 2024
Resolution: Recieved objective evidence from vessel for the deficiency being rectified. See narrative/documents.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 18 September 2024
Resolved
Class A fireboundries must that consist of windows need to have clamps to retain the window. Multiple window clips not properly connected or missing rubber stoppers. 46 CFR 116.433(c)(i)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 7 October 2024
Resolution: Recieved objective evidence from vessel for the deficiency being rectified. See narrative/documents.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 18 September 2024
Resolved
VESSEL HAS AN ATRIUM IN THE AFT PORTION OF THE MAIN DECK UP TO THE 3RD DECK AND THE SMOKE EXTRACTION SYSTEM DOES NOT WORK AS DESIGNED AND APPROVED. VESSEL MUST FIX SYSTEM AND PROVE PROPER OPERATION TO A COAST GUARD MARINE INSPECTOR. THIS SYSTEM MUST MEET THE REGULATION BY EXHAUSTING THE ENTIRE VOLUME OF THE SPACE IN 10 MIN. NO PASSENGERS IN THE ATRIUM UNTIL FIXED AND CLEARED.
46 CFR 116.440
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 7 May 2025
Resolution: Cleared as it cannot be determined that the vessel was built to new K standards that require smoke extraction in atriums.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 6 May 2024
Resolved
e general construction of the vessel must be such as to minimize fire hazards insofar as it is reasonable and practicable. Structural Fire Protection in bow thruster space is missing / damaged. Vessel shall repair / renew SFP in accordance with approved plan. Vessel shall lockout bow thruster provide proof of lockout and not operate until SFP is repaired and inspected by CG Marine Inspector.
Action required: 705 - Other - as specified
Due 16 July 2024
Resolved 18 July 2024
Resolution: SFP installed overhead.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 11 October 2023
Resolved
ALL ELECTRICAL INSTALLATIONS SHALL BE TO THE SATISFACTION OF THE [name withheld] SHORE-TIE CABLE.
46CFR183.01-15(a)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 October 2023
Resolution: Accepted O/O photos showing resolution.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 11 October 2023
Resolved
ALL ELECTRICAL INSTALLATIONS SHALL BE TO THE SATISFACTION OF THE [name withheld] WIRES IN THE FOLLOWING SPACE;
FUEL TANK PORT SIDE VOID
NO. 1 SSDG
46CFR183.01-15(a)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 October 2023
Resolution: Accepted O/O photos showing resolution.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 11 October 2023
Resolved
EXCEPT AS OTHERWISE PROVIDED IN THE SECTION, ALL VESSELS SHALL BE PROVIDED WITH NOT LESS THAN 02 AVENUES OF ESCAPE FROM ALL GENERAL AREAS ACCESSIBLE TO THE PASSENGERS OR WHERE THE CREW MAY BE EMPLOYED. CLEAR DEBRIS IN WAY OF VERTICAL ESCAPE FROM ENGINEER QUARTER.
46CFR177.15-1(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 October 2023
Resolution: Accepted O/O photos showing resolution.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 11 October 2023
Resolved
CYLINDERS MUST ALWAYS BE SECURED AND WHEN NOT IN USE MUST BE STORED IN A RACK IN AN UPRIGHT POSITION. PROPERLY SECURE ALL SODA MACHINE COMPRESSED GAS BOTTLES.
46CFR147.60
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 October 2023
Resolution: Accepted O/O photos showing resolution.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 11 October 2023
Resolved
FOR PORTABLE FIRE EXTINGUISHERS, THE INSPECTIONS, MAINTENANCE PROCEDURES, AND HYDROSTATIC PRESSURE TESTS... SHALL BE IN ACCORDANCE WITH NFPA 10, WITH THE FREQUENCY SPECIFIED BY NFPA 10. 02 FIRE EXTINGUISHERS IN BOW THRUSTER COMPARTMENT WERE LAST SERVICED IN 2022.
46CFR115.810(b)(1)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 October 2023
Resolution: Accepted O/O photos showing resolution.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 11 October 2023
Resolved
DOORS, OTHER THAN THOSE WHICH ARE NORMALLY LOCKED...SHALL BE OF THE SELF-CLOSING TYPE CAPABLE OF CLOSING AGAINST A 3.5 DEGREE LIST. PORT MAIN DECK CREW DOOR DID NOT CLOSE SECURELY / LATCH.
46CFR72.05(b)(9)(i)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 October 2023
Resolution: Accepted O/O photos showing resolution.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 25 May 2023
Resolved
The general construction of the vessel shall be such as to minimize fire hazards insofar as reasonable and practicable.
Self closing door on the 3rd mid deck stbd side, galley, and 2nd floor aft stbd side did not close all the way.
Old T 46CFR177.10-5
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 26 May 2023
Resolved 26 May 2023
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 25 May 2023
Resolved
The intent of this part is to insure that each vessel is provided with safe, readily available and sufficient firefighting equipment of the type necessary to extinguish any fires which are likely to be encountered in normal operation.
The nozzle on the portable fire extingusher on main deck stbd side all the way forward is broken.
Old T 46CFR181.01-5
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 9 June 2023
Resolved 26 May 2023
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 25 May 2023
Resolved
The general construction of the vessel shall be such as to minimize fire hazards insofar as reasonable and practicable.
The self closing door on stbd side by galley space (main deck) is missing tumbler and door wont close properly. Repair prior to carrying passengers.
Old T 46CFR177.10-5
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 26 May 2023
Resolved 26 May 2023
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 25 May 2023
Resolved
The intent of this part is to insure that each vessel is provided with safe, readily available and sufficient firefighting equipment of the type necessary to extinguish any fires which are likely to be encountered in normal operation.
The portable fire extinguisher by the beer and champagne bar on the main deck is missing bracket.
Old T 46CFR181.01-5
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 9 June 2023
Resolved 26 May 2023
07 - Fire Safety › N/A - No Subsystem › Fire-dampers
Issued 19 July 2022
Resolved
Provision shall be made by means of plugs, covers, etc., to prevent the admission of air into the space protected. Galley ventilation damper was unable to close.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 22 July 2022
Resolved 21 July 2022
Resolution: Fire damper was recieved required maintenance so that it was able to close rather than being locked open.
08 - Alarms › N/A - No Subsystem › Fire alarm
Issued 19 July 2022
Resolved
The fire detection and alarm system must be so arranged and installed that the presence of a fire in any of the protected spaces will be automatically registered visibly and audibly in the pilothouse or fire control station. Smoke alarm panel on bridge does not indicate audible alarm from fire detection system.
Condition: Improper Installation
Action required: 60 - Rectify deficiencies prior to movement
Due 29 July 2022
Resolved 22 July 2022
Resolution: Vessel is required 4 additional crew members for roaming fire watch while vessel is underway until def can be rectified.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 19 July 2022
Resolved
Machinery and equipment installed on each vessel must be suitable for the vessel and its operation and for the purpose intended. The Piping for hot water heater was not properly supported or secured.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 August 2022
Resolved 10 August 2022
Resolution: Pipes fastend to bulkhead with bracket
09 - Working and Living Conditions › 092 - Working Conditions › Stowage of cargo
Issued 19 July 2022
Resolved
Cylinders shall be securely fastened and supported, and where necessary protected against injury. Compressed gas cylinders were not properly secured.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 August 2022
Resolved 10 August 2022
Resolution: cylinders secured and stowed accordingly.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 19 July 2022
Resolved
all vessel shall be provided with bilge pumps in accordance with Table 182.25-10(a). Bilge pumps were not meeting 50 GPM rate requirement.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 August 2022
Resolved 10 August 2022
Resolution: bilge piping cleared of obstuction that was causing discharge rate to lower.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 19 July 2022
Resolved
boiler and galley uptakes, and similar sources of ignition shall be kept clear of and suitably insulated from any woodwork or other combustible matter. Galley cooking hood contains excess grease and requires cleaning.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 August 2022
Resolved 10 August 2022
Resolution: Galley hood degreased
09 - Working and Living Conditions › 092 - Working Conditions › Safe means of access
Issued 19 July 2022
Resolved
No means shall be provided for locking doors giving access to either of the 2 required means of escape. Stbd side engine room escape hatch was found to be stuck shut and without proper structural life protection
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 August 2022
Resolved 10 August 2022
Resolution: escape hatch unstuck and in full operable condition.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 19 July 2022
Resolved
Doors, other than those which are normally locked, such as from staterooms, fan rooms, lockers, etc., shall be of the self-closing type capable of closing against a 31/2 degree list, Fire doors on main deck leading to the dining room were found not to be self-closing.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 August 2022
Resolved 10 August 2022
Resolution: Door hinges tightened to close fully on their own
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 19 July 2022
Resolved
Adequate emergency lighting automatically actuated upon failure of the main lighting system shall be fitted along the line of escape. Rice pantry emergency lighting found inop and Exit sign in egress route, second deck found inop.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 August 2022
Resolved 10 August 2022
Resolution: light bulb replaced
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 19 July 2022
Resolved
Penetrations in A-Class fire control boundaries for electrical cables, pipes, trunks, ducts, etc. must be constructed to prevent the passage of flame and smoke for one hour. In addition, the penetration must be designed or insulated so that it will withstand the same temperature rise limits as the boundary penetrated. Fire stop should be replaced in the following locations: fwd bulkhead laz, port side engine room aft bulkhead, and ceiling in DC locker.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 August 2022
Resolved 10 August 2022
Resolution: Fire stop placed in all penetrations that needed it
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 26 March 2021
Resolved
04 DEFICIENCIES BELOW CORRESPOND TO THE FOLLOWING REGULATION: VESSELS THAT CARRY MORE THAN 150 PASSENGERS MUST COMPLY WITH THE REQUIREMENTS OF SUBCHAPER H.
PROVIDE PLANS FOR ATRIUM SPRINKLER SYSTEM.
46 CFR 177.10-5(a)
OLD T
Action required: 705 - Other - as specified
Due 31 May 2021
Resolved 21 July 2022
Resolution: sprinkler system tested and approved
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 26 March 2021
Resolved
VESSELS THAT CARRY MORE THAN 150 PASSENGERS MUST COMPLY WITH THE REQUIREMENTS OF SUBCHAPER H.
FIRE STOPS MISSING IN MULTIPLE FIRE BOUNDARY FEED THROUGH LOCATIONS.
46 CFR 177.10-5(a)
OLD T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 April 2021
Resolution: Complete
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 26 March 2021
Resolved
VESSELS THAT CARRY MORE THAN 150 PASSENGERS MUST COMPLY WITH THE REQUIREMENTS OF SUBCHAPER H.
ADJUST SPRING ON DOUBLE FIRE DOORS LEADING TO ATRIUM ON THE THIRD DECK.
46 CFR 177.10-5(a)
OLD T
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 April 2021
Resolution: Complete
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 26 March 2021
Resolved
VESSELS THAT CARRY MORE THAN 150 PASSENGERS MUST COMPLY WITH THE REQUIREMENTS OF SUBCHAPER H.
REMOVE SUPPLIES STORED IN EGRESS ROUTE ON SECOND DECK LEADING TO ATRIUM
46 CFR 177.10-5(a)
OLD T
Action required: 705 - Other - as specified
Due 31 May 2021
Resolved 21 July 2022
Resolution: Items stored in egress route have been cleared out.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 26 March 2021
Resolved
NAMEPLATES SHALL BE PROVIDED FOR EACH PIECE OF EQUIPMENT
TO INDICATE CLEARLY ITS SERVICE.
MULTIPLE SWITCHBOARDS WERE NOT ACCURATELY LABELED.
46 CFR 111.30-1(h)
OLD J
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 12 April 2021
Resolution: Complete
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 26 March 2021
Resolved
SIDES OF SWITCHBOARDS SHALL BE MADE INACCESSIBLE TO OTHER THAN QUALIFIED PERSONS.
DEADFRONT OF SWITCHBOARD LOCATED BY GALLEY STBD STORAGE ROOM ON THE MAIN DECK BY THE STAIRS WAS MISSING SCREWS, ALLOWING IT TO BE OPENED.
46 CFR 111.30-1(c)
OLD J
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 12 April 2021
Resolution: Complete
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 26 March 2021
Resolved
DRY PIPE VERTICAL EXHAUSTS ARE PERMISSIBLE IF SUITABLY INSULATED.
LAGGING MISSING ON #1 AND #2 GENERATOR EXHAUST PIPE
46 CFR 182.15-15(a)(1)
OLD T
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 12 April 2021
Resolution: Complete
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 26 March 2021
Resolved
DRIP PANS FITTED WITH FLAME SCREENS MAY BE REQUIRED UNDER FUEL STRAINERS OTHER THAN THOSE MOUNTED ON THE ENGINE.
#2 GENERATOR ON THE STBD SIDE, MISSING FUEL STRAINER BOWL.
46 CFR 182.20-40(b)(5)
OLD T
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 12 April 2021
Resolution: Complete
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 26 March 2021
Resolved
PRESSURE VESSELS REQUIRE INSPECTION IAW REGULATIONS OF SUBCHAPTER F.
PRESSURE VESSEL INSPECTION OVERDUE.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 12 April 2021
Resolution: Complete
01 - Certificates & Documentation › 011 - Ships Certificates › USCG Certificate of Documentation (COD)
Issued 24 July 2019
Resolved
Vessel COD expired November 30, 2018. Vessel provided documentation an application was submitted December 10, 2018 but never received COD from NVDC. NVDC declined COD request due to "lien on vessel". Vessel must provide a valid a COD prior to carrying passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 29 July 2019
Resolution: Received satisfactoy proof of COD renewal application and confirmation from NVDC.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 24 July 2019
Resolved
SSDG #1 and STRBD Main engine failed to shutdown during testing of the fixed fire extinguishing system. MI must witness proper shutdown of all engines during testing of fixed fire extinguishing system.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 29 July 2019
Resolution: Witnessed satisfactory test of fixed fire extinguishing system.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 24 July 2019
Resolved
Vessel failed to pump out bilge water from #3 void space. MI must witness proper operation of the bilge pump and bilge system.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 25 July 2019
Resolution: MI witnessed satisfactory test of the bilge pump. Pumped out water from lazarette and #3 void space.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 24 July 2019
Resolved
Vessel's audible and visual alarms and space identification for high water bilge alarms did not work. MI must witness proper operation of the vessel's high water bilge alarm system.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 25 July 2019
Resolution: MI witnessed satisfactory test of the high water bilge alarm in all required spaces.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 24 July 2019
Resolved
Insulation of deck hatch cover leading into the bow thruster space is secured with black electrical tape. Properly install insulation material.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 July 2019
Resolution: Vessel renewed insulation on all deck hatch covers located within machinery spaces.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 24 July 2019
Resolved
Found dead end electrical wires in multiple spaces: 1) forward port bow open deck, 2) #3 void space. Remove or properly enclose all dead end wires.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 5 August 2019
Resolution: Dead end wires removed.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 24 July 2019
Resolved
Found many window retention clips are loose and improperly maintained for window installation. Properly secure all windows and tighten all loose window retention clips.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 5 August 2019
Resolution: Windo retention clips installed.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 24 July 2019
Resolved
Found 26 adult life jackets saturated with hydraulic oil. Found 11 child life jackets not in serviceable condition. Destroy and replace life jackets. Passenger count reduced accordingly until life jackets are replaced.
Action required: 705 - Other - as specified
Resolved 25 July 2019
Resolution: Life jackets destroyed. Replaced all destroyed life jackets and placed onboard the vessel.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 24 July 2019
Resolved
Repair/replace grab line on ring buoy on stowed on forward port bow open deck and properly attach float light to ring buoy.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 July 2019
Resolution: repaired grab line and properly attached float light to ring buoy.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 24 July 2019
Resolved
Repair/replace corroded clip on ring buoy located of 3rd deck aft.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 July 2019
Resolution: Replaced corroded clip.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 24 July 2019
Resolved
Label port and starboard thruster switch.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 July 2019
Resolution: Label installed.
10 - Safety of Navigation › N/A - No Subsystem › Bridge operation
Issued 24 July 2019
Resolved
Remove or repair bow thruster control handle at the main operating station. Captain stated the control is not utilized. Bow thruster controls are used on the bridge wing operating stations.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 July 2019
Resolution: Bow thruster control repaired at main operating station.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 24 July 2019
Resolved
Trouble shoot/identify/ make proper repairs to constantly sounding alarm on bridge.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 July 2019
Resolution: Identified alarms were due to faulty diodes in E/R. Faulty components replaced.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 24 July 2019
Resolved
Secure loose smoke detector hanging from electrical wire located on the 3rd deck aft.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 25 July 2019
Resolution: Properly secured smoke detector.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 24 July 2019
Resolved
Observed at the main operating station the alarm indicator for "Open Engine Room" and "#3 GEN Low Lube Oil Pressure" are cross connected. Fix electrical wiring issue.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 July 2019
Resolution: Properly re-wired alarm indicators.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 24 July 2019
Resolved
Replace missing junction box cover in #3 Void space.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 29 July 2019
09 - Working and Living Conditions › 092 - Working Conditions › Cleanliness of engine room
Issued 24 July 2019
Resolved
Remove/secure loose cyclinder of refrigerant found in engine room.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 29 July 2019
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Insulation wetted through (oil)
Issued 24 July 2019
Resolved
Replace laggin exposed to diesel fuel on the #4 Generator. Observed smoke rising from lagging when generator was online.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 25 July 2019
Resolution: Replaced lagging.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 24 July 2019
Resolved
Replace "Food Grade Plastic Tubing" used as a sight gauge on the starboard coolant reservoir tank with proper hose.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 29 July 2019
09 - Working and Living Conditions › 091 - Living Conditions › Sanitary Facilities
Issued 24 July 2019
Resolved
Observed toilet leak from female restroom located below decks in front of engine room. Fix raw sewage leak.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 29 July 2019
09 - Working and Living Conditions › 092 - Working Conditions › Obstruction/slipping, etc.
Issued 24 July 2019
Resolved
The decks in the pilot house, port and starboard bridge wings were exposed to hydraulic oil from the overfill of the bow thruster pipe located in the pilot house. Clean all affected decks to prevent slips, trips, and falls hazards.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 26 July 2019
09 - Working and Living Conditions › 092 - Working Conditions › Ventilation (Working spaces)
Issued 24 July 2019
Resolved
Ventilate lazarette space and prep for CG inspection. MI oculd not enter space due to recent fresh paint applied in space.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 25 July 2019
Resolution: MI inspected space.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 30 July 2018
Resolved
A device must be provided to automatically shut down engines that draw intake air from a protected space prior to the release of extinguishing agent into the space. Generators 1 and 3 were not shut down via pressure switch on Halon system.
46 CFR 118.410 (b)(10)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 1 August 2018
Resolution: Engine shut downs were repaired and the system sucessfully tested.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 30 July 2018
Resolved
Detectors must be capable of being triggered/tested and restored to operation without replacement of any component. Fire detection system must be resettable without replacing detectors. 46 CFR 76.27-15(b)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 1 August 2018
Resolution: Fire detectors were replaced and system tested, fully functional.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 30 July 2018
Resolved
A galley hood must be equipped with a dry or wet chem
fire extinguishing system. The fire suppression system
must be installed properly. 46 CFR 118.425(b)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 12 September 2018
Resolved 7 November 2018
Resolution: Fire suppression system checked, installed correctly.
09 - Working and Living Conditions › 091 - Living Conditions › Cleanliness
Issued 30 July 2018
Resolved
The vessel may be inspected in accordance with standards
acceptable to the cognizant OCMI as good marine
practices. The galley vents must be cleaned and free of
grease. 46 CFR 115.800(a)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 August 2018
Resolved 7 November 2018
Resolution: Galley hood vents were cleaned of excess grease.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 30 July 2018
Resolved
Fire doors must be of the self-closing type. Adjust the
fire screen doors to close properly and fully.46 CFR 116.435(C)(6)(i)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 August 2018
Resolved 13 August 2018
Resolution: Attended vessel, resolved.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 30 July 2018
Resolved
The vessel may be inspected in accordance with standards
acceptable to the cognizant OCMI as good marine
practices. Replace the spanner wrenches at fire stations 2 & 5.46 CFR 115.800(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 August 2018
Resolved 27 August 2018
Resolution: Resolved
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 30 July 2018
Resolved
Installation and location of fire extinguishers must be
to the satisfaction of the cognizant OCMI. The fire extinguisher bracket on the passenger deck must be permanently affixed to the bulkhead. 46 CFR 118.520
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 August 2018
Resolved 7 November 2018
Resolution: All fire extinguishers were installed on proper brackets.
01 - Certificates & Documentation › 013 - Documents › Signs, indications
Issued 30 July 2018
Resolved
The vessel may be inspected in accordance with standards
acceptable to the cognizant OCMI as good marine
practices. Maximum passenger count placards must be posted at accesses to the catwalk. 46 CFR 115.800(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 August 2018
Resolved 7 November 2018
Resolution: Passenger capacity placards posted on catwalk levels.
Documentation › Certificates/Documents › Certificate of Inspection
Issued 12 September 2017
Resolved
Prove proper operation of propulsion controls and back-up controls.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 14 September 2017
Resolution: Vessel replaced the fitting on the air receiver which was leaking during previous hydrostatic test. Witnessed satisfactory hydrostatic test.
Engineering › Thrusters › Seal
Issued 1 August 2016
Resolved
Repair hydraulic leak on bow thruster in space #2.
Action required: 705 - Other - as specified
Due 12 August 2016
Resolved 1 September 2016
Resolution: Vessel properly repaired hydraulic leak on bow thruster.
Electrical › Lighting (service) › Lighting Fixture
Issued 1 August 2016
Resolved
Replace light guard on light fixture in space #2. 46 CFR 120.410(a)
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 12 August 2016
Resolved 1 September 2016
Resolution: Vessel displayed pictures of correctly installed light guard in space #2.
Electrical › Electrical Distribution System (service) › Wiring
Issued 1 August 2016
Resolved
Bundle dangling wire in space #2 and properly support.
Action required: 705 - Other - as specified
Due 12 August 2016
Resolved 1 September 2016
Resolution: Vessel displayed pictures of correctly bundled wires in space #2.
Accommodation/Occupational Safety › Occupational Safety › Guards for Exposed Hazards
Issued 1 August 2016
Resolved
Replace and add lagging on dry exhaust on generator #2. 46 CFR 116.970
Action required: 705 - Other - as specified
Due 12 August 2016
Resolved 1 September 2016
Resolution: CG Inspectors attested to correctly installed lagging on dry exhaust for NR2 Generator.
Electrical › Electrical Distribution System (service) › Panelboard
Issued 1 August 2016
Resolved
Provide blockage (blank) in the panel located in the galley (p-221/3). 46 CFR 183.10-10(a) Old T
Action required: 705 - Other - as specified
Due 12 August 2016
Resolved 1 September 2016
Resolution: Vessel displayed pictures of correctly blanked off galley panel.
Electrical › Lighting (service) › Lighting Fixture
Issued 1 August 2016
Resolved
Repair light fixture and replace bulbs in the engine room. 46 CFR 120.410(a)
Action required: 705 - Other - as specified
Due 12 August 2016
Resolved 1 August 2016
Resolution: CG Marine Inspector attested to correctly replaced lights.
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 1 August 2016
Resolved
Provide instructions for operation of the engine room fixed gas fire extinguishing system at local and remote stations. 46 CFR 122.612.
Action required: 705 - Other - as specified
Due 12 August 2016
Resolved 1 September 2016
Resolution: CG Inspector attested to correctly written instructions for E/R fixed gas fire extinguishing system.