SEA SCREAMER III

Built
1993
Last inspected
6 May 2026
Documentation
Valid · NVDC file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 6 May 2026
Operational controls None recorded without a removal date
Years with a record 11 calendar years (2016–2026)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

WDE8621
382617
Flag
UNITED STATES
Maury page id
psix-382617

Documentation record

Registered dimensions (L × B × D)65.0 ft × 19.0 ft × 10.0 ft
Registered tonnagegross 82 / net 66
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderNAVIGATOR BOATS · ELMORE, AL, UNITED STATES · built 1993
Hull materialFRP (Fiberglass)
PropulsionDiesel Reduction
Hull shapeShip
Hull configurationMonohull
Hailing portLITTLE RIVER, SC
Endorsements, as the file codes themcw_un, rec, reg
DocumentationValid · issued 25 May 2026 · expires 30 June 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it66 - Simplified, Net Ton
82 - Simplified, Gross Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Professional
The full record for this vessel

Behind this panel: 26 inspections, each with its date, unit and type; 46 deficiencies with the resolution recorded against each; operational controls, none recorded without a removal date; no tow-unit appearances recorded; no other recorded names; the documentation record: dimensions, tonnage, builder, hailing port and endorsements. Every line is a record the Coast Guard wrote; the counts above are the same counts as in the summary, and they are free.

Professional is $39 a month or $299 a year, or $19.99 a month locked for life at the founding rate, for the first 200 subscribers. It unlocks every detail section on every vessel page, fleet watch tied to your account, and ownership records on request. Already a subscriber? Sign in.

Maury does not score, rate or grade vessels, at any price.

Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 1972 to 2026, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 26

6 May 2026 Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 8368160
24 February 2026 Deficiency Check · Drydock Exam
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 8317492
2 May 2025 Annual Inspection · Deficiency Check · Administrative Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 8127589
17 June 2024 Administrative Inspection
Administrative · Sector North Carolina · USCG East District (CGD-E) · Activity 7936506
29 April 2024 Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7903539
15 November 2023 Internal Structural Exam · Drydock Exam · Examination of Repairs · Administrative Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7825825
11 May 2023 Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7686187
11 April 2022 COI Inspection · Administrative Inspection · DAPI Audit
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7428817
28 March 2022 Internal Structural Exam · Examination of Repairs · Hull Examination
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7419618
14 February 2022 Administrative Inspection
Administrative · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 7395887
24 November 2021 Examination of Repairs · Deficiency Check
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7359250
26 May 2021 Deficiency Check · DAPI Audit · Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7193780
19 January 2021 Examination of Repairs
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7127573
16 November 2020 Plan Review "T" Boat · Examination of Repairs
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7097702
10 August 2020 DAPI Audit · Annual Inspection · Examination of Repairs · Deficiency Check
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 7024590
16 April 2020 Drydock Exam · Administrative Inspection · Examination of Repairs · Internal Structural Exam · Hull Examination
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6939825
21 March 2019 Examination of Repairs · Deficiency Check · DAPI Audit · Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6644787
23 January 2019 Administrative Inspection · Examination of Repairs
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6613870
15 May 2018 DAPI Audit · Deficiency Check · Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6405993
14 March 2018 Examination of Repairs · Administrative Inspection · Drydock Exam · Hull Examination · Internal Structural Exam
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6371565
10 July 2017 Administrative Inspection · Deficiency Check
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6204716
25 May 2017 Deficiency Check
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6183499
10 May 2017 Examination of Repairs · DAPI Audit · COI Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 6143739
25 August 2016 Administrative Inspection · Plan Review "T" Boat · Construction Oversight
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 5982928
18 May 2016 COE-Administrative · DAPI Audit · Annual Inspection
Physical examination · Detached Duty Office Myrtle Beach · USCG Southeast District (CGD-SE) · Activity 5880418
22 April 2016 Examination of Repairs · Hull Examination · Drydock Exam · Internal Structural Exam
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 5859960

Deficiency record · 46

08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 6 May 2026 Resolved
On a vessel of at least 7.9 meters (26 feet) in length, a visual and audible alarm must be provided at the operating station to indicate a high water level in a space with a through-hull fitting below the deepest load waterline, such as a lazarette. Visual alarm was inoperable at the operating station for the lazarette.
Action required: 10 - Deficiency Rectified
Resolved 6 May 2026
Resolution: Bulb was burned out. New bulb installed.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 2 May 2025 Resolved
An adult life jacket must be provided for each person carried on board a vessel. Placed 57 adult and child sized PFDs out of service. Vessel is restricted to carrying not more than 61 total persons until new PFDs are provided for all persons onboard.
Action required: 705 - Other - as specified
Resolved 7 May 2025
Resolution: New PFDs purchased and provided on the vessel.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 15 November 2023 Resolved
The machinery guard for the starboard engine PTO is missing, reinstall the guard prior to refloating the vessel.
Action required: 705 - Other - as specified
Resolved 13 March 2024
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 15 November 2023 Resolved
The port engine oil fill tube is leaking IWO the hose connection; make necessary repairs prior to completion of the dry dock period.
Action required: 705 - Other - as specified
Resolved 13 March 2024
02 - Structural Conditions › N/A - No Subsystem › Steering gear
Issued 15 November 2023 Resolved
Where flexible non metallic hose is permitted for use in vital piping systems by 46 CFR 182.720, it must be SAE J-1942 type approved hose. The newly installed hydraulic hose for the steering system, located in the lazarette, does not indicate it meets the stated standard, provide proof of same or replace the hose with an approved type.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 15 April 2024
Resolved 24 February 2026
Resolution: New hoses provided.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 11 April 2022 Resolved
In a vessel of 12 meters of more in length but less than 50 meters in length: A masthead light, 5 miles; except that where the length of the vessel is less than 20 meters, 3 miles. Masthead light was not operational.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 May 2022
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 11 April 2022 Resolved
Each PFD must have at least 31 sq. in. of retro-reflective material on its front side, at least 31 sq. in. on its back side. The material must be Type I material that is approved under subpart 164.018 of this chapter. Retro-reflective material faded on PFDs; replace.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 23 May 2022
Resolution: PFD retroreflective material replaced
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 11 April 2022 Resolved
On a vessel of at least 26 feet in length, a visual and audible alarm must be provided at the operating station to indicate a high water level. High water alarm was audible, but visual light was out.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 May 2022
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 11 April 2022 Resolved
A vessel must carry either a first-aid kit approved under approval series 160.014 or a kit with equivalent contents and instructions. First aid kit missing contents and expired; replace.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 May 2022
02 - Structural Conditions › N/A - No Subsystem › Decks - cracking
Issued 11 April 2022 Resolved
At each initial and subsequent inspection for certification, re inspection and at every other vessel inspection the marine inspector shall require that all observed unsafe practices and hazardous situations be corrected. In the fuel tank compartment, observed stbd #1 deck beam failed fiberglass tabbed joint and stbd #3 deck beam fractures and failed fiberglass tabbed joint. Provide repair plan to the Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 12 May 2022
Resolution: Fiberglass joint failures in starboard #1 deck beam tabbed joint and starboard #3 deck beam fractured with tabbed joint were repaired. Failed fiberglass was removed, surface was free of paint and prepped, and repaired with 2 layers of woven roving.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 28 March 2022 Resolved
Repair the area of delamination on the stbd stern, inboard under the swim platform prior to completion of dry dock.
Action required: 705 - Other - as specified
Resolved 1 April 2022
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 26 May 2021 Resolved
Vessel required to be equipped with fixed/pre-engineered fire extinguishing system. Existing pre-engineered fire extinguishing system failed to provide/emit an audible alarm when activated/tested.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 9 June 2021
Resolved 9 July 2021
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 26 May 2021 Resolved
Vessel required to be fitted with a fire pump & associated piping. Existing hose bib for primary fire station was found leaking.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 9 June 2021
Resolved 9 July 2021
01 - Certificates & Documentation › 011 - Ships Certificates › USCG Certificate of Documentation (COD)
Issued 26 May 2021 Resolved
Vessel required to be marked with name/hailing port in way of port & starboard bow and transom. Existing markings IWO transom do not contain the vessels name (only hailing port).
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 9 June 2021
Resolved 9 July 2021
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 10 August 2020 Resolved
Vessel required to be equipped with a visual and audible alarm/indicator at the operating station to indicate high water level(s). Bilge high water visual indicator for engine room was extinguished.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 August 2020
Resolved 27 August 2020
Resolution: Attending Inspector performed operational test of bilge high water alarms, test sat.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 10 August 2020 Resolved
Vessel required to be equipped with peripheral hand rails. Existing peripheral hand rails were found loose IWO bow.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 August 2020
Resolved 27 August 2020
Resolution: Attending Inspector verified condition of peripheral hand rails.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 10 August 2020 Resolved
Vessel required to be fitted with a suitable steering apparatus. Existing steering system is equipped with improper securing devices for rudder(s).
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 August 2020
Resolved 27 August 2020
Resolution: Attending Inspector verified installation of rudder securing devices.
02 - Structural Conditions › N/A - No Subsystem › Decks - cracking
Issued 10 August 2020 Resolved
An inspection for renewal of a COI includes an inspection of the vessels structure to ensure vessel is in satisfactory condition and fit for route intended. Attending Inspector(s) called out "soft spot" IWO main deck (between engine room hatches).
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 10 September 2020
Resolved 23 February 2021
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 10 August 2020 Resolved
Vessel required to be equipped with a fixed fire extinguishing system or pre-engineered fixed gas extinguishing system. Existing pre-engineerred fixed gas extinguishing system audible alarm is inoperable.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 24 August 2020
Resolved 27 August 2020
Resolution: Attending Inspector performed operational test of pre-engineered fire extinguishing system alarms/shutdowns. Test sat.
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 21 March 2019 Resolved
Vessel is required to carry current/up to date navigational publications for areas transited. Vessel did not carry (on baord) current/up to date navigational publications of areas transitted.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 April 2019
Resolved 6 May 2019
Resolution: Attending Inspectors verified carriage of current/up to date navigational publications.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 21 March 2019 Resolved
All vessels shall be provided with a satisfactory arrangement for draining any watertight compartment. Vessel is fitted with electric submersible bilge pumps in addition to the fixed bilge system. The electric submersible bilge pumps IWO fwd compartment/bilge and fwd machinery space failed to operate in manual/local modes.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 April 2019
Resolved 6 May 2019
Resolution: Attending Inspector(s) performed operational tests of vessels electric submersible bilge pumps.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 21 March 2019 Resolved
Vessels owner shall be prepared to conduct tests/inspections of vessels machinery systems. Vessels "dripless" shaft couplings supply lines (water) was deteriorated and required replacement (port/starboard shaft seals).
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 April 2019
Resolved 6 May 2019
Resolution: Attending Inspector(s) verified installation of shaft cooling/supply flexible hoses.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-op. damage
Issued 21 March 2019 Resolved
Vessels hull is subject to inspection at initial and subsequent inspsections for certification. Vessels main deck longitudinal deck beams in way of lazarette are not secured properly due to delamination of "tabbing" fore/aft.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 6 May 2019
Resolution: Attending Inspector(s) verified repairs made to "tabbing" of main deck longitudinal framing in way of lazarette.
04 - Emergency Systems › N/A - No Subsystem › Public address system
Issued 21 March 2019 Resolved
Vessel is required to be fitted with a fixed public address system and be audible during normal operating conditions throughout the accomodations spaces. Vessels public address system speakers are under repair/inoperable at time of inspection.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 April 2019
Resolved 6 May 2019
Resolution: Attending Inspector(s) performed operational test of vessels public address system.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 21 March 2019 Resolved
Vessels fuel tank fill, if necessary, shall be fitted with a suitable flexible hose having high resistance to salt water, petroleum oils, heat and vibration. Vessels flexible fuel fill hose was deteriorated/crimped.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 April 2019
Resolved 6 May 2019
Resolution: Attending Inspector(s) verified installation of flexible hose in way of diesel fuel tank fill.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 21 March 2019 Resolved
Vessel shall be provided with a satisfactory arrangement for draining watertight compartments. Vessels flexible hose in way of fixed bilge piping required replacement due to deterioration/crimping.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 April 2019
Resolved 6 May 2019
Resolution: Attending Inspector(s) verified installation/renewal of flexible hose connections in way of fixed bilge system.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 21 March 2019 Resolved
Provisions shall be made by means of plugs, covers to prevent the admission of air into the space protected. Vessels ventilation trunk was equipped with additional ventilation opening/louver in way of port console.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 April 2019
Resolved 6 May 2019
Resolution: Attending Inspector(s) verified sealing of ventilation opening in way of port operators station.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 21 March 2019 Resolved
Vessels watertight bulkheads shall be made watertight. Vessels watertight bulkhead IWO fuel tank space contained eight open penetrations where previous fuel filter assemblies were installed.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 April 2019
Resolved 6 May 2019
Resolution: Attending Inspector(s) verified sealing of watertight bulkhead penetrations in way of fuel tank void/machinery space.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 21 March 2019 Resolved
An adult lie jacket must be provided for each person carried on board a vessel. Five of the vessels Type I adult PFD's were found unservicable due to torn/frayed waist straps.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 April 2019
Resolved 6 May 2019
Resolution: Attending Inspector(s) verified the carriage of proper type/qty of adult Type I PFD's.
05 - Radio Communications › N/A - No Subsystem › VHF radio installation
Issued 21 March 2019 Resolved
Vessels VHF-FM radio telephone installation is required to be interfaced with GPS unit. Vessels VHF-FM radio-telephone is not properly connected/interfaced with the installed GPS unit (DSC equipped).
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 April 2019
Resolved 6 May 2019
Resolution: Attending Inspector(s) verified the interface between the vessels GPS unit/VHF-FM radio-telephones.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 15 May 2018 Resolved
Bilge high water alarm (visual indicator) was inoperable at time of inspection.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 May 2018
Resolved 11 July 2018
Resolution: Attending Inspector(s) performed operational test of bilge high water alarms and verified operation of visual & audible alarms.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 15 May 2018 Resolved
Emergency escape markings IWO port embarkation station/gunwale were missing.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 30 May 2018
Resolved 11 July 2018
Resolution: Attending Inspector(s) verified installation of emergency escape markings IWO port embarkation station.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 15 May 2018 Resolved
PFD stowage markings were improper (type/qty).
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 30 May 2018
Resolved 11 July 2018
Resolution: Attending Inspector(s) verified PFD stowage markings (type/qty).
Engineering › Bilge Water Management System › Strainer
Issued 10 July 2017 Resolved
Vessels fixed bilge suction strainers are not properly sized/intalled.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 31 July 2017
Resolution: Attending Inspector received verification from the vessels owner/operator attesting to the installation of new strainers for all bilge suctions.
Navigation › Piloting/Steering › Marine Charts
Issued 10 May 2017 Resolved
Vessel not equipped with current/up to date marine charts/navigational publications for areas transited.
Action required: 705 - Other - as specified
Due 10 June 2017
Resolved 25 May 2017
Resolution: Attending Inspector verified carriage of current/up to date navigation publications.
Documentation › Manuals/Policy Documentation › Emergency Instructions
Issued 10 May 2017 Resolved
Vessel not equipped with complete emergency instructions.
Action required: 705 - Other - as specified
Due 10 June 2017
Resolved 25 May 2017
Resolution: Attending Inspector verified carriage/posting of Emergency Instructions.
Fire Fighting › Nozzles › Type
Issued 10 May 2017 Resolved
Vessel not equipped with proper type of fire nozzle (straight/fog).
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 10 June 2017
Resolved 25 May 2017
Resolution: Attending Inspector verified carriage of proper type of fire nozzle.
Documentation › Certificates/Documents › Proof of Consortium Enrollment (DAPI)
Issued 10 May 2017 Resolved
Provide proof of enrollment in maritime consortium.
Action required: 705 - Other - as specified
Due 10 June 2017
Resolved 25 May 2017
Resolution: Attending Inspector verified enrollment in an approved maritime consortium.
Fire Fighting › Ventilation Systems › Ducts
Issued 10 May 2017 Resolved
Ventilation closure devices for machinery space were not vapor tight (pre-engineered fire suppression system)
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 10 June 2017
Resolved 25 May 2017
Resolution: Attending Inspector verified ventilation closure devices were vaportight.
Fire Fighting › Fixed Gas Fire Extinguishing System › Operating Controls
Issued 10 May 2017 Resolved
Vessels pre-engineered fire suppression system was not configured with audible/visual alarms @ operating station.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Due 10 May 2017
Resolved 10 May 2017
Resolution: Attending Inspector(s) witnessed repairs made to Fireboy system & performed operational test.
Communications › Alarms/Indicators › Bilge Alarm
Issued 10 May 2017 Resolved
Vessels bilge high water alarms were not equipped with visual indicators for spaces served.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Due 10 May 2017
Resolved 10 May 2017
Resolution: Attending Inspector(s) witnessed repairs made to vessels bilge high water alarms & performed operational test.
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 18 May 2016 Resolved
Restencil the life ring
Action required: 705 - Other - as specified
Due 18 May 2016
Resolved 27 May 2016
Documentation › Certificates/Documents › Certificate of Documentation (CG-1270)
Issued 18 May 2016 Resolved
Renew COD
Condition: Invalid
Action required: 705 - Other - as specified
Due 18 May 2016
Resolved 27 May 2016
Lifesaving › Lifejacket/PFD (Type I) › Retroreflective Material
Issued 18 May 2016 Resolved
Replace retro tape
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 18 May 2016
Resolved 27 May 2016
Documentation › Manuals/Policy Documentation › Maneuvering Information
Issued 18 May 2016 Resolved
Replace Coast Pilot and Light List
Condition: Invalid
Action required: 705 - Other - as specified
Due 18 May 2016
Resolved 27 May 2016
Engineering › Gas Turbine (auxiliary) › Heat Exchanger
Issued 18 May 2016 Resolved
Add clamp to exhaust manifold.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 18 May 2016
Resolved 27 May 2016