ISLAND PRINCESS

ISLAND PRINCESS is a 1994 passenger vessel (inspected). The Coast Guard has recorded 55 inspections since 1994, most recently in February 2026, along with 161 deficiencies, 1 operational control and 1 casualty investigation in 2013.

Records from 1994 to 2026. Most recent: inspection, 25 February 2026.

Built
1994
Last inspected
25 February 2026
Documentation
Valid · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

WDQ7876
403358
Flag
UNITED STATES
368456860
Maury page id
psix-403358

Inspections, by type

…with no type recorded4
Years with a record 29 calendar years (1994–2026)
The 55 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Registered dimensions (L × B × D)65.0 ft × 17.4 ft × 6.0 ft
Registered tonnagegross 45 / net 36
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderDEFENDER YACHT CORP · MIAMI, FL, UNITED STATES · built 1994
Hull materialFRP (Fiberglass)
PropulsionDiesel Reduction
Hull shapeShip
Hull configurationMonohull
Hailing portMIAMI, FL
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 20 November 2025 · expires 30 November 2026
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it45 - Simplified, Gross Ton
36 - Simplified, Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

WDQ7876MMSI 368456860 · active · compulsorily equipped · granted 12 February 2026, expires 12 February 2036
WDH7112MMSI 367644930 · expired · voluntarily equipped · granted 23 October 2014, cancelled 28 December 2024
WDB5622MMSI 366911620 · expired · compulsorily equipped · granted 31 October 2003, cancelled 4 January 2014
WCJ6217MMSI not assigned · expired · compulsorily equipped · granted 13 July 1994, cancelled 26 September 2004
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown. A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.

Inspection history · 55

25 February 2026 Deficiency Check · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8312804
25 February 2025 Annual Inspection · Deficiency Check
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8083798
13 December 2024 Drydock Exam · Examination of Repairs · Internal Structural Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8048323
4 December 2024 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8041546
8 November 2023 Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7821806
25 April 2023 Administrative Inspection · In-Service Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7675744
23 November 2022 Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7821802
21 November 2022 Internal Structural Exam · Examination of Repairs · Administrative Inspection · Drydock Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7598297
16 November 2022 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7595454
23 November 2021 Administrative Inspection · COI Inspection · DAPI Audit
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7356292
6 January 2021 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7120360
15 October 2020 Deficiency Check · Internal Structural Exam · Administrative Inspection · Drydock Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7078303
18 June 2020 In-Service Inspection · Deficiency Check · Administrative Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6980332
4 November 2019 Internal Structural Exam · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6848432
31 August 2018 Internal Structural Exam · Drydock Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6528159
24 August 2018 COI Inspection · DAPI Audit
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6517479
18 September 2017 Deficiency Check · DAPI Audit · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6269149
18 November 2016 Annual Inspection · DAPI Audit
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6043557
24 October 2016 Drydock Exam · Deficiency Check · Internal Structural Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6028674
26 October 2015 Deficiency Check · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 5750581
9 October 2014 Drydock Exam · Deficiency Check · Internal Structural Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 5005367
27 August 2014 Type not recorded
No type recorded · Station Miami Beach · USCG Southeast District (CGD-SE) · Activity 4967502
27 September 2011 Annual Inspection · DAPI Audit · Deficiency Check
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 4154929
1 October 2008 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 3336671
24 March 2008 Deficiency Check · Internal Structural Exam · Plan Review "T" Boat · Simplified Stability Test · Drydock Exam · Initial Certification
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 3170086
18 July 2007 Administrative Inspection
Administrative · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 2999714
9 February 2006 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 2582366
8 February 2006 COI Inspection · Deficiency Check
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 2581397
16 September 2005 Hull Examination
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 2494259
9 September 2005 Administrative Inspection
Administrative · Sector Key West · USCG Southeast District (CGD-SE) · Activity 2488019
7 January 2005 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 2270404
25 October 2004 Deficiency Check · Re-Inspection · In-Service Inspection
Physical examination · Sector Key West · USCG Southeast District (CGD-SE) · Activity 2233044
19 October 2004 Type not recorded
No type recorded · Sector Key West · USCG Southeast District (CGD-SE) · Activity 2225375
19 October 2004 Damage Survey
Physical examination · Sector Key West · USCG Southeast District (CGD-SE) · Activity 2228604
16 October 2003 COI Inspection
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1929473
31 July 2003 Hull Examination
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1862373
18 June 2002 Administrative Inspection
Administrative · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1632370
22 April 2002 Administrative Inspection
Administrative · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1607653
24 October 2001 Hull Examination
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1425229
25 April 2001 Re-Inspection
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1439195
26 April 2000 COI Inspection · MARPOL Annex V Examination
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1462842
27 October 1999 Hull Examination
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1365417
17 August 1999 Deficiency Check
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1112782
10 August 1999 Type not recorded
No type recorded · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 777024
21 June 1999 Deficiency Check
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1411937
29 April 1999 MARPOL Annex V Examination · Re-Inspection
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1430673
15 April 1998 MARPOL Annex V Examination · Re-Inspection
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1464088
30 October 1997 Hull Examination
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1116581
29 April 1997 COI Inspection · MARPOL Annex V Examination
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1106309
1 May 1996 Deficiency Check
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1082802
9 April 1996 Re-Inspection
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1079763
25 October 1995 Hull Examination
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 1184636
30 July 1995 Type not recorded
No type recorded · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 28218
18 April 1995 Re-Inspection
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 872801
3 May 1994 Hull Examination · COI Inspection
Physical examination · MSO MIAMI · USCG Southeast District (CGD-SE) · Activity 870682

Deficiency record · 161

07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 25 February 2026 Resolved
Each length of hose must be lined commercial fire hose that conforms to UL 19. Fire hose was substantially ruptured and not of UL 19 construction. 46 CFR 181.15-10(d)(1)
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 25 February 2026
Resolution: New fire hose replaced w UL 19 rated hose.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 25 February 2026 Resolved
Provision shall be made for closing all supply cowls or scoops when the fixed CO2 system is operated. The forward port cowl closure device was missing a section and did not effectively close off the cowl. 46 CFR 182.15-45(h)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 March 2026
Resolved 10 March 2026
Resolution: MI confirmed cowl closure was complete.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 25 February 2026 Resolved
Exhaust piping shall be gas tight through it's length. Wet exhaust piping on the stbd main was leaking water in way of the flexible hose connection after the water injection manifold. 46 CFR 182.15-20(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 March 2026
Resolved 10 March 2026
Resolution: MI confirmed hose clamps on flex line was gas tight.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 25 February 2026 Resolved
At each inspection for certification and at every other vessel inspection all observed fire hazards must be corrected. Blow-by gasses from both main engines were uncontrollably releasing into the engine compartment without a means to contain crank case fumes and atomized oil.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 March 2026
Resolved 10 March 2026
Resolution: MI confirmed measures are taken to arrest crank case mist.
02 - Structural Conditions › N/A - No Subsystem › Bulkhead strength
Issued 25 February 2026 Resolved
Penetrations and openings in watertight bulkheads must have means to make them watertight. The second watertight bulkhead had a hole of approximately 3-4" serving wire runs that were not watertight. 46 CFR 171.114(a)(2)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 March 2026
Resolved 10 March 2026
Resolution: W/T bulkhead penetration was sealed up.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 25 February 2025 Resolved
Diesel exhaust shall be in accordance with 46CFR182.15-15. Every exhaust shall be secured with at least 2 non-overlapping clamps at each end to produce a secure, liquid and vapor tight joint. Add additional clamp on both ends of port and starboard flexible hose where cooling water injects into exhaust system. 46 CFR 182.20-15 ABYC P-1. 1.7.1.10.1
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 March 2025
Resolved 19 March 2025
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 25 February 2025 Resolved
There shall be provided a number of approved life preservers suitable for children equal to at least 10 percent of the total passengers carried. Vessel only had 9 of 12 children's life preservers. Vessel limited to 9 children passengers until life preservers are replaced. 46CFR180.25-5
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 11 March 2025
Resolved 19 March 2025
Resolution: Vessel purchased 03 additional children PFD to total 12.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 25 February 2025 Resolved
All life preservers shall be marked with the vessels name. Rewrite name on all children's life preservers. 46CFR180.25-15
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 March 2025
Resolved 19 March 2025
05 - Radio Communications › N/A - No Subsystem › VHF radio installation
Issued 25 February 2025 Resolved
Stations in the maritime service must be licensed by the FCC. Vessel station license is expired. Provide proof of renewed FCC station license. 47CFR80.13(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 March 2025
Resolved 19 March 2025
Resolution: Vessel requested to limit route to within 1000 feet of shore. Station license no longer required.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 4 December 2024 Resolved
A vessel that is exposed to salt water more than three months in any 12 month period since the last examination must undergo a drydock examination and an internal structural at least once every two years. Vessel failed to undergo a drydock inspection and an internal structural exam within two years.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 26 February 2025
Resolution: Credit DD/ISE completed on 7Jan2025.
02 - Structural Conditions › N/A - No Subsystem › Hull - cracking
Issued 4 December 2024 Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its Certificate of Inspection giving consideration to provisions for a seaworthy hull. FRP found failing in multiple locations on vessel's underwater body. Sand all anti-foulant from underwater body to allow inspection of hull.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 13 December 2024
Resolution: Underwater body of hull sanded and made ready for inspection
09 - Working and Living Conditions › 091 - Living Conditions › Dirty, parasites
Issued 4 December 2024 Resolved
A vessel with installed toilet facilities must have a marine sanitation device that complies with 33 CFR part 159. Approximately 1" of sewage found in MSD space bilge. Repair leak and sanitize bilge for marine inspectors to complete inspection.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 13 December 2024
Resolution: Sewage removed from bilge and space sanitized.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 16 November 2022 Resolved
A vessel that is exposed to salt water more than 3 months in any 12 month period since the last examination must undergo a dry-dock examination and an internal structural exam at least once every 2 years. Vessels last dry-dock was 15OCT2020. 46 CFR 176.600(C)(1)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 23 November 2022
Resolution: Completed Credit Drydock
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 23 November 2021 Resolved
All vessels shall be provided with an approved adult type life preserver for each person carried. Vessel has 114 serviceable lifejackets onboard. Vessel is only permitted to carry the number of passengers in which an adult sized life jacket is provided. Add 05 serviceable lifejackets in order to carry the max capacity of 119 listed on COI. 46 CFR 180.25-5
Action required: 705 - Other - as specified
Resolved 3 December 2021
Resolution: Vessel purchased 8 new lifejackets to supplement count.
01 - Certificates & Documentation › 012 - Crew Certificates › Certificates for radio personnel
Issued 23 November 2021 Resolved
Commercial radio operator licenses issued by the FCC are classified in accordance with the Radio Regulations. Vessel’s captain did not have a current Marine Operator Permit. Vessel is restricted to operating within 1000ft from shore until a valid marine operator permit is provided. 47 CFR 13.7
Action required: 705 - Other - as specified
Resolved 15 January 2022
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 23 November 2021 Resolved
The pump outlet shall be fitted with a pressure gauge. The outlet gauge on the fire pump was inoperable. Replace gauge and provide proof of operation. 46 CFR 181.10-1(c)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 3 December 2021
Resolution: Vessel purchased and installed new gauge on fire pump outlet.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 6 January 2021 Resolved
To maintain a valid Certificate of Inspection, you must complete your annual inspection within the periods specified in 176.500(b)(1) [annual inspection within 3 months before or after each anniversary date] and your Certificate of Inspection must be endorsed. Vessel is outside of three month window for Inspection and is not permitted to operate until annual inspection has been completed.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 January 2021
Resolved 30 November 2021
Resolution: Vessel Completed satisfactory COI Renewal exam.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 18 June 2020 Resolved
Vessel must be operated in accordance with applicable laws and regulations and in a manner to afford adequate precaution against hazards. Fuel leaks on forward engine need to be secured. Oily rags and oil leaks on main engine need to be cleaned up. 46 CFR 185.100
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 18 June 2020
Resolved 22 June 2020
Resolution: Vessel rep sent in photos that showed main engine leaks were cleaned up.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 18 June 2020 Resolved
Electrical equipment on a vessel must protect passengers, crew, and vessel from electrical hazards. All disabled pumps and old wiring that is not in service need to be removed from the sewage space. 46 CFR 183.200
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 18 June 2020
Resolved 10 July 2020
Resolution: verified during def check
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 18 June 2020 Resolved
Life rings must be in accordance with Subchapter Q specifications. Life rings need to be replaced and relabeled with vessel's name. 46 CFR 180.70(b)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 18 June 2020
Resolved 10 July 2020
Resolution: verified during def check
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 4 November 2019 Resolved
Replace retro-reflective tape on identified child life jacket and adult life jacket. 46CFR180.71
Action required: 10 - Deficiency Rectified
Due 4 November 2019
Resolved 4 November 2019
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 4 November 2019 Resolved
Replace damaged adult life jacket identified during inspection. Jacket is damaged and cannot be repaired.
Action required: 10 - Deficiency Rectified
Due 4 November 2019
Resolved 4 November 2019
Documentation › Markings/Placards › Lifejacket Placard
Issued 18 September 2017 Resolved
Must46 CFR 185.516 - Must have donning placards in view of passengers.
Action required: 705 - Other - as specified
Due 28 September 2017
Resolved 21 September 2017
Resolution: Posted
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 18 September 2017 Resolved
46 CFR 181.140 - Must provide service records to Coast Guard upon request.
Action required: 705 - Other - as specified
Due 18 September 2017
Resolved 18 September 2017
Resolution: Produced service records for review.
Accommodation/Occupational Safety › Other Accommodation Spaces › Open Deck Space
Issued 18 September 2017 Resolved
46 CFR 185.602 - Upper deck must be marked with passenger limit by the entrance.
Action required: 705 - Other - as specified
Due 28 September 2017
Resolved 21 September 2017
Resolution: Posted
Personnel › Certificates/Documents/Licenses › License, Radio Officer
Issued 18 September 2017 Resolved
47 CFR 13 - Master must have a valid Radio Operator Permit.
Action required: 705 - Other - as specified
Due 28 September 2017
Resolved 4 November 2019
Lifesaving › Lifebuoys › Serviceable
Issued 18 September 2017 Resolved
46 CFR 180.70 - Replace life bouy, attach light and lanyard.
Action required: 705 - Other - as specified
Due 28 September 2017
Resolved 21 September 2017
Resolution: Replaced.
Lifesaving › Rocket Parachute Flares › General
Issued 18 September 2017 Resolved
46 CFR 180 - Missing three flares.
Action required: 701 - Prior to carriage of passengers/cargo
Due 18 September 2017
Resolved 18 September 2017
Resolution: Purchased three new flares.
Electrical › Electrical Distribution System (service) › Conductor
Issued 18 September 2017 Resolved
46 CFR 183 - Remove all surge protectors.
Action required: 705 - Other - as specified
Due 28 September 2017
Resolved 21 September 2017
Resolution: Removed.
Operations/Management › Drills/Instruction › Fire
Issued 18 September 2017 Resolved
46 CFR 185.420 - Must conduct a satisfactory fire drill.
Action required: 705 - Other - as specified
Resolved 22 September 2017
Resolution: Demonstrated.
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 18 November 2016 Resolved
First aid kit missing items. Renew first aid kit as per 46CFR160.041. 46CFR184.710
Action required: 705 - Other - as specified
Due 2 December 2016
Resolved 1 December 2016
Documentation › Logs/Records › MIS Form
Issued 18 November 2016 Resolved
Provide MIS report from the drug consortium.
Action required: 705 - Other - as specified
Resolved 18 November 2016
Construction/Loadline › Hull › Keel
Issued 25 October 2016 Resolved
Multiple areas were found delaminated from wooden false keel and throughout the vessel. False-keel found with 2 major areas of rot. 176.802
Action required: 705 - Other - as specified
Due 25 October 2016
Resolved 17 November 2016
Resolution: Reparied as original.
Engineering › Steering Gear System › Rudder
Issued 25 October 2016 Resolved
Rudder found with major deflection. Renew. 176.802
Action required: 705 - Other - as specified
Due 25 October 2016
Resolved 17 November 2016
Resolution: Replaced rudder as original.
Engineering › Shafting/Propeller Arrangements › Strut Bearing
Issued 25 October 2016 Resolved
Strut Bearing worn greater than 50%. Replace. 176.802
Action required: 705 - Other - as specified
Due 25 October 2016
Resolved 17 November 2016
Resolution: Strut bearings replaced as original.
Electrical › Electrical Distribution System (service) › Wiring
Issued 25 October 2016 Resolved
Make wiring penetration through the pilothouse bulkhead weather tight. 183.340
Action required: 705 - Other - as specified
Due 25 October 2016
Resolved 17 November 2016
Resolution: Bulkhead in way of electrical penetrations sealed.
Fire Fighting › Fire Pumps › Pressure
Issued 26 October 2015 Resolved
Prove proper operation of fire pump.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 29 October 2015
Resolution: Verified satisfactory operation of fire pump.
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 26 October 2015 Resolved
Properly stencil ring buoy with vessel's name.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 November 2015
Resolved 29 October 2015
Resolution: Verified ring lifebuoys were properly stenciled.
Fire Fighting › Remote Fuel Shutoff › General
Issued 26 October 2015 Resolved
Properly label fuel shut off valves.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 4 November 2015
Resolved 26 October 2015
Resolution: Crew labeled fuel shut off valves.
Engineering › Fuel Oil Service System › Hose
Issued 26 October 2015 Resolved
Provide chaffing gear for fuel lines on port and starboard engine.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 4 November 2015
Resolved 29 October 2015
Resolution: Verified chaffing gear installed on engine fuel lines.
Operations/Management › Bilge/Bilge System Management › Control of Excess Water
Issued 26 October 2015 Resolved
Prove automatic operation of submersible bilge pumps and indicator lights for all shapes.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 4 November 2015
Resolved 29 October 2015
Resolution: Verified operation of high level indication lights and bilge pump activation in all spaces.
Engineering › Steering Gear System › Hydraulic Hose
Issued 9 October 2014 Resolved
Renew hyd hoses for steering ram in steering space
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 21 October 2014
Engineering › Bilge Water Management System › Not Installed
Issued 9 October 2014 Resolved
Provide skin valve for bilge pump in steering space
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 21 October 2014
Operations/Management › Drug and Alcohol Testing › EAP Training Requirements
Issued 27 September 2011 Resolved
Provide documentation of required EAP training for crew and supervisors.
Due 11 October 2011
Resolved 11 October 2011
Navigation › Piloting/Steering › Marine Charts
Issued 27 September 2011 Resolved
Provide up-to-date charts for operating area.
Due 11 October 2011
Resolved 11 October 2011
Electrical › Electrical Distribution System (service) › Wiring
Issued 27 September 2011 Resolved
Remove non-shipboard use power strips on bridge and replace with shipboard use type.
Due 25 October 2011
Resolved 16 November 2011
Resolution: Owner/operator installed a permenant electrical outlet. See activity # 4190023 for details.
Electrical › Electrical Distribution System (service) › Wiring
Issued 27 September 2011 Resolved
Remove the green extension cord on upper deck.
Due 11 October 2011
Resolved 11 October 2011
Electrical › Electrical Distribution System (service) › Overcurrent Device
Issued 27 September 2011 Resolved
Renew the bilge pump motor with a motor designed for an ambient temp of 50 degree C; or derate and meet the requirements of 46 CFR 183.10-5(f).
Due 25 October 2011
Resolved 10 November 2011
Resolution: Owner/operator derated the bilge pump by reducing the overcurrent protection from 20 Amps to 10 Amps.
Electrical › Electric Generation Source (service) › Generator
Issued 27 September 2011 Resolved
Provide the nameplate for the generator which meets 46 CFR 183.10-5.
Due 25 October 2011
Resolved 16 November 2011
Electrical › Electric Generation Source (service) › Metallic Enclosure/Frame
Issued 27 September 2011 Resolved
Replace missing bolt on forward port generator engine foot mount.
Due 11 October 2011
Resolved 11 October 2011
Stability › Watertight Integrity › General
Issued 27 September 2011 Resolved
Provide a metallic shut-off valve, one on either side, for the potable water tank. (piping going through WTB) 46 CFR 182.40-1.
Due 25 October 2011
Resolved 10 November 2011
Resolution: Owner/operator installed a metallic shut-off valve on the E/R side of the bulkhead.
Electrical › Electric Generation Source (service) › Panelboard
Issued 27 September 2011 Resolved
Repair or renew the voltmeter for the DC switchboard and prove proper operation.
Due 11 October 2011
Resolved 11 October 2011
Electrical › Electrical Distribution System (service) › Switchboard
Issued 27 September 2011 Resolved
Repair or renew the amp meter for the AC switchboard and prove proper operation.
Due 11 October 2011
Resolved 11 October 2011
Lifesaving › Rescue Boat › Embarkation/Disembarkation Capabilities
Issued 27 September 2011 Resolved
Provide a rescue platform and submit plans to Sector Miami prior to installation/fabrication; or provide a means to recover a helpless person from the water, which can be observed from the operating station. 46 CFR 180.210.
Due 27 October 2011
Resolved 11 October 2011
Resolution: Owner installed a CCTV cameria at the aft platform and a monitor on the bridge.
Electrical › Electric Generation Source (service) › Overcurrent Device
Issued 27 September 2011 Resolved
Derate and provide proof that the generator has been derated to 80% of its capacity, since the generator is rated at 40 C ambient temperature. Also, provide a nameplate with the derated overcurrent protection, which is installed.
Due 25 October 2011
Resolved 10 November 2011
Resolution: Owner/operator derated the generator by reducing the over current protection from 50 Amps to 40 Amps.
Construction/Loadline › Hull › Keel
Issued 24 March 2008 Resolved
Submit repair proposal for keel.
Action required: 705 - Other - as specified
Resolved 20 June 2008
Construction/Loadline › Hull › Hull Plating
Issued 24 March 2008 Resolved
Make permanent repairs to FRP. Provide list of materials to US Coast Guard.
Action required: 705 - Other - as specified
Resolved 20 June 2008
Accommodation/Occupational Safety › Occupational Safety › Deck Rail
Issued 24 March 2008 Resolved
Make permanent repairs to railing stbd side forward.
Action required: 705 - Other - as specified
Resolved 20 June 2008
Engineering › Feedwater/Condensate Water System › Pump
Issued 24 March 2008 Resolved
Properly secure sewage pumps.
Action required: 705 - Other - as specified
Resolved 20 June 2008
Accommodation/Occupational Safety › Occupational Safety › Rubbish/Waste Materials
Issued 24 March 2008 Resolved
Remove all water and debris from bilges.
Action required: 705 - Other - as specified
Resolved 20 June 2008
Construction/Loadline › Hull › Bottom Plating
Issued 24 March 2008 Resolved
Glass bottom bolts to be removed and inspected to the satisfaction of attending Marine Inspector.
Action required: 705 - Other - as specified
Resolved 20 June 2008
Construction/Loadline › Penetrations › Valve Flange
Issued 24 March 2008 Resolved
Make all thru-hull valves ready for inspection.
Action required: 705 - Other - as specified
Resolved 20 June 2008
Construction/Loadline › Hull › Hull Plating
Issued 24 March 2008 Resolved
Properly grind back all areas marked on hull using 12:1 scarf and repair IAW approved proposal.
Action required: 705 - Other - as specified
Resolved 20 June 2008
Construction/Loadline › Hull › Bottom Plating
Issued 24 March 2008 Resolved
Glass bottom window retention molding is holed and wasted, repair to original condition or replace in kind.
Action required: 705 - Other - as specified
Resolved 20 June 2008
Fire Fighting › Fire Pumps › Arrangement
Issued 24 March 2008 Resolved
Existing fire pump does not meet 46 CFR 181.300(b). Submit plans for review and approval for installation of new fire pump.
Action required: 705 - Other - as specified
Resolved 22 August 2008
Engineering › Bilge Water Management System › Pump
Issued 24 March 2008 Resolved
Vsl only has individual electric bilge pumps and is required to have a fixed bilge system. Submit plans for review and approval for installation of new fixed bilge system.
Action required: 705 - Other - as specified
Resolved 22 August 2008
Engineering › Fuel Oil Service System › Filter
Issued 24 March 2008 Resolved
Provide plugs for petcocks on fuel oil system raycor filters.
Action required: 705 - Other - as specified
Resolved 22 August 2008
Engineering › Fuel Oil Storage/Transfer System › Piping
Issued 24 March 2008 Resolved
Provide grounding straps on fuel fill flex hose for both fuel tanks.
Action required: 705 - Other - as specified
Resolved 22 August 2008
Engineering › Fuel Oil Service System › Valve
Issued 24 March 2008 Resolved
Provide proper tool for emergency fuel shutoff covers.
Action required: 705 - Other - as specified
Resolved 22 August 2008
Engineering › Fuel Oil Service System › Valve
Issued 24 March 2008 Resolved
Properly label location of emergency fuel shut off valves.
Action required: 705 - Other - as specified
Resolved 22 August 2008
Electrical › Lighting (service) › Lighting Fixture
Issued 24 March 2008 Resolved
Provide protective global for overhead light fixture located in main cabin forward and aft.
Action required: 705 - Other - as specified
Resolved 22 August 2008
Communications › Audible Communications › Horn/Whistle
Issued 24 March 2008 Resolved
Install gas operated siren for Engine Room fixed CO2 system at next scheduled drydock.
Action required: 705 - Other - as specified
Resolved 12 August 2010
Resolution: Electric alarm approved at plan review, vessel engine room is not a normally manned space, signs posted, approved owners request to keep electric alarm.
Documentation › Markings/Placards › Warning Signs
Issued 24 March 2008 Resolved
Properly display warning placard in engine room for fixed Co2 system.
Action required: 705 - Other - as specified
Resolved 22 August 2008
Electrical › Electrical Distribution System (service) › Junction Box
Issued 24 March 2008 Resolved
Properly hard wire bilge pump into junction box.
Action required: 705 - Other - as specified
Resolved 22 August 2008
Engineering › Bilge Water Management System › Hose
Issued 24 March 2008 Resolved
Properly double clamp flex hoses on electric bilge pumps.
Action required: 705 - Other - as specified
Resolved 28 August 2008
Documentation › Certificates/Documents › FCC SSL
Issued 24 March 2008 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Action required: 705 - Other - as specified
Resolved 20 November 2009
Electrical › Electrical Distribution System (service) › Wiring
Issued 24 March 2008 Resolved
Properly repair wiring on electric bilge pump located aft glass bottom void.
Action required: 705 - Other - as specified
Resolved 28 August 2008
Operations/Management › Drills/Instruction › Fire
Issued 24 March 2008 Resolved
Provide and post emergency instructions for fire, flooding and man overboard.
Action required: 705 - Other - as specified
Resolved 28 August 2008
Navigation › Piloting/Steering › US Coast Pilot
Issued 24 March 2008 Resolved
Provide current edition for Coast Pilot [name withheld], Tides & Currents, and ColRegs.
Action required: 705 - Other - as specified
Resolved 28 August 2008
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 24 March 2008 Resolved
Replace expired aspirin, ammonia inhalation, and Burn Gel.
Action required: 705 - Other - as specified
Resolved 3 September 2008
Documentation › Markings/Placards › Lifejacket Placard
Issued 24 March 2008 Resolved
Properly post lifejacket donning placard in main cabin.
Action required: 705 - Other - as specified
Resolved 28 August 2008
Operations/Management › Drug and Alcohol Testing › Testing, Equipment
Issued 24 March 2008 Resolved
Provide alcohol test kits and post help hotline numbers.
Action required: 705 - Other - as specified
Resolved 3 September 2008
Fire Fighting › Fire Pumps › Pressure
Issued 24 March 2008 Resolved
Prove proper operation of main fire pump.
Action required: 705 - Other - as specified
Resolved 3 September 2008
Engineering › Bilge Water Management System › Pump
Issued 8 February 2006 Resolved
Prove proper operation of Fwd bilge pump.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 February 2006
Resolution: Corrected
Electrical › Electric Generation Source (service) › Generator Cable
Issued 8 February 2006 Resolved
Remove unauthorized extension cord in fwd bilge or replace with marine grade.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 February 2006
Resolution: Extension cord has been removed.
Stability › Watertight Integrity › General
Issued 8 February 2006 Resolved
Install quick closing valve to bilge overboard through-hull fitting in fwd compartment.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 February 2006
Resolution: New through hull brass quick closing valve has been installed.
Accommodation/Occupational Safety › Other Accommodation Spaces › Open Deck Space
Issued 8 February 2006 Resolved
Renew decking in fwd main passenger deck.
Due 7 March 2006
Resolved 2 June 2006
Electrical › Lighting (service) › Lighting Fixture
Issued 8 February 2006 Resolved
Install light bulb and cover in eng room overhead.
Due 7 March 2006
Resolved 9 February 2006
Resolution: Corrected
Fire Fighting › Portable CO2 Fire Extinguisher › Mounting Bracket
Issued 8 February 2006 Resolved
Properly mount 1 B-II fire ext.
Due 10 February 2006
Resolved 2 June 2006
Accommodation/Occupational Safety › Occupational Safety › Tripping/Falling Hazard
Issued 8 February 2006 Resolved
Mount fire axe.
Due 14 February 2006
Resolved 25 May 2006
Resolution: Does not need fire axe.
Electrical › Lighting (emergency) › Battery Operated Lantern
Issued 8 February 2006 Resolved
Provide 02 portable flashlights.
Due 8 February 2006
Resolved 8 February 2006
Resolution: New flashlights have been installed and work properly.
Communications › Internal Communications System › Sound-powered Telephone
Issued 8 February 2006 Resolved
Prove proper operation of public address system.
Due 21 February 2006
Resolved 2 June 2006
Navigation › Electronic Positioning › Radio Direction Finding Device
Issued 8 February 2006 Resolved
Register EPIRB
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 February 2006
Resolution: Received confirmation of EPIRB being registered.
Engineering › Bilge Water Management System › Pump
Issued 8 February 2006 Resolved
Prove proper operation of aft high level bilge alarm.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 February 2006
Resolution: Alarm has been tested and works properly.
Fire Fighting › Ventilation Systems › Ducts
Issued 8 February 2006 Resolved
Provide means of closing ventalation to engine room.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 February 2006
Resolution: Fire dampers have been installed.
Fire Fighting › Fire Hoses › Diameter
Issued 8 February 2006 Resolved
Provide and properly install a 1.5 inch fire hose.
Due 7 March 2006
Resolved 2 June 2006
Engineering › Bilge Water Management System › Pump
Issued 16 September 2005 Resolved
Install positive shutof vlaves at hullside for all submersible bilge pumps.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 14 October 2005
Engineering › Bilge Water Management System › Piping
Issued 16 September 2005 Resolved
Replace all plastic PVC thru-hulls with bronze or marleon.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 14 October 2005
Engineering › Sea-water System (primary cooling) › Valve
Issued 16 September 2005 Resolved
Replace handle on generator Raw Water suction valve.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 October 2005
Resolved 14 October 2005
Engineering › Sea-water System (primary cooling) › Valve
Issued 16 September 2005 Resolved
Remove and clean and inspect or replace both main diesel engine raw water suction vlaves.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 14 October 2005
Engineering › Diesel Engine (propulsion-direct drive) › Piping (exhaust)
Issued 16 September 2005 Resolved
Repair exhaust leaks forward of mufler port side in rudder room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 14 October 2005
Engineering › Diesel Engine (propulsion-direct drive) › Piping (exhaust)
Issued 16 September 2005 Resolved
Repair cracks in exhaust pipe bulkhead penetrations.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 14 October 2005
Accommodation/Occupational Safety › Occupational Safety › Deck Rail
Issued 16 September 2005 Resolved
Repair hand railing portside forward near pilot house.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 14 October 2005
Construction/Loadline › Penetrations › Flange Pad
Issued 16 September 2005 Resolved
Remove bands around underwater viewing windows where indicated to allow visual inspection of degradaded fiberglass.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 14 October 2005
Construction/Loadline › Hull › Hull Plating
Issued 16 September 2005 Resolved
Grind out all noted areas and submit repair proposal, materials list, and repair procedures.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 14 October 2005
Documentation › Certificates/Documents › Certificate of Documentation (CG-1270)
Issued 25 October 2004 Resolved
Provide a valid Certificate of Documentation.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Documentation › Certificates/Documents › FCC SSL
Issued 25 October 2004 Resolved
Provide a valid FCC Radio Safety Cert.
Action required: 705 - Other - as specified
Due 30 November 2004
Resolved 8 February 2006
Resolution: Corrected
Lifesaving › Hand Flares › Expired
Issued 25 October 2004 Resolved
Renew 6 orange and 6 red hand held flares.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Quantity of CO2
Issued 25 October 2004 Resolved
Complete annual servicing of all portable fire extinguishers and fixed fire suppression system.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Operations/Management › Drug and Alcohol Testing › Proof of Enrollment
Issued 25 October 2004 Resolved
Provide proof of a valid drug testing program.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Personnel › Training › First Aid/CPR
Issued 25 October 2004 Resolved
Provide proof of First Aid/CPR training for one deckhand.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Navigation › Piloting/Steering › Coast Guard Light List
Issued 25 October 2004 Resolved
Provide current Tide Tables, Tidal Current Tables, U.S. Coast Pilot and Light List.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Personnel › Training › Familiarization Training
Issued 25 October 2004 Resolved
Conduct Emergency Drills and crew training.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Communications › Radio Communications › EPIRB
Issued 25 October 2004 Resolved
Provide an automatically deployable, Category 1 406 MHz EPIRB, properly mounted and registered with N.O.A.A.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Personnel › Certificates/Documents/Licenses › License, Radio Officer
Issued 25 October 2004 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Lifesaving › Lifejacket/PFD (Type I) › Quantity
Issued 25 October 2004 Resolved
Provide one additional adult size PFD.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Engineering › Shafting/Propeller Arrangements › Stern Gland
Issued 25 October 2004 Resolved
Repair leak on starboard shaft seal.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Communications › Alarms/Indicators › Bilge Alarm
Issued 25 October 2004 Resolved
Repair bilge high level alarm in viewing panel compartment.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 25 October 2004 Resolved
Conduct emergency drills in the presence of a USCG Marine Inspector.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Electrical › Lighting (emergency) › Battery Operated Lantern
Issued 25 October 2004 Resolved
Provide 2 portable lights.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 November 2004
Resolved 23 November 2004
Resolution: Completed.
Documentation › Certificates/Documents › Certificate of Inspection
Issued 19 October 2004 Resolved
Prior to carrying passengers, vessel must undergo a new to zone inspection to operate in [name withheld] area.
Action required: 701 - Prior to carriage of passengers/cargo
Due 20 October 2004
Resolved 25 October 2004
Resolution: Completed.
Documentation › Certificates/Documents
Issued 16 October 2003 Resolved
Provide a valid Coertificate of Documentation (COD) reflecting new ownership. LEGACY COMPONENT DESC: Certificate of Documentation (CG-1270)
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Documentation › Certificates/Documents
Issued 16 October 2003 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Personnel › Certificates/Documents/Licenses
Issued 16 October 2003 Resolved
Provide a master with a currrent FCC Radio Operators Permit.
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Personnel › Certificates/Documents/Licenses
Issued 16 October 2003 Resolved
Provide certification of CPR course completion for 50 percent of crew. LEGACY COMPONENT DESC: Certificate, CPR Course Completion
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Operations/Management › Drills/Instruction
Issued 16 October 2003 Resolved
Conduct training and make proper log entries to document crew indoctrination, training, and emergency drills.
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Operations/Management › Passenger Operations
Issued 16 October 2003 Resolved
Provide means of conducting passenger count and making that information available ashore.
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Operations/Management › Drills/Instruction
Issued 16 October 2003 Resolved
Post emergency instructions.
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Operations/Management › Drills/Instruction
Issued 16 October 2003 Resolved
Post emergency broadcast placard.
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Navigation › Piloting/Steering
Issued 16 October 2003 Resolved
Provide navigation publications (or excerpts) including Coast Pilot [name withheld], and Tide Tables.
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Lifesaving › Visual Distress Signals (General)
Issued 16 October 2003 Resolved
Mark flare box with the words "Distress Signals". LEGACY COMPONENT DESC: Marking
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Navigation › Collision/Grounding Avoidance
Issued 16 October 2003 Resolved
Make repairs to masthead light and anchor lights. LEGACY COMPONENT DESC: Navigation Lights
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Accommodation/Occupational Safety › Occupational Safety
Issued 16 October 2003 Resolved
Mark upper deck with passenger capacity.
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Lifesaving › Lifejacket/PFD (General)
Issued 16 October 2003 Resolved
Mark all lifejackets with correct vessel name. LEGACY COMPONENT DESC: Marking
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Electrical › Lighting (service)
Issued 16 October 2003 Resolved
Remove dead-end wiring IWO light fixture. LEGACY COMPONENT DESC: Lighting Branch Circuit
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Engineering › Diesel Engine (auxiliary)
Issued 16 October 2003 Resolved
Locate and repair oil leak IWo the generator.
Condition: Improper/Lack of Maintenance
Due 16 October 2003
Resolved 5 November 2003
Fire Fighting › Fixed CO2 Fire Extinguishing System
Issued 16 October 2003 Resolved
Install extensions to FF piping , 2 inches beyond the last horn. LEGACY COMPONENT DESC: Piping
Condition: Improper Installation
Due 16 October 2003
Resolved 5 November 2003
Operations/Management › Drills/Instruction
Issued 16 October 2003 Resolved
Conduct satisfactor emergency drills in the presecne of a CG Inspector.
Due 16 October 2003
Resolved 5 November 2003
Engineering
Issued 16 October 2003 Resolved
Pove operation of fire pump and primary and secondary steering.
Due 16 October 2003
Resolved 5 November 2003
Construction/Loadline
Issued 25 April 2001 Resolved
Unknown Component - Unknown Cause/Condition
Condition: Unknown
Due 1 May 2001
Resolved 9 May 2001
Lifesaving
Issued 26 April 2000 Resolved
REPAIR/REPLACE RING LIFE BUOY ON UPPER DECK.
Condition: Unknown
Due 10 May 2000
Resolved 17 May 2000
Documentation
Issued 26 April 2000 Resolved
PROVIDE CPR CERTIFICATION CARDS FOR AT LEAST 50% OF THE CREW.
Condition: Unknown
Due 10 May 2000
Resolved 17 May 2000
Lifesaving
Issued 26 April 2000 Resolved
PROVIDE FOUR COMPLETE BANDS OF RETROREFLECTIVE TAPE ON BOTH RING LIFE BUOYS.
Condition: Unknown
Due 10 May 2000
Resolved 17 May 2000
Documentation
Issued 26 April 2000 Resolved
AMEND FIRE FIGHTING EMERGENCY PROCEDURES TO INCLUDE INSTALLATION OF FIXED FIRE FIGHTING SYSTEM AND VENTILATION CLOSURES. ALSO, AMEND MAN OVERBOARD PROCEDUCRES TO INCLUDE INSTRUCTIONS ON PERFORMING RESCUE BREATHING.
Condition: Unknown
Due 10 May 2000
Resolved 17 May 2000
Fire Fighting
Issued 26 April 2000 Resolved
PROVIDE VENTILATION CLOSURES FOR NATURAL VENTILATION DUCTS IN ENGINE ROOM ON PORT AND STARBOARD SIDES.
Condition: Unknown
Due 10 May 2000
Resolved 17 May 2000
Navigation
Issued 26 April 2000 Resolved
PROVIDE NAVIGATION PUBLICATIONS FOR VESSEL'S AREA OF OPERATION, I.E. COAST PILOT, LIGHT LIST, TIDE TABLES, ETC.
Condition: Unknown
Due 10 May 2000
Resolved 17 May 2000
Construction/Loadline
Issued 17 August 1999 Resolved
Provide bilge high level alarms IAW 46 CFR, 182.530._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 September 1999
Resolved 23 September 1999
Construction/Loadline
Issued 21 June 1999 Resolved
Provide fixed bilge system IAW 46 CFR, Subpart E, Part 182.500, .510, .520 with proposal to be submitted no later than 13 August, 1999._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 21 June 1999
Resolved 21 June 1999
Lifesaving
Issued 29 April 1999 Resolved
Prior to 13May99, repair lifefloats mainbody exposure damage_x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 29 April 1999
Resolved 29 April 1999
Construction/Loadline
Issued 29 April 1999 Resolved
Prior to 13May99, provide stuffing for P/S wire runs from MDE space to forward P/S heads via PVC piping through WTB's.
Condition: Unknown
Due 29 April 1999
Resolved 29 April 1999
Documentation
Issued 29 April 1999 Resolved
Prior to 04May99, provide itemized drug program paperwork IAW the USCG Chemical Testing Program Checklist._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 3 May 1999
Resolved 3 May 1999
Lifesaving
Issued 29 April 1999 Resolved
Prior to 13May99, provide EPIRB hydrostatic release servicing/expiration date_x001C_ _x001C_ _x001C_
Condition: Unknown
Due 3 May 1999
Resolved 3 May 1999
Electrical
Issued 9 April 1996 Resolved
INSTALL MASTER SWITCHES ON ALL POSITIVE BATTERY CABLES FEEDING STARTER MOTORS.
Condition: Unknown
Due 9 April 1996
Resolved 9 April 1996
Electrical
Issued 9 April 1996 Resolved
PROVIDE A HERTZ METER FOR SSDG.
Condition: Unknown
Due 9 April 1996
Resolved 9 April 1996
Engineering
Issued 9 April 1996 Resolved
PROVIDE FLAME BOWL UNDER EMERGENCY FUEL SHUT OFF REACH RODS.
Condition: Unknown
Due 9 April 1996
Resolved 9 April 1996
Engineering
Issued 9 April 1996 Resolved
PROVIDE A 5 GPM HAND FIRE PUMP WITH SUCTION AND DISCHARGE HOSES.
Condition: Unknown
Due 9 April 1996
Resolved 9 April 1996
Lifesaving
Issued 9 April 1996 Resolved
CORRECT MARKINGS ON LIFE FLOATS AND PDF STOWAGE BOXES.
Condition: Unknown
Due 9 April 1996
Resolved 9 April 1996
Lifesaving
Issued 18 April 1995 Resolved
Provide paddles for five lifefloats.
Condition: Unknown
Due 25 May 1995
Resolved 25 May 1995
Lifesaving
Issued 18 April 1995 Resolved
Provide waterlights for five lifefloats.
Condition: Unknown
Due 25 May 1995
Resolved 25 May 1995
Lifesaving
Issued 18 April 1995 Resolved
Provide and install wood battens between lifefloats.
Condition: Unknown
Due 25 May 1995
Resolved 25 May 1995
Navigation
Issued 18 April 1995 Resolved
Provide current tide and current tables.
Condition: Unknown
Due 25 May 1995
Resolved 25 May 1995

Casualty record · 1

27 August 2013Routine · role: Involved in a Marine Casualty · activity 4706741
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it, and the bridge, lock or dam the investigation names where it names one. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.