Records from 1993 to 2016. Most recent: inspection, 10 August 2016.
Fire Fighting › Ventilation Systems › Fans
Issued 5 June 2003
Resolved
Demonstrate operation of means for stopping ventilation fans serving machinery and working spaces as per the 1979 IMO MODU Code 9.10.1. These means shall be capable of being operated from outside such space in case of fire.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Proved proper operation of securing ventilation from outside space.
Fire Fighting › Ventilation Systems › Duct Hatches
Issued 5 June 2003
Resolved
Demonstrate a means for closing all ventilators, annual spaces around funnels and other openings to machinery and working spaces as per the 1979 IMO MODU Code 9.10.1.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the closing of all ventilators, annual spaces around funnels and other openings to machinery and working spaces.
Electrical › Electrical Distribution System (service) › Distribution Panel Bus
Issued 5 June 2003
Resolved
Prepare and install a directory of circuits for all elctrical distribution panels.
Condition: Unknown
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the installation of circuit directory cards in all distribution panels.
Electrical › Lighting (emergency)
Issued 5 June 2003
Resolved
Install and prove operation of emergency lighting under transitional source of power which provides adequate illumination for the entire launching process of lifeboats and liferafts from the stowed position to the water as required by IMO MODU Code 5.3.4.1 and NVIC 3-88 enclosure (1) paragraph 7.I. LEGACY COMPONENT DESC: Battery Operated Lantern
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Installed emergency lighting for liferafts and determined that the transitional source of lighting was sufficient for the launching of the lifeboats.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 5 June 2003
Resolved
Install additional emergency lighting powered under the transitional source of power which provides adequate illumination of escape routes from the motor room, mud pump room and other service spaces as required by IMO MODU Code 5.3.4.1 and NVIC 3-88 enclosure (1) paragraph 7.I.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed a satisfactory operational test of emergency lighting under transitional power.
Electrical › Electrical Distribution System (emergency)
Issued 5 June 2003
Resolved
Prove operation of essential internal communication equipment under transitional source of power as required by IMO MODU Code 5.3.4.2 (i.e. general alarm, fire alarm, public address system, etc...) LEGACY COMPONENT DESC: General alarm, fire alarm, public address
Condition: Unknown
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed satisfactory test of all equipment under transitional power.
Documentation › Certificates/Documents
Issued 5 June 2003
Resolved
Provide proof that fire protection material, Polyspec Flex FR, has been tested in accordance with the FTP Code. LEGACY COMPONENT DESC: MODU Safety Certificate
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Received correspondence proving that the fire protection insulation material, polyspec Flex FR, complies with the FTP Code.
Fire Fighting › Ventilation Systems › Stairway Enclosure Ventilation
Issued 5 June 2003
Resolved
Ventilator openings shall be provided with efficient and accessible closing devices as required by ICLL, 1966 Regulation 19.
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Withnessed the installing of steps providing access to the ventilation closures.
Operations/Management › Drills/Instruction
Issued 5 June 2003
Resolved
Conduct satisfactory fire and abandon ship drill in the presence of the attending USCG Marine Inspector. LEGACY COMPONENT DESC: Fire/Abandon Ship
Action required: 705 - Other - as specified
Due 10 June 2003
Resolved 10 June 2003
Resolution: Witnessed satisfactory fire and abandon ship drills.
Deck/Cargo › Cargo Transfer/Lightering (liquid) › Transfer Hose
Issued 5 June 2003
Resolved
Provide evidence of tests and inspections of all oil transfer hoses as required by 46 CFR 155.800.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Received documentation for transfer hoses.
Operations/Management › Equipment Service/Testing
Issued 5 June 2003
Resolved
Provide for review lifesaving equipment maintenance records. LEGACY COMPONENT DESC: Lifesaving equipment maintenance records
Condition: Unknown
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Reviewed lifesaving equipment maintenance records.
Operations/Management › Drills/Instruction
Issued 5 June 2003
Resolved
Provide for review emergency training and drill records. LEGACY COMPONENT DESC: Emergency training and drill records
Condition: Unknown
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Reviewed emergency training and drill records.
Engineering › Bilge Water Management System › Interface Detector
Issued 5 June 2003
Resolved
Repair and prove operation of faulty ballast indicator panel system lights in the ballst control room.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed satisfactory test of ballast indicator panel system lights.
Fire Fighting › Fire Pumps
Issued 5 June 2003
Resolved
Repair and prove proper operation of remote fire pump start/stop switch located on the ballast control system console in the ballast control room. LEGACY COMPONENT DESC: Remote start/stop switch
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed satisfactory test of the remote fire pump start/stop switch located on the ballast control system console in the ballast control room.
Fire Fighting › Fire Main › Condition
Issued 5 June 2003
Resolved
Prove operation of fire main system and all fire pumps from each local and remote starting station.
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed satisfactory operation of fire main system and all fire pumps from local and remote starting locations.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 5 June 2003
Resolved
Prove operation of navigational lights and signals.
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Withnessed satisfactory test of all navigation lights.
Deck/Cargo › Cargo Transfer/Lightering (liquid) › Emergency Shut-down
Issued 5 June 2003
Resolved
Prove operation of remote shutdowns for fuel oil transfer pumps, oil fuel unit pumps and other similar pumps.
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed satisfactory test of all remote shutdowns.
Engineering › Bilge Water Management System
Issued 5 June 2003
Resolved
Prove operational test of bilge water level detection and automatic bilge pump operation for each column. LEGACY COMPONENT DESC: operational test
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed satisfactory test of bilge level detection and bilge system.
Fire Fighting › Fixed CO2 Fire Extinguishing System
Issued 5 June 2003
Resolved
Remove locking device for SCR CO2 compartment watertight door. LEGACY COMPONENT DESC: watertight door
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the removal of locking device on SCR CO2 watertight door.
Electrical › Electrical Distribution System (service) › Wiring
Issued 5 June 2003
Resolved
Properly support and secure electrical cable leading from receptacle on starboard motor room bulkhead to air dryers.
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Properly secured cable.
Electrical › Electrical Distribution System (service) › Wiring
Issued 5 June 2003
Resolved
Properly support and secure electrical cables for NO.1 & NO.7 generator prime mover alarm light.
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the proper installation of cables.
Electrical › Electrical Distribution System (service) › Wiring
Issued 5 June 2003
Resolved
Properly support and secure electrical cable located on the forward pump room bulkhead.
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the proper installation of cable located on the forward pump room bulkhead.
Engineering › Diesel Engine (auxiliary)
Issued 5 June 2003
Resolved
Install piping supports for generator prime mover cooling water and fire main piping located starboard side motor room bulkhead. LEGACY COMPONENT DESC: piping
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the installation of brackets for generator prime mover cooling water and fire main.
Electrical › Electrical Distribution System (service) › Busway
Issued 5 June 2003
Resolved
Remove dead ended cables in cable transits located on forward pump room bulkhead.
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the removal of dead ended cable in the cable transits located on forward pump room bulkhead.
Electrical › Lighting (service) › Lighting Fixture
Issued 5 June 2003
Resolved
Install cover for fluorescent light fixture located in mud pump room.
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the installation of light fixture cover in mud pump room.
Fire Fighting › Miscellaneous Items
Issued 5 June 2003
Resolved
Provide audible and visual signal for general and fire alarms in high ambient noise areas (i.e. motor room, emergency generator room, air compressor room, pump room). LEGACY COMPONENT DESC: General alarm
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed satisfactory test of audible signal in all spaces and determined that audible signal was loud enough not requiring a visual signal for these spaces,
Stability › Watertight Integrity
Issued 5 June 2003
Resolved
Install approved cable penetration material to cable penetrations to moon pool and mud pump bulkhead. LEGACY COMPONENT DESC: Cable penetrations
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the installation of approved watertight cable transits.
Electrical › Electrical Distribution System (service) › Wiring
Issued 5 June 2003
Resolved
Re-route, properly support and secure electrical cable from 120 VAC distribution panel located in the emergency generator room.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the proper installation of cable in emergency generator room.
Fire Fighting › International Shore Connection › Connection
Issued 5 June 2003
Resolved
Provide for examination required international shore connection and standard discharge connection.
Condition: Unknown
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Vessel representative provided an international shore connection and standard discharge connection.
Stability › Watertight Integrity
Issued 5 June 2003
Resolved
Repair and prove operation of watertight door located on bulkhead separating mud pump room and moon pool area. LEGACY COMPONENT DESC: Quick acting watertight door
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the proper operation of watertight door separating mud pump room and moon pool area.
Fire Fighting › Ventilation Systems
Issued 5 June 2003
Resolved
Prove operation of loss of ventilation alarms. LEGACY COMPONENT DESC: Loss of ventilation alarm
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Witnessed the proper operation of loss of ventilation alarm in the mud pump room, sack room, and occumadation stairway.
Documentation › Certificates/Documents › MODU Safety Certificate
Issued 5 June 2003
Resolved
Make available for inspection drill floor, shale shaker area, and mud pits spaces.
Condition: Unknown
Action required: 705 - Other - as specified
Due 10 July 2003
Resolved 10 June 2003
Resolution: Satisfactory inspected drill floor, shale shaker area, and mud pits.
Electrical
Issued 14 May 1999
Resolved
REPAIR AND CONDUCT SATISFACTORY TEST OF REVERSE POWER RELAY FOR #3 MAIN GENERATOR, AND LOG.
Condition: Unknown
Due 28 May 1999
Resolved 17 May 1999
Documentation
Issued 14 May 1999
Resolved
IMPLEMENT 46 CFR 109.213 REGULATIONS FOR TRAINING CREW AND INDUSTRIAL PERSONNEL.
Condition: Unknown
Due 14 June 1999
Resolved 17 May 1999
Fire Fighting
Issued 14 May 1999
Resolved
MAKE ALL FIRE DOORS LEADING TO GALLEY SELF CLOSING AND REMOVE ALL HOLDBACKS.
Condition: Unknown
Due 14 May 1999
Resolved 14 May 1999
Lifesaving
Issued 14 May 1999
Resolved
REPLACE ALL LIFEBOAT DAVIT BUMPER PADS.
Condition: Unknown
Due 14 May 1999
Resolved 14 May 1999
Construction/Loadline
Issued 20 November 1997
Resolved
Reinstall the hazardous location boundary doors to open INTO the mud pit compartment from the moon pool area; reinstall boundary doors to open INTO the SCR/motor room from the mud pit room (zone 1 to zone 2 and zone 2 to unclassified zone transitions respectively) iaw 1979 IMO MODU Code.
Condition: Unknown
Due 20 November 1997
Resolved 20 November 1997
Documentation
Issued 20 November 1997
Resolved
Provide copies of valid ABS endorsed loadline certificate and Panamanian IMO MODU Code certificate when all ABS outstanding annual survey comments have been satisfactorily resolved. Must be completed prior to expiration date of current year's (1996/197) endorsement.
Condition: Unknown
Due 20 November 1997
Resolved 20 November 1997
Construction/Loadline
Issued 20 November 1997
Resolved
Provide fume-tight (and weather-tight/water-tight where applicable) bulkhead and/or deck penetration enclosures/sealing arrangements for all improperly sealed electrical cable, piping, and BOP chord penetrations between hazardous location divisions (Div 1 to Div 2/Div 2 to unclassified)
Condition: Unknown
Due 31 December 1997
Resolved 31 December 1997
Fire Fighting
Issued 29 November 1996
Resolved
MAKE REPAIRS TO FIREFIGHTING EQUIPMENT IN ACCORDANCE WITH GULF WIDE SAFETY SYSTEMS, INC. REPORT, DATED 25SEP96.
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Lifesaving
Issued 29 November 1996
Resolved
CONTINUANCE OF LETTER OF COMPLIANCE CONTINGENT UPON WEIGHT TESTS OF LIFEBOATS PRIOR TO 17AUG97.
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Electrical
Issued 29 November 1996
Resolved
ADDRESS HISTORICAL PROCEDURE TO TURN-OFF OBSTRUCTION LIGHTS AT NIGHT DUE TOELECTRICAL SWITCH NOISE IN CONTROL ROOM. SECURE NOISE OR INSTATE POLICY REQUIRING OBSTRUCTION LIGHT OPERATION AT ALL TIMES OF REDUCED VISIBILITY.
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Documentation
Issued 29 November 1996
Resolved
PLACE CARGO SHIP SAFETY RADIO CERTIFICATE AND PANAMANIAN SAFE MANNING CERTIFICATE ON BOARD.
Condition: Unknown
Due 3 December 1996
Resolved 3 December 1996
Lifesaving
Issued 29 November 1996
Resolved
PLACE WIND DIRECTION INDICATOR AND TAIL ROTOR WARNING SIGNS AT HELIPORT.
Condition: Unknown
Due 3 December 1996
Resolved 3 December 1996
Documentation
Issued 29 November 1996
Resolved
PROVIDE COPY OF FULL TERM PANAMANIAN MODU SAFETY CERTIFICATE, INTERNATIONALOIL POLLUTION PREVENTION CERTIFICATE AND LOADLINE CERTIFICATE. CONTINUANCE OF LOC CONTINGENT UPON COMPLIANCE.
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Lifesaving
Issued 29 November 1996
Resolved
PLACE PROPER INSTRUCTIONS AT LIFERAFT STATIONS. PROPERLY STENCIL AND STOW LIFERAFTS. REPAIR LIGHTING AT LIFERAFT STATIONS.
Condition: Unknown
Due 3 December 1996
Resolved 3 December 1996
Lifesaving
Issued 29 November 1996
Resolved
CAPACITY OF MODU CREW LIMITED TO 80 PERSONS WHILE LIFERAFT NO. 5 IS BEING SERVICED AND LIFEJACKET LIGHTS ARE ON ORDER.
Condition: Unknown
Due 3 December 1996
Resolved 3 December 1996
Fire Fighting
Issued 29 November 1996
Resolved
ADDRESS FIREMAN'S OUTFIT DEFICIENCIES: REPLACE FLASHLIGHTS, LIFELINES AND BOOTS. HYDROSTATICALLY TEST OUTDATED SCBA BOTTLES. CALIBRATE 02/LEL MONITORS. LABEL STOWAGE ROOMS/CONTAINERS.
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Electrical
Issued 29 November 1996
Resolved
LABEL EMERGENCY LIGHTING THROUGHOUT RIG.
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Lifesaving
Issued 29 November 1996
Resolved
PROPERLY MOUNT AND ARRANGE LIFE RINGS, PER FIRE CONTROL/LIFESAVING PLAN.
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Lifesaving
Issued 29 November 1996
Resolved
MAKE REPAIRS AND REPLACE EQUIPMENT TO ENSURE ALL LIFEBOATS ARE EQUIPPED IN ACCORDANCE WITH SOLAS 74, CHAPTER III.
Condition: Unknown
Due 3 December 1996
Resolved 3 December 1996
Construction/Loadline
Issued 29 November 1996
Resolved
REPLACE WASTED DECK GRATING ON TOP OF C-COLUMN, ADJACENT TO ANCHOR WINCH, AND AT WALKWAY TO E-COLUMN, ADJACENT TO STARBOARD LIFERAFT.
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Fire Fighting
Issued 29 November 1996
Resolved
INSTALL VALVE IN AIR LINE TO PAINT LOCKER, OUTSIDE OF LOCKER ADJACENT TO FIXED CO2 SYSTEM. PLACE "SECURE AIR SUPPLY VALVE" IN FIXED FIREFIGHTING SYSTEM INSTRUCTIONS.
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Lifesaving
Issued 29 November 1996
Resolved
TRAIN CREW ON PROPER ABANDONMENT PROCEDURE FROM LIFERAFTS AND PROPER USE/LIMITATIONS OF SELF CONTAINED BREATHING APPARATUS (SCBA).
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Electrical
Issued 29 November 1996
Resolved
MAKE REPAIRS AND/OR REPLACE WASTED SECTIONS OF S/W COOLING PIPING TO GENERATORS.
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Lifesaving
Issued 29 November 1996
Resolved
RENEW 47 LIFE PRESERVER LIGHTS.
Condition: Unknown
Due 3 December 1996
Resolved 3 December 1996
Electrical
Issued 29 November 1996
Resolved
REPAIR CABLE TO OVERSPEED SHUT DOWN ON GENERATOR NO. 3.
Condition: Unknown
Due 29 November 1996
Resolved 29 November 1996
Construction/Loadline
Issued 6 December 1995
Resolved
REPAIR BILGE ALARM IN COLUMN "C"
Condition: Unknown
Due 6 December 1995
Resolved 6 December 1995
Electrical
Issued 6 December 1995
Resolved
TROUBLESHOOT AND REPAIR GROUND INDICATION ON EMERGENCY GENERATOR PANEL.
Condition: Unknown
Due 6 December 1995
Resolved 6 December 1995
Electrical
Issued 6 December 1995
Resolved
ADJUST OVERSPEED SENSING DEVICE ON EMERGENCY GENERATOR AND PROOF TEST PROPER OPERATION OF AUTO-BUS TRANSFER.
Condition: Unknown
Due 6 December 1995
Resolved 6 December 1995
Engineering
Issued 6 December 1995
Resolved
PROPERLY LABEL EMERGENCY FUEL SHUT-OFF FOR DAY TANK.
Condition: Unknown
Due 6 December 1995
Resolved 6 December 1995
Electrical
Issued 6 December 1995
Resolved
PROVE PROPER OPERATION OF PURGE LOSS ALARM ON TV MONITOR FOR MUD LOGGING UNIT.
Condition: Unknown
Due 6 December 1995
Resolved 6 December 1995
Documentation
Issued 6 December 1995
Resolved
PROVIDE COPY OF FULL TERM PANAMANIAN MODU SAFETY CERTIFICATE.
Condition: Unknown
Due 6 December 1995
Resolved 6 December 1995
Accommodation/Occupational Safety
Issued 6 December 1995
Resolved
COMPLETE NDT OF ALL PRESSURE VESSELS TO THE SATISFACTION OF THE FLAG ADMINISTRATION AND SUBMIT REPORT TO [name withheld].
Condition: Unknown
Due 6 December 1995
Resolved 6 December 1995
Fire Fighting
Issued 6 December 1995
Resolved
REPAIR GENERAL ALARM BELL IN COLUMN "A"
Condition: Unknown
Due 6 December 1995
Resolved 6 December 1995
Electrical
Issued 17 December 1993
Resolved
MAKE ALL PURGE SYSTEMS ON DRILL FLOOR OPERATIONAL AND TEST ALARMS OF SAME PRIOR TO COMMENCING DRILLING OPERATIONS.
Condition: Unknown
Due 28 December 1993
Resolved 28 December 1993
Deck/Cargo
Issued 17 December 1993
Resolved
LOAD TEST PORT FORWARD CRANE UPON COMPLETION OF REPAIRS._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 28 December 1993
Resolved 28 December 1993
Lifesaving
Issued 17 December 1993
Resolved
REPAIR AND TEST OPERATION OF GENERAL ALARM BELLS IN THE FOLLOWING AREAS: 1. PILOT HOUSE 2. COLUMN E PUMP ROOM 3. M.S.D. SPACE
Condition: Unknown
Due 28 December 1993
Resolved 28 December 1993
Engineering
Issued 17 December 1993
Resolved
REPAIR AND TEST OPERATION OF ALL GENERATORS' REVERSE CURRENT RELAYS.
Condition: Unknown
Due 28 December 1993
Resolved 28 December 1993