SDC is a mobile offshore drilling unit. The Coast Guard has recorded 1 inspection in 2002, along with 145 deficiencies.

Records in 2002. Most recent: inspection, 8 July 2002.

Built
Not recorded
Last inspected
8 July 2002
Documentation
Not in the documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

Flag
LIBERIA
—
Maury page id
psix-39741

Inspections, by type

Years with a record 1 calendar year (2002)
The 1 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

This record may be incomplete: the most recent inspection recorded for this vessel was 24 years ago. Maury shows what the Coast Guard recorded, not whether the vessel has been inspected since, is still in service, or what condition it is in. Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Offshore class in Maury's sources begin in 1978.

Documentation record

Tonnage as PSIX records itNot recorded
This hull's Official Number is not in the NVDC file dated 10 September 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.

Radio station licence

No FCC ship-station licence is recorded against this Official Number in the file of 6 September 2026. That is a fact about the licence file, not about the radio.

A report is not offered for this hull: Its Coast Guard record spans fewer than two calendar years. That is a statement about the record, not about the vessel. Reports.

Inspection history · 1

8 July 2002 Letter of Compliance (Initial/Renewal)
Administrative · MSO ANCHORAGE · USCG Arctic District (CGD-A) · Activity 1785401

Deficiency record · 145

Fire Fighting › Fire Pumps
Issued 8 July 2002 Resolved
Emergency fire pump inoperable. LEGACY COMPONENT DESC: Pressure
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 30 July 2002
Resolution: Pump repaired. Proper operation witnessed by CG inspector.
Lifesaving › Lifeboat
Issued 8 July 2002 Resolved
Prove proper operation of all Life Boat illumination, both regular and emergency LEGACY COMPONENT DESC: Lamp (inside)
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 30 July 2002
Resolution: Cleared.
Lifesaving › Lifejacket/PFD (General)
Issued 8 July 2002 Resolved
Replace all retro reflective tape on all Life Boat, Rescue Boat & Personal Floatation Devices with SOLAS approved tape. LEGACY COMPONENT DESC: Retroreflective Material
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 6 August 2003
Resolution: Cleared 08/06/2003.
Lifesaving › Launching Appliances › Winch
Issued 8 July 2002 Resolved
Prove proper operation of #1 & #3 Life Boat winches.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Launching Appliances › Davit
Issued 8 July 2002 Resolved
Prove proper operation of #1 & #3 Life Boat davit assemblies.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Launching Appliances › Release Mechanism
Issued 8 July 2002 Resolved
Prove proper operation of #1 & #3 Life Boat releasing gear.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Documentation › Certificates/Documents
Issued 8 July 2002 Resolved
Provide test certificate for #1 Life Boat weight test.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Lifeboat Equipment
Issued 8 July 2002 Resolved
Provide the following equipment for #1 Life Boat: 1-fire extinguisher, 1-lantern and illuminating oil, 1-L/B equipment list, 1-L/B operating manual. LEGACY COMPONENT DESC: Portable Fire-extinguishing Equipment
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Lifeboat Equipment
Issued 8 July 2002 Resolved
Provide the following equipment for #2 Life Boat: 1-L/B equipment list, 1-L/B operating manual, 6-provisions. LEGACY COMPONENT DESC: Food Ration
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Lifeboat Equipment › Tools (engine)
Issued 8 July 2002 Resolved
Provide the following equipment for #3 Life Boat:1-spare flashlight bulb, 1-tool kit1-L/B equipment list, 58-cans condensed milk, 2-provisions. Prove proper operation of interior lights and connect air bottle fitting.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Lifeboat Equipment › Tools (engine)
Issued 8 July 2002 Resolved
Provide the following equipment for #4 Life Boat: 1-spare flashlight bulb, 1-tool kit, 1-L/B equipment list, 1-L/B operating manual, 58-cans condensed milk, 2-provisions. Prove proper operation of interior lights,c heck pressure relief valve on air bottle, replace gauge on air bottle.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Embarkation Appliances/Stations › Handholds
Issued 8 July 2002 Resolved
Install tie-off cleats and railings on Life Raft embarkation platforms.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 8 July 2002 Resolved
Provide two additional waterlights for ring buoys as required by IMO MODU CODE.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Embarkation Appliances/Stations › Designated Location
Issued 8 July 2002 Resolved
Provide fixed port side means of embarkation.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Embarkation Appliances/Stations
Issued 8 July 2002 Resolved
Remove jacob ladders at life boat embarkation stations or relocate to allow support by vertical surface.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Communications › Alarms/Indicators › Fire Alarm
Issued 8 July 2002 Resolved
Prove proper operation of fire alarm panel for remaining portions of the rig.
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Communications › Visual Communication › Warning Sign (radio room)
Issued 8 July 2002 Resolved
Remove 'Breathing Apparatus' sign outside radio room.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Portable CO2 Fire Extinguisher › Mounting Bracket
Issued 8 July 2002 Resolved
Secure CO2 bottle in radio equipment room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Accommodation/Occupational Safety › Other Accommodation Spaces › Laundry
Issued 8 July 2002 Resolved
Remove all duct tape from dryer duct venting and replace with metal tape.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Combustible Materials
Issued 8 July 2002 Resolved
Remove all combustibles around all hot water heaters.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Accommodation/Occupational Safety › Other Accommodation Spaces › Laundry
Issued 8 July 2002 Resolved
Relocate 220 volt access for laundry (dryers) machines in 3rd deck laundry room.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Electrical › Lighting (emergency)
Issued 8 July 2002 Resolved
Prove proper operation of emergency lighting in 3rd deck port side forward camp stairwell, 2nd deck rec room, change room, and electrical room in galley.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 8 July 2002 Resolved
Label all halon pull stations for area they protect.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Portable Foam Applicators
Issued 8 July 2002 Resolved
Secure foam application in mud pump room and boiler room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Accommodation/Occupational Safety › Occupational Safety › Guards for Exposed Hazards
Issued 8 July 2002 Resolved
Replace guard over pump shaft in mud processing room.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Ventilation Systems
Issued 8 July 2002 Resolved
Prove proper operation of damper closure in aft boiler room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Miscellaneous Items
Issued 8 July 2002 Resolved
Place proper spanner wrenches in all fire stations in MAT.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Miscellaneous Items
Issued 8 July 2002 Resolved
Place fire blanket in storage space below helo deck as required by fire plan.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Communications › Visual Communication
Issued 8 July 2002 Resolved
Install tail rotor warning signs on port and starboard ladders to helo deck.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Communications › Alarms/Indicators
Issued 8 July 2002 Resolved
Prove proper operation of fire bell in emergency generator room. LEGACY COMPONENT DESC: Fire Alarm
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Operations/Management › Vessel Safety Management › Emergency Preparedness
Issued 8 July 2002 Resolved
Prepare and submit for OCMI approval an Emergency Escape Plan in accordance with 33 CFR subchapter N.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Documentation › Safety/Response Plans/Programs
Issued 8 July 2002 Resolved
Review hazardous location plans for accuracy.
Action required: 705 - Other - as specified
Resolved 7 November 2002
Resolution: Cleared.
Fire Fighting › Structural Fire Protection - General
Issued 8 July 2002 Resolved
Verify all Class I, DivI locations for explosion proof fixtures.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Fixed Halon Fire Extinguishing System › Quantity of Halon
Issued 8 July 2002 Resolved
Install appropriate weight bottle for halon system in generator room.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Operations/Management › Vessel Safety Management › Emergency Preparedness
Issued 8 July 2002 Resolved
Provide updated lifesaving and fire fighting plans.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Accommodation/Occupational Safety › Occupational Safety
Issued 8 July 2002 Resolved
Remove all extraneous stenciling and install SOLAS signs.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Lifeboat › Markings
Issued 8 July 2002 Resolved
Black out/paint over 'BOAT 28' on #2 L/B.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Lifesaving › Lifeboat › Handholds/Handrails
Issued 8 July 2002 Resolved
Move handrail that prevents #2 L/B aft door from opening.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: CLeared.
Lifesaving › Lifebuoys
Issued 8 July 2002 Resolved
Replace ring buoys with SOLAS approved ring buoys.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 August 2003
Resolution: Cleared.
Engineering › Steam Boiler (auxiliary/waste heat)
Issued 8 July 2002 Resolved
Clear boiler room sandbox area for verification/access to sand.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Firemans Outfit › Axe
Issued 8 July 2002 Resolved
Mark all fire axes with vessel name.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Lifesaving › Lifejacket/PFD (General)
Issued 8 July 2002 Resolved
Prove personal floatation devices are SOLAS approved or replace with same.
Action required: 705 - Other - as specified
Resolved 6 August 2003
Resolution: Cleared.
Lifesaving › Lifejacket/PFD (General)
Issued 8 July 2002 Resolved
Mark all personal floatation devices with vessel name.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Fire Hydrants › Location/Position
Issued 8 July 2002 Resolved
Label fire stations in pump room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Fire Hydrants › Condition
Issued 8 July 2002 Resolved
Repair leaking hydrants at PR1 and PR2 in pump room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Communications › Audible Communications › Bell
Issued 8 July 2002 Resolved
Properly mount fire alarm bell in lower pump room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Communications › Alarms/Indicators › Fire Alarm
Issued 8 July 2002 Resolved
Install visual fire alarm and general alarm indicators in pump room at each level.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Deck/Cargo › Marine Portable Tanks › Securing Device
Issued 8 July 2002 Resolved
Secure top of waste oil tank in pump room
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Portable CO2 Fire Extinguisher › Location
Issued 8 July 2002 Resolved
Place fire extinguishers 62R and 18R at proper locations.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Electrical › Lighting (service)
Issued 8 July 2002 Resolved
Replace telephone light globe in lower pump room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Fixed Fire Detection System › Smoke Detectors
Issued 8 July 2002 Resolved
Replace fire detectors at first landing into pump room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service)
Issued 8 July 2002 Resolved
Install blanks in electrical panel in the mechanical room off galley. LEGACY COMPONENT DESC: Distribution Panel Bus
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Wiring
Issued 8 July 2002 Resolved
Secure dead end wire in entrance to pump room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Accommodation/Occupational Safety › Occupational Safety
Issued 8 July 2002 Resolved
Secure SCBA bottles in emergency response station and BOSN hold.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Nozzles › Number
Issued 8 July 2002 Resolved
Replace missing nozzle from F/S 16D and others.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Operations/Management › FireFighting
Issued 8 July 2002 Resolved
Install fire pull stations in BOSN hold in accordance with Fire Control Plan.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Electrical › Lighting (service)
Issued 8 July 2002 Resolved
Replace burned out lights on helo deck.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Lighting (service) › Lighting Fixture
Issued 8 July 2002 Resolved
Replace missing guards for lights on helo deck.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Engineering › Pressure Vessel › Marking and Stamping
Issued 8 July 2002 Resolved
Provide data plates for air receivers in Camp Generator Space and Drill Floor Air Controls.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Engineering › Lubricating Oil Storage/Transfer System
Issued 8 July 2002 Resolved
Install site glass guard for port oil tank in Drill Floor generator space.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Engineering › Fuel Oil Service System › Filter
Issued 8 July 2002 Resolved
Install flame impingement bowls for all DAHL fuel filters.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Electrical › Electric Generation Source (service)
Issued 8 July 2002 Resolved
Repair and prove proper operation of No. 4 generator; including all safety shutdowns.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Panelboard
Issued 8 July 2002 Resolved
Blank off opening to spare switch in forward electrical room starboard panel Switch MCC #5.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Combustible Materials
Issued 8 July 2002 Resolved
Remove combustibles: Portable Honda generator, 5 gallon fuel tanks, etc. from Emergency generator room.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Pollution Prevention/Response › Prevention Equipment › Oily Water Separator (15 ppm)
Issued 8 July 2002 Resolved
Install and prove proper operation of oily water separator. * Until item is cleared, all oily waste must be retained on board vessel.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared. IOPP Certificate issued by ABS.
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 8 July 2002 Resolved
All doors in serving Camp Utilities spaces protected by Halon systems must be marked "Keep Door Closed At All Times."
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Stability › Watertight Integrity
Issued 8 July 2002 Resolved
Mark all watertight doors and air lock doors for moon pool with "Keep Closed at All Times."
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 8 July 2002 Resolved
Relocate light obscuring stern light.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Panelboard
Issued 8 July 2002 Resolved
Install blank in Panel B in Nav Instrument Cabin.
Action required: 705 - Other - as specified
Resolved 30 July 2002
Resolution: Cleared.
Engineering › Pressure Vessel
Issued 8 July 2002 Resolved
Remove pressure vessel from Barite line in vicinity of Barite tank 1.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Quantity of CO2
Issued 8 July 2002 Resolved
Install CO2 for fixed extinguishing system for Galley Incinerator. Galley Incinerator may not be used until item is corrected.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Documentation › Safety/Response Plans/Programs
Issued 8 July 2002 Resolved
Provide updated hazardous location plan.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Wiring
Issued 8 July 2002 Resolved
Remove all dead-ended cables throughout vessel.
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Fire Fighting › Water Fog Applicators › Location
Issued 8 July 2002 Resolved
Properly mount low velocity fog applicators in SDC pump room.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Combustible Materials
Issued 8 July 2002 Resolved
Remove combustibles from foyer to Air Heater and incinerator.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Communications › Visual Communication
Issued 8 July 2002 Resolved
Install signs for fire alarms stating: "Go To Fire Station when Bell is Ringing" or words to similar affect.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 8 July 2002 Resolved
Replace all globes on exterior camp emergency lighting located in all stairwells to provide proper lighting for egress.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Communications › Visual Communication
Issued 8 July 2002 Resolved
Make all strobe lights used for alarms in high noise areas one consistent color (SDC pump room has white strobe and drill area generator space has red strobe).
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Communications › Visual Communication
Issued 8 July 2002 Resolved
Install visual indicator for fire alarm and general alarm in all high noise areas.
Action required: 705 - Other - as specified
Resolved 30 July 2002
Resolution: Cleared.
Electrical › Lighting (emergency)
Issued 8 July 2002 Resolved
Prove proper operations of emergency lights in following spaces: recreation room, theater, and conference room.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Fire Fighting › Fixed CO2 Fire Extinguishing System
Issued 8 July 2002 Resolved
Provide attending marine inspector copies of all ABS approved drawings for fixed fire extinguishing systems.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Communications › Audible Communications
Issued 8 July 2002 Resolved
Prove proper operation of fire alarm in emergency generator room and camp utility generator room.
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Communications › Visual Communication › Signalling Lamp
Issued 8 July 2002 Resolved
Install visual alarm in generator and emergency generator room.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Communications › Visual Communication › Signalling Lamp
Issued 8 July 2002 Resolved
Install visual alarm in sewage room.
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Communications › Visual Communication › Signalling Lamp
Issued 8 July 2002 Resolved
Install visual alarm in aqua chem room.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Communications › Visual Communication › Signalling Lamp
Issued 8 July 2002 Resolved
Install visual alarm in MAT control room.
Action required: 705 - Other - as specified
Resolved 29 July 2002
Resolution: Cleared.
Accommodation/Occupational Safety › Occupational Safety › Hand Grab
Issued 8 July 2002 Resolved
Install cage for vertical egress ladder on port side.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Communications › Audible Communications › Bell
Issued 8 July 2002 Resolved
Install fire alarm bell in cellar deck.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Junction Box
Issued 8 July 2002 Resolved
Replace wasted explosion proof junction box located under water tanks across from hydrant station D09.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Documentation › Certificates/Documents
Issued 8 July 2002 Resolved
Provide servicing certificate for HALON system for camp services generator space.
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Fire Fighting › Portable CO2 Fire Extinguisher
Issued 8 July 2002 Resolved
Repair latch to fire extinguisher locker at entrance to Camp Services generator space.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Portable CO2 Fire Extinguisher
Issued 8 July 2002 Resolved
Provide portable fire extinguisher for Camp Services generator control room - missing.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Combustible Materials
Issued 8 July 2002 Resolved
Remove waste oil storage drum/collection site from Camp Services generator space.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Self-contained Breathing Apparatus › Air Bottle
Issued 8 July 2002 Resolved
Remove from vessel hoop wound aluminum SCBA bottle in emergency generator space.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Lighting (emergency)
Issued 8 July 2002 Resolved
Properly mark all "E" lights for egress path from SDC pump room.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Lighting (service)
Issued 8 July 2002 Resolved
Provide proof that florescent light installed in air lock corridor leading to mud room meets Class I, Div I.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Wiring
Issued 8 July 2002 Resolved
Remove dead-ended cable from void space of desander pump room.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Wiring
Issued 8 July 2002 Resolved
Remove dead-ended cable from fwd bulkhead of Nav Cabin (aft) space.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Fire Fighting › Portable CO2 Fire Extinguisher
Issued 8 July 2002 Resolved
Replace portable fire extinguisher R56 and provide mounting bracket.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Wiring
Issued 8 July 2002 Resolved
Remove temporary wiring (extension cords) from overhead runs in Electrician's space.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Fire Hydrants › Condition
Issued 8 July 2002 Resolved
Hose stations F2 and F3 are not attached to the hydrant.
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Fire Fighting › Water Fog Applicators › Location
Issued 8 July 2002 Resolved
Properly mount low velocity fog applicators at hose stations F1 and F5.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Communications › Audible Communications › Bell
Issued 8 July 2002 Resolved
Repair, prove proper operation and properly stencil alarm bell in waste oil tank space off cellar deck.
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Wiring
Issued 8 July 2002 Resolved
Remove dead-ended cable from waste oil tank space off cellar deck.
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Accommodation/Occupational Safety › Occupational Safety › Hand Grab
Issued 8 July 2002 Resolved
Install man cages for all vertical ladders greater than 12 feet in height in Cellar Deck.
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Junction Box
Issued 8 July 2002 Resolved
Rewire heat trace box adjacent to stbd entrance to Cellar Deck in accordance with BCCI.
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Accommodation/Occupational Safety › Occupational Safety
Issued 8 July 2002 Resolved
Prove proper operation of pressure differential system for Cellar Deck.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Wiring
Issued 8 July 2002 Resolved
Properly mount overhead cable run for wiring to #1 mixer in mud room.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Structural Fire Protection - General
Issued 8 July 2002 Resolved
Seal (to make gas tight) numerous holes in bulkhead between Mud Room and Heat Recovery Room in area of Electrician's Office.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Engineering › Generator (propulsion-electric) › Reverse Power Protection Relay Circuitry
Issued 8 July 2002 Resolved
Prove proper operation of Reverse Current Relay and High Temperature Shutdown for #4 generator.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Fire Fighting › Combustible Materials › Oily Residue (sludge/slop) Tank
Issued 8 July 2002 Resolved
Remove all waste oil storage/collection from Boiler room.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Clear.
Engineering › Equipment Service/Testing
Issued 8 July 2002 Resolved
Remove acetylene gage from Air Purge system. Item located on aft bulkhead of Drill Shed.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Junction Box
Issued 8 July 2002 Resolved
Provide missing bolt from Class I, Div I electrical box on aft bulkhead of drill floor.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Lifesaving › Lifeboat › Windows/Translucent Panels
Issued 8 July 2002 Resolved
Replace broken port window on No. 1 lifeboat.
Condition: Unknown
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Communications › Visual Communication
Issued 8 July 2002 Resolved
Install sign or stencil Red Light and Alarm Bell in lower SDC pump room flat.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Fire Hoses › Location
Issued 8 July 2002 Resolved
Remove B-V wheel unit fire extinguisher hose from helo deck gutter and coil on safety net.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Portable CO2 Fire Extinguisher › Location
Issued 8 July 2002 Resolved
Fire extinguisher 8R off station.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Fire Hydrants › Condition
Issued 8 July 2002 Resolved
PR1 & PR2 attach fire hose to hydrants.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Fire Hydrants › Condition
Issued 8 July 2002 Resolved
PR1 hydrant leaking.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Fixed Halon Fire Extinguishing System › Quantity of Halon
Issued 8 July 2002 Resolved
DA trailer HALON bottle out of hydro (10-87), system not serviced.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared. Removed from system and Fire Plan.
Lifesaving › Lifeboat › Markings
Issued 8 July 2002 Resolved
Paint over boat #28 on lifeboat 1.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Wiring
Issued 8 July 2002 Resolved
Remove dead end wire from back of pump stroke/rate counter in drillers console.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Fire Fighting › Fire Hoses › Diameter
Issued 8 July 2002 Resolved
Replace 2 ½ in fire hoses with 1 ½ in fire hoses in MAT.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Distribution Panel Bus
Issued 8 July 2002 Resolved
Install blank in Electrical Stores (fwd) power distribution box.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Communications › Visual Communication
Issued 8 July 2002 Resolved
Install SOLAS signage in accordance with IMO.
Action required: 705 - Other - as specified
Resolved 6 August 2003
Resolution: Cleared.
Engineering › Pressure Vessel › Marking and Stamping
Issued 8 July 2002 Resolved
Install the ID plates for the two air receivers, CG to provide information required to be on plate and will stamp the propeller stamp at next visit. Same as item #62.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Communications › Visual Communication
Issued 8 July 2002 Resolved
Renew faded stenciling as necessary (e.g., damper closures for halon, emergency fuel shutoffs).
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Distribution Panel Bus
Issued 8 July 2002 Resolved
Install blank in electrical panel in RES B room.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Lighting (emergency)
Issued 8 July 2002 Resolved
Prove proper operation of emergency lighting in DA trailer STBD side.
Action required: 705 - Other - as specified
Resolved 14 January 2003
Resolution: Cleared.
Electrical › Electric Generation Source (service)
Issued 8 July 2002 Resolved
Repair wire pulled from STBD side blower motor on drill floor.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Wiring
Issued 8 July 2002 Resolved
Remove dead end wire coming up from sub-structure port side.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Electrical › Electrical Distribution System (service) › Wiring
Issued 8 July 2002 Resolved
Remove dead end wires in choke manifold building adjacent to drill floor.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Engineering › Steam Boiler (auxiliary/waste heat)
Issued 8 July 2002 Resolved
Prove proper operation of all boiler safeties.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 8 July 2002 Resolved
Clean or replace P & S aft Obstruction light lenses.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Electrical › Lighting (emergency)
Issued 8 July 2002 Resolved
Install "E" light to illuminate port side egress path to MAT.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Communications › Visual Communication
Issued 8 July 2002 Resolved
Stencil/label Fire Station pull box mounted near access to Cellar Deck.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Accommodation/Occupational Safety › Occupational Safety
Issued 8 July 2002 Resolved
Prove proper operation of pressure differential system for Rig Dog House.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Accommodation/Occupational Safety › Occupational Safety
Issued 8 July 2002 Resolved
Prove proper operation of the driller's console purge system.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Combustible Materials
Issued 8 July 2002 Resolved
Remove all combustibles from main stair tower in Camp.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Fire Hydrants › Condition
Issued 8 July 2002 Resolved
Attach hose to hydrant at station FR 9.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Fire Fighting › Combustible Materials
Issued 8 July 2002 Resolved
Remove 5 gal waste oil and oiled sorbent pads from emergency generator room.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electric Supply System (service) › Cable
Issued 8 July 2002 Resolved
Install wire clips for overhead run of cable in stbd Aquachem room.
Action required: 705 - Other - as specified
Resolved 6 November 2002
Resolution: Cleared.
Electrical › Electric Supply System (service) › Cable
Issued 8 July 2002 Resolved
Properly install electrical cable runs in Mud Room.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Engineering › Fuel Oil Storage/Transfer System
Issued 8 July 2002 Resolved
Properly mount all overhead runs of low pressure hose with metal clips in Mud Room.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.
Electrical › Electric Supply System (service) › Cable
Issued 8 July 2002 Resolved
Properly mount cable run with metal clips in stbd aft stair tower coming from drill floor to subfloor.
Action required: 705 - Other - as specified
Resolved 13 January 2003
Resolution: Cleared.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.