Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 7 May 2025
Operational controls None recorded without a removal date
Years with a record 10 calendar years (2016–2025)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

382419
Flag
UNITED STATES
Maury page id
psix-382419

Documentation record

Registered dimensions (L × B × D)30.0 ft × 11.8 ft × 3.3 ft
Registered tonnagegross 7 / net 6
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderFISH RITE BOATS · CENTRAL POINT, OR, UNITED STATES · built 1992
Hull materialAluminum
PropulsionJet Drive
Hull shapeShip
Hull configurationMonohull
Hailing portKLAMATH, CA
Endorsements, as the file codes themcw_un
DocumentationValid · issued 5 March 2026 · expires 31 March 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it6 - Simplified, Net Ton
7 - Simplified, Gross Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Professional
The full record for this vessel

Behind this panel: 12 inspections, each with its date, unit and type; 10 deficiencies with the resolution recorded against each; operational controls, none recorded without a removal date; no tow-unit appearances recorded; no other recorded names; the documentation record: dimensions, tonnage, builder, hailing port and endorsements. Every line is a record the Coast Guard wrote; the counts above are the same counts as in the summary, and they are free.

Professional is $39 a month or $299 a year, or $19.99 a month locked for life at the founding rate, for the first 200 subscribers. It unlocks every detail section on every vessel page, fleet watch tied to your account, and ownership records on request. Already a subscriber? Sign in.

Maury does not score, rate or grade vessels, at any price.

Vessel history report

A report is not offered for this hull. Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. What a sparse-record report looks like.

Inspection history · 12

7 May 2025 Deficiency Check · Annual Inspection
Physical examination · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 8124123
15 May 2024 Deficiency Check · Annual Inspection
Physical examination · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 7901533
11 May 2023 Annual Inspection
Physical examination · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 7686907
2 June 2022 Annual Inspection
Physical examination · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 7466807
9 June 2021 Drydock Exam · COI Inspection · Hull Examination · Internal Structural Exam
Physical examination · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 7221582
22 September 2020 Administrative Inspection
Administrative · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 7063060
6 May 2019 Annual Inspection
Physical examination · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 6678254
9 October 2018 Annual Inspection
Physical examination · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 6557853
3 May 2018 Hull Examination · Internal Structural Exam
Physical examination · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 6449524
7 June 2017 Annual Inspection · Deficiency Check · Administrative Inspection · DAPI Audit
Physical examination · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 6168855
11 August 2016 Annual Inspection · DAPI Audit · Internal Structural Exam
Physical examination · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 5966653
17 May 2016 Deficiency Check
Physical examination · Marine Safety Detachment Humboldt Bay · USCG Southwest District (CGD-SW) · Activity 5915500

Deficiency record · 10

13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 7 May 2025 Resolved
Exhaust blower switches must be located outside of any space required to be ventilated by this section, and must be of the type interlocked with the starting switch and the ignition switch so that the blowers are started before the engine starter motor circuit or the engine ignition is energized. A red warning sign at the switch must state that the blowers must be operated prior to starting the engines for the time sufficient to insure at least one complete change of air in the space served. MARINE INSPECTOR OBSERVED... engine start switches were not interlocked to blowers. Operator to repair circuit so that both engine start switches are properly interlocked to blowers, and to provide proper warning sign at operating station, to the satisfaction of the attending marine inspector. 46 CFR 182.460(e)
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 23 May 2025
Resolution: Operator installed exhaust blower/engine starting interlock. Witnessed satisfactory operation.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 7 May 2025 Resolved
The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector. If any of the equipment or records have not been properly maintained, a qualified servicing facility must perform the required inspections, maintenance procedures, and hydrostatic pressure tests. A tag issued by a qualified servicing organization, and attached to each extinguisher, may be accepted as evidence that the necessary maintenance procedures have been conducted. MARINE INSPECTOR OBSERVED... required 10-B:C extinguisher did not have up to date annual servicing. Operator to have extinguisher replaced or serviced to the satisfaction of the marine inspector. 46 CFR 176.810(b)(iv)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 May 2025
Resolution: Operator sent photo of updated maintenance tag for 10-B:C fire extinguisher.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 7 May 2025 Resolved
Marine employers must establish programs for the chemical testing for dangerous drugs on a random basis of crewmembers on inspected vessels who occupy a position, required by the vessel's Certificate of Inspection. MARINE INSPECTOR OBSERVED... operator did not have proper documentation at time of inspection describing procedures for random drug testing. Operator to provide documentation of procedures for random drug testing to the satisfaction of the marine inspector.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 28 May 2025
Resolution: Operator provided copy of company random drug testing policy.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 7 May 2025 Resolved
The master and crew of a vessel will be familiar with the content of and have mounted at the operating station, emergency instructions containing the actions to be taken in the event of fire, heavy weather, or man overboard conditions. MARINE INSPECTOR OBSERVED... vessel did not have emergency instructions posted. Operator to provide documentation of emergency instructions, and may be kept with drill logs, to the satisfaction of the marine inspector. 46 CFR 185.510
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 7 May 2025
Resolution: Marine inspector provided copy of 46 CFR 185.512 to operator, which satisfies the requirements of 46 CFR 185.510.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 15 May 2024 Resolved
The following spaces must be equipped with a fixed gas fire extinguishing system, in compliance with § 181.410, or other fixed fire extinguishing system specifically approved by the Commandant, except as otherwise allowed by paragraph (b) of this section: A space containing machinery powered by gasoline; A space containing a fuel tank for gasoline. Vessel currently has incomplete Fireboy installation. Operator to complete proper installation to the satisfaction of the Marine Inspector, prior to the carriage of passengers. 46 CFR 181.400(a)(4)(5)
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 31 May 2024
Resolution: Operator submitted photos showing proper install of proper installation of extinguishing system in accordance with 46 CFR 181.400(b)(5).
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 22 September 2020 Resolved
To maintain a valid Certificate of Inspection, you must complete your annual inspection within the periods specified in §176.500(b)(1) and your Certificate of Inspection must be endorsed. The vessel failed to schedule or complete the required annual inspection. The vessel must complete a re-inspection for COI prior to operating.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 22 September 2020
Resolved 25 June 2021
Resolution: Cleared.
Documentation › Certificates/Documents › Certificate of Inspection
Issued 7 June 2017 Resolved
COI is expired. Renew COI prior to carrying passengers.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 June 2017
Resolved 12 June 2017
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 7 June 2017 Resolved
First Aid Kit incomplete.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 12 July 2017
Resolved 29 June 2017
Documentation › Markings/Placards › Lifejacket Placard
Issued 7 June 2017 Resolved
Provide new lifejacket placard.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 12 July 2017
Resolved 29 June 2017
Documentation › Markings/Placards › Oil Discharge Placard
Issued 7 June 2017 Resolved
Provide new oil discharge placard.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 12 July 2017
Resolved 29 June 2017