07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 18 March 2026
Resolved
Shutoff valves, installed so as to close against the fuel flow...shall be operable from outside the tank compartment.
Remote cable missing from fuel shutoff valves.
46 CFR 182.20-40(b)(3)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 April 2026
Resolved 7 April 2026
Resolution: Picture and video well received. ALL SAT.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 18 March 2026
Resolved
Flexible or portable cords such as SO, STO, and similar types cannot be used for permanently installed wiring.
Temporaty wiring and power strips in multiple spaces.
46 CFR 183.10-20(a)(2)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 April 2026
Resolved 7 April 2026
Resolution: Picture well received. ALL SAT.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 18 March 2026
Resolved
Motors shall be mounted as high as practicable above the bilges.
A/C Pump not mounted.
46 CFR 183.10-5(c)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 April 2026
Resolved 7 April 2026
Resolution: Picture well received. ALL SAT.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 18 March 2026
Resolved
Marine Inspector shall require that all observed unsafe practices and hazardous situations be corrected.
Missing splash covers on electrical outlets in head.
46 CFR 176.25-50(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 April 2026
Resolved 7 April 2026
Resolution: Picture well received. ALL SAT.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 18 March 2026
Resolved
Portable fire extinguishers shall be installed and located to the satisfaction of the Officer in charge, Marine Inspection.
Engine Room portable fire extinguisher not mounted.
46 CFR 181.30-10
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 April 2026
Resolved 7 April 2026
Resolution: Picture well received. ALL SAT.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 18 March 2026
Resolved
Covered metal trash containers shall be provided in lounge areas.
Combustible trash cans found on board.
46 CFR 177.30-7(d)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 April 2026
Resolved 16 April 2026
Resolution: Picture well received. ALL SAT
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 18 March 2026
Resolved
A cable may be spliced only under conditions outlined in 46 CFR Subchapter J 111.60-40.
Unauthorized splices in new lighting in the spaces below deck.
46 CFR 111.60-40
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 April 2026
Resolved 17 April 2026
Resolution: Pictures well received. ALL SAT.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 9 December 2024
Resolved
Each floating water light must be approved in accordance with § 161.010 in subchapter Q of this chapter, or other standard specified by the Commandant, including, but not limited to, approval series 160.110. Vsl's waterlight approved under 161.112, needs approval under 161.010 or 160.110. 46 CFR 180.70(d)(1)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 9 January 2025
Resolved 16 January 2025
Resolution: New waterlight purchased and attached to ring buoy near helm station
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 9 December 2024
Resolved
Each child size life jacket must be stowed in a location that is appropriately marked and separated from adult life jackets so the child size life jackets are not mistaken for adult life jackets. Vsl's adult and youth lifejackets stowed together on top deck, missing quantity identification. 46 CFR 180.78(a)(5)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 9 January 2025
Resolved 16 January 2025
Resolution: PFD's seperated and properly labeled.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 9 December 2024
Resolved
Fire hose shall be 1.5 inches in diameter and 50 feet in length. Stbd side fire hose on top deck had pin hole leak. 46 CFR 181.15-10(c) (Old T)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 9 January 2025
Resolved 16 January 2025
Resolution: Fire hose replaced
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 9 December 2024
Resolved
This part is intended to provide a minimum standard of regulations for electrical installations and equipment that will result in a vessel that is reasonably safe from... electrical shock of personnel. Dead end wires found on port side of E/R in vicinity of entrance. 46 CFR 183.01-5(a) (Old T)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 9 January 2025
Resolved 16 January 2025
Resolution: Dead end wires removed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 4 April 2023
Resolved
A vessel must be provided with bilge pumps in accordance with Table 182.520(a).
Forward bilge pump failed to operate.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 January 2024
Resolved 8 January 2024
Resolution: Small hole was discovered in bilge piping for #1 void, repair was made and successfully operated.
02 - Structural Conditions › N/A - No Subsystem › Hull damage impairing seaworthiness
Issued 6 May 2019
Resolved
Repair steel in the following areas: F/W Space Main Deck, STBD Aft Near Sewage Tank, Port Laz Space near Ladder, STBD Side Laz Xfers BLHD, Exhaust Trunk (Vent) STBD E/R
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 9 December 2021
Resolution: Superseded or corrected during a subsequent inspection.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 6 May 2019
Resolved
Repair Bilge Piping Identified in Diesel Tank Room.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 9 December 2021
Resolution: Superseded or corrected during a subsequent inspection.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 6 May 2019
Resolved
Provide Proof of ASME Approved Air Compressor.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2019
Resolved 9 December 2021
Resolution: Superseded or corrected during a subsequent inspection.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 6 May 2019
Resolved
Remove Dead End Wiring Throughout Vessel.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2019
Resolved 9 December 2021
Resolution: Superseded or corrected during a subsequent inspection.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 6 May 2019
Resolved
Mount Battery Boxes.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2019
Resolved 9 December 2021
Resolution: Superseded or corrected during a subsequent inspection.
05 - Radio Communications › N/A - No Subsystem › Other (radio communication)
Issued 6 May 2019
Resolved
Missing Passenger Radio Certificate and DSC
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2019
Resolved 9 December 2021
Resolution: Superseded or corrected during a subsequent inspection.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 1 August 2018
Resolved
Renew SOLAS tape and grab line.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 September 2018
Resolved 14 August 2018
Resolution: Grab line and retro was placed on two life rings.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 1 August 2018
Resolved
Show proper operation of engineroom bilge suction.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 August 2018
Resolved 1 August 2018
Resolution: Vessel rep showed proper operation of the engineroom bilge suction.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 1 August 2018
Resolved
Provide strain relief for cable located at port and starboard engine control box.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 September 2018
Resolved 28 August 2018
Resolution: Strain relief added to both MDE control boxes.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 1 August 2018
Resolved
Provide strain relief for shore tie cable.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 September 2018
Resolved 14 August 2018
Resolution: Strain relief was provided for shore tie cable.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 1 August 2018
Resolved
Provide proper mounting for electric cable, port side, in freshwater tank.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 September 2018
Resolved 14 August 2018
Resolution: Power cable was properly spliced in dehumidifier box.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 1 August 2018
Resolved
Povide repairs to generator raw water cooling pump.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 September 2018
Resolved 14 August 2018
Resolution: Third party replaced impeller for seawater pump on generator.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 1 August 2018
Resolved
Tighten packing glands for both shafts and/or renew packing.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 September 2018
Resolved 14 August 2018
Resolution: Packing glands were tightened by third party.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 1 August 2018
Resolved
Provide professional cleaning for generator windings.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 September 2018
Resolved 28 August 2018
Resolution: Third party company provided service to generator windings.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 1 August 2018
Resolved
Show proper operation of engine driven bilge pump.
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 August 2018
Resolved 2 August 2018
Resolution: Vessel owner showed proper operation of engine driven bilge pump.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 1 August 2018
Resolved
Properly wire GPS cable for navigation bridge in junction box and stuffing tube.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 September 2018
Resolved 16 October 2018
Resolution: GPS cable was properly routed to the antenna.
Electrical › Electric Supply System (service) › Cable
Issued 22 May 2017
Resolved
Remove extension cords from E/R.
Action required: 705 - Other - as specified
Due 9 June 2017
Resolved 5 June 2017
Resolution: All extension cords were removed from the vessel.
Electrical › Electric Generation Source (service) › Generator
Issued 22 May 2017
Resolved
Remove oil from vent and windings.
Action required: 705 - Other - as specified
Due 9 June 2017
Resolved 5 June 2017
Resolution: Engine mechanic attended vessel and replaced rear main seal of prime mover.
Documentation › Certificates/Documents › Certificate of Documentation (CG-1270)
Issued 20 April 2016
Resolved
Provide copy of original COD.
Action required: 705 - Other - as specified
Due 1 May 2016
Resolved 29 April 2016
Resolution: Vessel owner renewed COD.
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 20 April 2016
Resolved
Provide replacement for expired medications.
Action required: 705 - Other - as specified
Due 1 May 2016
Resolved 27 April 2016
Resolution: Epired medications were updated.
Engineering › Diesel Engine (propulsion-reduction gear) › Exhaust Manifold
Issued 20 April 2016
Resolved
Purchase and place in service three hose clamps for exhaust.
Action required: 705 - Other - as specified
Due 1 May 2016
Resolved 27 April 2016
Resolution: New hose clamps were placed in service.
Engineering › Freshwater Generation System › Piping
Issued 20 April 2016
Resolved
Replace drain hoses for sink drain and A/C drain.
Action required: 705 - Other - as specified
Due 1 May 2016
Resolved 27 April 2016
Resolution: Both hoses were replaced with wire-reindorced hose and double-clamped.