Records from 1995 to 1998. Most recent: inspection, 16 November 1998.
A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.
Lifesaving
Issued 22 October 1998
Resolved
Provide proper weaklink for all of the vessel's life rafts, IAW SOLAS 74, Chp III/38.6.2, NLT 15NOV98.
Condition: Unknown
Due 3 December 1998
Resolved 3 December 1998
Lifesaving
Issued 22 October 1998
Resolved
Provide SOLAS approved 4.0KG lifebouys on the STD and Port bridge wings, IAW SOLAS 74, Chp III/31.1.7, NLT 15NOV98.
Condition: Unknown
Due 3 December 1998
Resolved 3 December 1998
Documentation
Issued 22 October 1998
Resolved
Provide Flag State approved officer's licenses or provide letter from Flag State approving officer's licenses currently on board, IAW STCW 95, Reg. I/10 & Reg I/2, NLT 15NOV98.
Condition: Unknown
Due 3 December 1998
Resolved 3 December 1998
Fire Fighting
Issued 9 July 1998
Resolved
REPAIR/RENEW AS ORIGINAL DETERIORATED VENTILATION CLOSURES ON THE BOAT DECKAND PROPERLY INSTALL GASKETS IN SAME._x001C_ SOLAS 60 II/47(a)
Condition: Unknown
Due 20 July 1998
Resolved 20 July 1998
Fire Fighting
Issued 9 July 1998
No resolution recorded
REPAIR/RENEW AS ORIGINAL AND PROVE THE PROPER OPERATION OF THE MUSHROOM VENTS MOUNTED ON THE DECK AND BULKHEAD AFT, MAIN DECK._x001C_ SOLAS 60 II/47(a)
Condition: Unknown
Due 12 July 1998 — due date passed with no resolution recorded
Fire Fighting
Issued 23 June 1998
Resolved
PROVIDE PROPER ARRANGEMENT FOR FIRE EXTINGUISHERS FOR PAINT LOCKER. CORRECTTO SATISFACTION OF CLASS BY NEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Unknown
Issued 23 June 1998
Resolved
INSTALL COVER LIGHTS IN ENGINE ROOM. CORRECT TO SATISFACTION OF CLASS SOCIETY BY NEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Electrical
Issued 23 June 1998
Resolved
INSTALL COVERS TO LIGHT IN CO2 ROOM. CORRECT TO SATISFACTION OF CLASS_x001C_ BY NEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Navigation
Issued 23 June 1998
Resolved
PROVIDE CORRECTIONS TO U.S. COAST PILOT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Navigation
Issued 23 June 1998
Resolved
PROVIDE CORRECTIONS FOR ALL AREA CHARTS.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Navigation
Issued 23 June 1998
Resolved
PROVIDE COPY OF INLAND NAVIGATION RULES BY NEXT U.S. PORT. TO SATISFACTION OF CLASS SOCIETY.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Deck/Cargo
Issued 23 June 1998
Resolved
INSTALL CONTAINMENT AROUND LUBE OIL VENTS ON PORT AND STARBOARD SIDE DECK HOUSE. CORRECT PRIOR TO NEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Deck/Cargo
Issued 23 June 1998
Resolved
PROVIDE PROPER CONTAINMENT FOR PORTSIDE BUNKERING STATION. CORRECT PRIOR TONEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Navigation
Issued 23 June 1998
Resolved
PROVIDE COPY OF EMERGENCY STEERING INSRUCTIONS ON BRIDGE TO SATISFACTION OFCLASS SOCIETY PRIOR TO NEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Electrical
Issued 23 June 1998
Resolved
INSTALL COVERS TO LIGHT IN EMERGENCY GENERATOR ROOM. CORRECT PRIOR TO NEXT U.S. PORT. TO SATISFACTION OF CLASS.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Engineering
Issued 23 June 1998
Resolved
PROVIDE CLASS REPORT PROVING PROPER OPERATION OF 15PPM OILY WATER SEPARATOR. CORRECT PRIOR TO NEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Fire Fighting
Issued 23 June 1998
Resolved
REPAIR HOLES IN VENT CLOSURES ON BOAT DECK. CORRECT TO SATISFACTION OF CLASS SOCIETY PRIOR TO NEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Fire Fighting
Issued 23 June 1998
Resolved
INSTALL RUBBER GASKETS IN VENT CLOSURES ON BOAT DECK. CORRECT TO SATISFACTION OF CLASS PRIOR TO NEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Unknown
Issued 23 June 1998
Resolved
RENEW HAND RAILS BETWEEN CARGO HATCHES. CORRECT TO SATISFACTION OF CLASS PRIOR TO NEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Unknown
Issued 23 June 1998
Resolved
RENEW HAND RAILS AFT OF FORWARD CARGO CRAIN. CORRECT TO SATISFACTION OF CLASS SOCIETY BY NEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Deck/Cargo
Issued 23 June 1998
Resolved
RENEW CONTAINMENT AROUND FUEL OIL VENTS PORT AND STARBOARD SIDE AMIDSHIP._x001C_ CORRECT NO LATER THAN NEXT U.S. PORT.
Condition: Unknown
Due 10 July 1998
Resolved 10 July 1998
Unknown
Issued 3 November 1995
Resolved
Alarm on the oily water seperator did not operate.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Fire Fighting
Issued 3 November 1995
Resolved
Adjust packing on #1 fire pump.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Unknown
Issued 3 November 1995
Resolved
Alarm on Oily Water Separator did not work. _x001C_ (duplicate see # 20)
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Fire Fighting
Issued 3 November 1995
Resolved
Valve handle was missing on semi-portable foam fire extinguisher in engine room.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Engineering
Issued 3 November 1995
Resolved
Valve on high pressure return line was misaligned causing a leak onto the deck plate.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Unknown
Issued 3 November 1995
Resolved
Stores in the paint locker were not stowed. Open and unsecured paints and solutions in paint locker. (boarding was conducted at sea)
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Electrical
Issued 3 November 1995
Resolved
Missing lights and covers in general habitation areas and passageways.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Electrical
Issued 3 November 1995
Resolved
Light bulbs and fixture covers were missing throughout the passageways and engine room.
Condition: Unknown
Due 15 November 1995
Resolved 15 November 1995
Unknown
Issued 3 November 1995
Resolved
Vessel did not have "Discharge of oil prohibited" placard.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Lifesaving
Issued 3 November 1995
Resolved
Lights on life rings did not function.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Navigation
Issued 3 November 1995
Resolved
Echo depth sounder continous recording device was not operational.
Condition: Unknown
Due 3 May 1996
Resolved 17 May 1996
Navigation
Issued 3 November 1995
Resolved
Missing U.S. Coast Pilot
Condition: Unknown
Due 8 November 1995
Resolved 8 November 1995
Unknown
Issued 3 November 1995
Resolved
Vessel could not find their SOPEP (response plan).
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Navigation
Issued 3 November 1995
Resolved
Missing light list.
Condition: Unknown
Due 8 November 1995
Resolved 8 November 1995
Lifesaving
Issued 3 November 1995
Resolved
Pre-arrival tests were not logged in ships log.
Condition: Unknown
Due 8 November 1995
Resolved 8 November 1995
Engineering
Issued 3 November 1995
Resolved
Excessive oil leaks on main engine.
Condition: Unknown
Due 15 November 1995
Resolved 15 November 1995
Fire Fighting
Issued 3 November 1995
Resolved
Improper firefighting suits.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Fire Fighting
Issued 3 November 1995
Resolved
Portable fire extinguisher in aft steering was missing the hose.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Fire Fighting
Issued 3 November 1995
Resolved
CO2 bottles to fixed FF system were not adequately secured.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Construction/Loadline
Issued 3 November 1995
Resolved
Access to escape hatches was blocked by dangling lines.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Electrical
Issued 3 November 1995
Resolved
Missing light guards in aft steering.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Navigation
Issued 3 November 1995
Resolved
Repair oil leak onto deck from steering manifold.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995
Lifesaving
Issued 3 November 1995
Resolved
Lifeline stantion was bent and cable (rail) was missing.
Condition: Unknown
Due 9 November 1995
Resolved 9 November 1995