Records from 2019 to 2023. Most recent: inspection, 21 September 2023.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 21 September 2023
No resolution recorded
Any required automatic sprinkler, fire detection and fire alarm system shall be capable of immediate operation at all times and no action by the crew shall be necessary to set in operation. PSCO observed storage up to the overhead in AC space #9 behind fire screen door 031, engineer stores in vicinity of steering gear room which obstructed automatic sprinkler system from operating properly.
Deficiency Code: 07190
Action Code: 50ac
74 SOLAS 97 II-2/12.1.1
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 October 2023 — due date passed with no resolution recorded
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 21 September 2023
No resolution recorded
Spaces are classified according to their fire risk as shown in category (1) to (14). A/C space number 1, unlabeled A/C space on deck 3 in the vicinity of fire screen door 40A, hotel storage space on deck 3 and storage compartment in vicinity of fired screen door 054 spaces where storage of combustibles is prohibited. PSCO observed storage of various combustible items in all listed spaces.
Deficiency Code: 07101
Action Code: 50ac
74 SOLAS 81 II-2/20.b.2
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 October 2023 — due date passed with no resolution recorded
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 21 September 2023
Resolved
Muster and embarkation stations shall be adequately illuminated. PSCO witnessed the embarkation area on deck three not to be illuminated. Low location lighting was inoperable.
Deficiency Code: 04103
Action Code: 10c
74 SOLAS 97 III/11.4
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 21 September 2023
Resolved 21 September 2023
Resolution: Low location light was replaced and operable. Witnessed by PSCO.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 12 May 2022
Resolved
If your voyage time is less than 96 hours then you must submit an NOA before departure, but at least 24 hours before arriving at the port or place of destination. The vessel failed to submit an NOA 24 hours prior to arriving in port on a voyage that was less than 96 hours.
Action required: 10 - Deficiency Rectified
Due 12 May 2022
Resolved 31 May 2022
Resolution: Vessel has submitted the NOA, but not in the required submission timeline
07 - Fire Safety › N/A - No Subsystem › Fire control plan
Issued 3 May 2022
Resolved
In all ships general arrangement plans shall be permanently exhibited for the guidance of the ship's officers, showing clearly for each deck the control stations, the various fire sections enclosed by "A" class divisions...readily available in an accessible position. The fire control plan fails to annotate the means of closure for fire doors.
74 SOLAS 97 II-2/20.1
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 June 2022
Resolved 31 May 2022
Resolution: Class Report received.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 3 May 2022
Resolved
"A" class divisions are those divisions formed by bulkheads and decks which comply with the following: they shall be constructed of steel or other equivalent material; they shall be suitably stiffened; they shall be so constructed as to be capable of preventing the passage of smoke and flame to the end of the one-hour standard fire test...the Administration may require a test of a prototype bulkhead or deck to ensure that it meets the above requirements for integrity and temperature rise. FSD 100 is missing locking mechanism leaving opening through the door.
74 SOLAS 97 II-2/3.3
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 3 May 2022
Resolved 3 May 2022
Resolution: Corrected on the spot.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 3 May 2022
Resolved
In addition to complying with the specific provisions for fire integrity of bulkheads and decks mentioned elsewhere in this Part, the minimum fire integrity of all bulkheads and decks shall be as prescribed in tables 26.1 to 26.4. The pool grille galley had a rolling shudder which failed to operate.
74 SOLAS 81 Amend II-2/26.1
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 3 May 2022
Resolved 3 May 2022
Resolution: Corrected on the spot.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 2 October 2019
Resolved
Code 0899. The condition of the ship and it's equipment shall be maintained to conform with the provisions of the present regulations. Water leak in bos'n store is dripping on electrical runs. Pipe leaking above sewing machine in space adjacent to laundry room. 74SOLAS(04)I/11.a
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 November 2019
Resolved 3 May 2022
Resolution: Cleared with Report from RO/RSO.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 2 October 2019
Resolved
Code 0899. Emergency source of electrical power in passenger ships shall be in all service and accommodation in alleyways, stairways, and exits. The following e-lights were not operational: e-light deck 8 outboard, e-light room 401B, e-light in owner's suite. Fire door 006 and fire door 115 exit lights were out. Inadequate means of escape signs at crew mess. 74SOLAS(04)II-1/42.2.1.3
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 November 2019
Resolved 3 May 2022
Resolution: Cleared with Report from RO/RSO.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 2 October 2019
Resolved
Code 0899. All conductors shall be so made as to retain the original fire-resisting properties of the cable. Exposed wires in the theater booth room. 74SOLAS(04)II-1/45.5.6
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 November 2019
Resolved 3 May 2022
Resolution: Cleared with Report from RO/RSO.
04 - Emergency Systems › N/A - No Subsystem › Location of emergency installations
Issued 2 October 2019
Resolved
Code 0680. Means of escape shall be marked by lighting or photoluminescent strips. Inadequate signage in crew mess. Inadequate signage in theater. 74SOLAS(97)II-2/28.1.10
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 November 2019
Resolved 3 May 2022
Resolution: Cleared with Report from RO/RSO.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 2 October 2019
Resolved
Code 0725. Passenger ships shall be equipped with a sprinkler and fire detection system in all service spaces. Inadequate fire detection and supression in bar storage area on Deck 5. 74SOLAS(97)II-2/36.2
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 November 2019
Resolved 3 May 2022
Resolution: Cleared with Report from RO/RSO.
04 - Emergency Systems › N/A - No Subsystem › Location of emergency installations
Issued 2 October 2019
Resolved
Code 0680. Emergency source of electrical power in passenger ships shall be in alleyways, stairways, and exits. Lower section of theater had no emergency lighting. 74SOLAS(04)II-1/42.2.1.3
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 November 2019
Resolved 3 May 2022
Resolution: Cleared with Report from RO/RSO.