Records from 1994 to 2010. Most recent: inspection, 2 December 2010.
Inspection history · 86
2 December 2010
Administrative Inspection
Administrative · Marine Safety Unit Vicksburg · USCG Heartland District (CGD-H) · Activity 3903413
27 October 2010
Administrative Inspection
Administrative · Marine Safety Unit Vicksburg · USCG Heartland District (CGD-H) · Activity 3879231
5 October 2010
Re-Inspection · Administrative Inspection · MTSA Verification
Physical examination · Marine Safety Unit Vicksburg · USCG Heartland District (CGD-H) · Activity 3865448
25 March 2010
Administrative Inspection
Administrative · Marine Safety Unit Vicksburg · USCG Heartland District (CGD-H) · Activity 3702603
5 January 2010
COI Inspection · Administrative Inspection · MTSA Verification
Physical examination · Marine Safety Unit Vicksburg · USCG Heartland District (CGD-H) · Activity 3662176
15 December 2009
Administrative Inspection
Administrative · Marine Safety Unit Vicksburg · USCG Heartland District (CGD-H) · Activity 3650471
2 December 2009
Deficiency Check · Administrative Inspection
Physical examination · Marine Safety Unit Vicksburg · USCG Heartland District (CGD-H) · Activity 3644023
14 July 2009
MTSA Verification · Administrative Inspection · In-Service Inspection
Physical examination · Marine Safety Unit Vicksburg · USCG Heartland District (CGD-H) · Activity 3540460
27 April 2009
In-Service Inspection · Administrative Inspection · MTSA Verification
Physical examination · Marine Safety Unit Vicksburg · USCG Heartland District (CGD-H) · Activity 3462457
5 February 2009
Administrative Inspection
Administrative · Marine Safety Unit Vicksburg · USCG Heartland District (CGD-H) · Activity 3412841
7 January 2009
COI Inspection · Administrative Inspection · MTSA Verification
Physical examination · Marine Safety Unit Vicksburg · USCG Heartland District (CGD-H) · Activity 3396937
22 October 2008
In-Service Inspection · MTSA Verification
Physical examination · Sector Lower Mississippi · USCG Heartland District (CGD-H) · Activity 3353663
30 July 2008
MTSA Verification · In-Service Inspection
Physical examination · Sector Lower Mississippi · USCG Heartland District (CGD-H) · Activity 3302848
17 April 2008
Periodic Inspection · MTSA Verification
Physical examination · Sector Lower Mississippi · USCG Heartland District (CGD-H) · Activity 3189128
8 January 2008
COI Inspection · MTSA Verification
Physical examination · Sector Lower Mississippi · USCG Heartland District (CGD-H) · Activity 3126503
22 October 2007
In-Service Inspection · Underwater Inspection in lieu of Drydock · Internal Structural Exam
Physical examination · Sector Lower Mississippi · USCG Heartland District (CGD-H) · Activity 3089655
10 January 2007
MTSA Verification · COI Inspection
Physical examination · Sector Lower Mississippi · USCG Heartland District (CGD-H) · Activity 2853407
12 July 2006
In-Service Inspection
Physical examination · Sector Lower Mississippi · USCG Heartland District (CGD-H) · Activity 2710514
27 February 2006
Deficiency Check
Physical examination · Sector Lower Mississippi · USCG Heartland District (CGD-H) · Activity 2592679
14 January 2006
MTSA Verification · COI Inspection
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 2566876
16 November 2005
Re-Inspection
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 2544910
19 April 2005
Re-Inspection
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 2342107
20 January 2005
MTSA Verification · COI Inspection
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 2312987
16 November 2004
Underwater Inspection in lieu of Drydock · Internal Structural Exam
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 2254492
12 November 2004
Administrative Inspection
Administrative · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 2239944
5 October 2004
Re-Inspection
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 2225441
9 July 2004
Re-Inspection
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 2127134
25 May 2004
Administrative Inspection
Administrative · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 2078078
14 April 2004
Administrative Inspection · Quarterly Examination
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 2054459
21 January 2004
COI Inspection
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1989394
22 December 2003
Security Plan Review - ASP
Administrative · Marine Safety Center (MSC) · Activity 1969265
25 November 2003
Quarterly Examination
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1959467
13 November 2003
Internal Structural Exam · Administrative Inspection
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1950996
6 August 2003
Quarterly Examination
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1895601
22 May 2003
Quarterly Examination
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1794445
22 January 2003
COI Inspection
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1735601
12 November 2002
Hull Examination
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1810579
10 October 2002
Deficiency Check · Quarterly Examination
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1695677
11 July 2002
Quarterly Examination
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1669840
17 April 2002
Deficiency Check · Quarterly Examination
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1604082
23 January 2002
COI Inspection
Physical examination · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1477654
8 November 2001
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1075982
8 November 2001
Type not recorded
No type recorded · Marine Safety Unit Baton Rouge · USCG Heartland District (CGD-H) · Activity 1489370
11 September 2001
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1453953
23 July 2001
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1457972
24 April 2001
Re-Inspection · Deadweight Survey
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1470604
23 January 2001
COI Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1441786
12 October 2000
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1426480
26 July 2000
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1369803
26 April 2000
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1408521
25 January 2000
COI Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1464261
16 December 1999
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1361332
25 October 1999
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1369405
28 July 1999
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1372704
29 April 1999
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1432109
26 January 1999
COI Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1459467
4 November 1998
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1467088
4 August 1998
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1472733
27 June 1998
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1127319
13 May 1998
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 791345
30 April 1998
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1378363
27 January 1998
COI Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1424523
3 November 1997
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1438654
7 October 1997
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1108576
5 August 1997
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1371950
1 July 1997
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1113286
7 May 1997
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1431781
31 January 1997
COI Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1414742
4 November 1996
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1404260
30 September 1996
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1433105
12 September 1996
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 956654
8 August 1996
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1359227
7 May 1996
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1437094
13 March 1996
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1371318
1 February 1996
COI Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1383142
7 November 1995
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1355540
21 September 1995
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1186281
9 August 1995
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1412849
3 July 1995
Administrative
Administrative · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 881387
20 June 1995
Administrative
Administrative · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1191235
25 May 1995
Re-Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1358793
13 March 1995
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 87033
15 February 1995
Administrative
Administrative · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1153872
1 February 1995
Initial Certification · Hull Examination
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1374209
9 January 1995
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1161218
22 December 1994
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 57784
Accommodation/Occupational Safety › Occupational Safety › Rubbish/Waste Materials
Issued 5 January 2010
Resolved
All trash cans shall meet 46CFR72.05-55(b) constructed of incombustible material. Please remove those trash cans which can't meet or your unable to prove they meet 46CFR72.05-55(b) or NVIC 9-97.
Action required: 705 - Other - as specified
Due 5 February 2010
Resolved 21 July 2010
Resolution: Replaced trash cans with ones that met 46CFR 72.05-55(b).
Lifesaving › Lifejacket/PFD (General) › Storage
Issued 14 January 2006
Resolved
PFD locker was turned into a a deck crew locker room w/ PFD's still in space. Need to remove the lockers for crew.
Action required: 705 - Other - as specified
Due 27 February 2006
Resolved 27 February 2006
Fire Fighting › Portable CO2 Fire Extinguisher › Service
Issued 14 January 2006
No resolution recorded
All fire extinguishers did not recieve need service tags when they were done. Company was called to come out and issue tags to extinguishers.
Action required: 705 - Other - as specified
Due 27 January 2006 — due date passed with no resolution recorded
Resolution: Company was there same day to correct.
Fire Fighting › Fire Hoses › Condition
Issued 14 January 2006
No resolution recorded
All fire hoses need to be removed from rack, drained of residual water, and dried prior to placing back in rack.
Action required: 705 - Other - as specified
Due 21 January 2006 — due date passed with no resolution recorded
Resolution: All hoses drained and dried.
Fire Fighting › Structural Fire Protection - General › Accommodation Space Protection
Issued 14 January 2006
Resolved
Determine fire load for slot tech storage room and submit to MSC to be included in fire load calculations. Vsl determined that all the plastic containers had not been added to fire load.
Action required: 705 - Other - as specified
Due 20 February 2006
Resolved 27 February 2006
Documentation › Markings/Placards › Warning Signs
Issued 14 January 2006
Resolved
Need to restencile Emergency Escape hatch near fwd fire door. Paint has been worn off.
Action required: 705 - Other - as specified
Due 27 January 2006
Resolved 27 February 2006
Electrical › Electrical Distribution System (service) › Outlet Box
Issued 14 January 2006
Resolved
All cash cages need to ensure that either outlet boxes are installed or that only authorized power stripes in spaces are mounted. Cleaning also needs to be conducted behind all spaces where authorized power stripes are located.
Action required: 705 - Other - as specified
Due 27 January 2006
Resolved 27 February 2006
Lifesaving › Lifebuoys › Buoyant Lifeline
Issued 14 January 2006
Resolved
Replace lines on liferings that lead to light.
Action required: 705 - Other - as specified
Due 27 January 2006
Resolved 27 February 2006
Lifesaving › Rescue Boat › Hull (rigid)
Issued 19 April 2005
Resolved
Rescue boat has 1' puncture on the stbd side, mid ship below the waterline and navigation lights were broken.
Condition: Damaged By Earlier Event
Due 19 May 2005
Resolved 19 May 2005
Resolution: Rescue boat repaired.
Construction/Loadline › Penetrations › Gasket
Issued 16 November 2004
Resolved
Replace all outer deck hatch covers. All are dry rotted and need to be replaced.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 November 2004
Resolved 2 December 2004
Resolution: All gaskets replaced.
Construction/Loadline › Structures › Deck Plating
Issued 16 November 2004
Resolved
All outer decks need to be repaired. Large pockets of rust cover entire outer deck. Smallest rust hole is 6x8" in size. Vessel needs to remove rusted paint and non-skid and resurface the deck appropriately.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 December 2004
Resolved 8 December 2004
Resolution: Vessel states that completion of deck is 50%. Will monitor progress.
Engineering › Bilge Water Management System › Interface Detector
Issued 16 November 2004
Resolved
Bilge alarms were inadvertantly placed in ballast tanks 2, 3 and 4. Vessel had removed fuse to bilge alarms to prevent them from going off. Vessel needs to remove alarm and dead end wires in waterproof box.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 30 November 2004
Resolved 8 December 2004
Resolution: Bilge alarms in ballast tanks have been removed and wires placed in waterproof dead end box..
Engineering › Bilge Water Management System › Pump
Issued 16 November 2004
Resolved
Vessel has not tested bilge suction and have not incorporated into maintenance plan. Vessel required to determine most efficient way to test, incorportate and record results.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 November 2004
Resolved 8 December 2004
Resolution: Vessel has incorporated testing method. Will observe on next inspection.
Deck/Cargo › Holds/Tanks › Bulkhead
Issued 16 November 2004
Resolved
During ISE it was found that several voids/tanks had self tapping screws and bolts drilled through overhead in deck. Remove screws and make permenant repairs.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 November 2004
Resolved 2 December 2004
Resolution: All screws have been removed and deck has been repaired.
Communications › Alarms/Indicators › Fire Alarm
Issued 12 November 2004
Resolved
Vsls AEVADS announcement does not correspond with vsls EEP. Vessel is required to change AEVADS announcement to give proper direction to crew and passengers. Current announcement has crew/paxs proceeding to lifejacket donning location instead of proceeding to the nearest exit.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 21 November 2004
Resolved 8 December 2004
Resolution: New msg card has been installed and tested. Will confirm during Jan COI inspection.
Fire Fighting › Means of Escape › Escape Route Signs
Issued 5 October 2004
Resolved
Stencile escape hatches w/ "do not cover".
Condition: Unknown
Action required: 705 - Other - as specified
Due 12 October 2004
Resolved 6 October 2004
Resolution: Stencile is complete.
Documentation › Manuals/Policy Documentation › Instructions for On-board Maintenance (lifesaving)
Issued 5 October 2004
Resolved
Vessel has implemented the use of an electrical plan ob vsl to reduce the number of unauthorized power stripes. Vsl is updating electrical plan and pass along importance of PIC of any changes occur.
Condition: Unknown
Action required: 705 - Other - as specified
Due 5 November 2004
Resolved 20 October 2004
Resolution: Updated plan and trained each department manager on the importance of passing along information about the vessel.
Deck/Cargo › Holds/Tanks › Hatch Cover
Issued 5 October 2004
Resolved
Replace cover on void located in survallience room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 12 October 2004
Resolved 12 October 2004
Resolution: Hatch cover has been reinstalled.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Piping
Issued 5 October 2004
Resolved
Replace CO2 hose on middle bottle located in computer room.
Condition: Unknown
Action required: 705 - Other - as specified
Due 19 October 2004
Resolved 13 October 2004
Resolution: New hose was installed on CO2 bottle.
Electrical › Electrical Distribution System (service) › Wiring
Issued 5 October 2004
Resolved
Metal bands on all wires need to be installed. New wires continue to be ran, and eng. department is not kept in the loop of new installation or are unable to keep up w/ new installations.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 5 November 2004
Resolved 6 October 2004
Resolution: Metal bands have been installed on all new electrical runs.
Fire Fighting › Fixed CO2 Fire Extinguishing System
Issued 27 January 2004
Resolved
Flex hose on #4 CO2 bootle was cracked. CO2 rep will replace. LEGACY COMPONENT DESC: Piping
Condition: Unknown
Action required: 705 - Other - as specified
Due 27 February 2004
Resolved 3 March 2004
Resolution: New flex hose has been installed on CO2 system.
Electrical › Electrical Distribution System (service)
Issued 27 January 2004
Resolved
Install metal bands around wire runs throughout the vessel. LEGACY COMPONENT DESC: Wiring
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 27 February 2004
Resolved 3 March 2004
Resolution: Metal bands installed.
Engineering › Diesel Engine (propulsion-reduction gear)
Issued 27 January 2004
Resolved
Repair hole on #2 Generator muffler and develope someway to provent repeat puncture. LEGACY COMPONENT DESC: Silencer (exhaust)
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 3 February 2004
Resolved 3 March 2004
Resolution: Repaired hole in muffler.
Electrical › Electrical Distribution System (service)
Issued 21 January 2004
Resolved
Vessel had daisy chained extension cords and surge protectors. Need to install additional outlets to reduce the need for excesive surge protectors LEGACY COMPONENT DESC: Outlet Box
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 February 2004
Resolved 3 March 2004
Resolution: Additional outlets installed.
Electrical › Electrical Distribution System (service)
Issued 21 January 2004
Resolved
Remove all extension cords throughout vessel. LEGACY COMPONENT DESC: Overcurrent Device
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 February 2004
Resolved 3 March 2004
Resolution: Completed.
Lifesaving › Lifebuoys
Issued 25 November 2003
Resolved
Replace battery in life ring light on port fourth deck exterior.
Due 1 December 2003
Resolved 1 December 2003
Resolution: Battery replaced.
Documentation › Safety/Response Plans/Programs
Issued 25 November 2003
Resolved
Revise fire control plan to show required IMO symbology. LEGACY COMPONENT DESC: Fire Control Plans
Due 29 January 2004
Resolved 15 January 2004
Resolution: Will reconfirm new fire control plan at COI.
Fire Fighting › Fixed Fire Detection System
Issued 25 November 2003
Resolved
Ensure all smoke detectors/alarms are working properly.
Due 1 December 2003
Resolved 1 December 2003
Electrical › Electric Supply System (service)
Issued 25 November 2003
Resolved
Remove all power strips and propose an alternative method of replacement.
Due 1 December 2003
Resolved 29 December 2003
Resolution: Sent in alternate method.
Construction/Loadline › Penetrations
Issued 25 November 2003
Resolved
Plug camera hole in ceiling, 1st deck aft corner.
Due 1 December 2003
Resolved 1 December 2003
Fire Fighting › Automatic Sprinkler System
Issued 25 November 2003
Resolved
Remove all gear that is stowed above the sprinkler zone line in vault man trap, slot repair stowage and aft liquor stowage.
Due 1 December 2003
Resolved 1 December 2003
Accommodation/Occupational Safety › Occupational Safety
Issued 25 November 2003
Resolved
Label "Push up- To exit" on escape scuttle in computer room.
Due 1 December 2003
Resolved 1 December 2003
Resolution: New labels made and posted.
Electrical › Electrical Distribution System (service)
Issued 25 November 2003
Resolved
Replace plastic wire ties (with metallic) on overhead wire run at port forward engineroom. LEGACY COMPONENT DESC: Cable
Due 1 December 2003
Resolved 1 December 2003
Resolution: Continuous process.
Fire Fighting › Structural Fire Protection - General
Issued 25 November 2003
Resolved
Replace structural fire protection above tool cage in engineroom.
Due 1 December 2003
Resolved 1 December 2003
Accommodation/Occupational Safety › Occupational Safety
Issued 25 November 2003
Resolved
Replace belt guard on #2 sewage pump/motor coupling. LEGACY COMPONENT DESC: Guards for Exposed Hazards
Due 1 December 2003
Resolved 1 December 2003
Engineering › Fuel Oil Service System
Issued 25 November 2003
Resolved
Repair remote fuel oil cut out valve on port fuel oil tank. LEGACY COMPONENT DESC: Piping
Due 9 December 2003
Resolved 8 December 2003
Resolution: Part ordered and replaced.
Engineering › Non-conventional Propulsion/Steering
Issued 24 February 2003
Resolved
Make repairs and prove proper operation of port Z drive.
Due 24 March 2003
Resolved 6 March 2003
Electrical › Electrical Distribution System (service)
Issued 29 January 2003
Resolved
Provide a log of ground fault readings. Record status at the start of C.E. watch and note wrok done to clear the ground. LEGACY COMPONENT DESC: Ground Detection
Due 1 March 2003
Resolved 3 February 2003
Electrical › Electrical Distribution System (service)
Issued 25 October 2002
Resolved
Ensure all electrical penetrations thru A-60 decks are completed as original or by an accepted equivalent. LEGACY COMPONENT DESC: Wiring
Due 23 January 2003
Resolved 29 January 2003
Fire Fighting › Combustible Materials
Issued 25 October 2002
Resolved
Provide fire load calculations for stair towers with cigarette machines. Prove fire load is within standards or remove machines. LEGACY COMPONENT DESC: Furniture/Furnishings
Due 15 November 2002
Resolved 8 January 2003
Fire Fighting › Automatic Sprinkler System › Pressure Tank
Issued 10 October 2002
Resolved
Prove proper operation of sprinkler tank low level and low pressure alarms.
Due 10 November 2002
Resolved 11 October 2002
Resolution: Corrected.
Fire Fighting › Structural Fire Protection - General
Issued 10 October 2002
Resolved
Replace structural fire protection in engineroom overhead, port side, forward bulkhead near #4 genset.
Due 10 November 2002
Resolved 11 October 2002
Resolution: Corrected.
Electrical › Electrical Distribution System (service) › Ground Detection
Issued 10 October 2002
Resolved
Clear ground on main switchboard casino bus "B".
Due 10 November 2002
Resolved 11 October 2002
Resolution: Corrected.
Fire Fighting › Ventilation Systems
Issued 11 July 2002
Resolved
Prove proper operation of fire dampeners 30 and 33. LEGACY COMPONENT DESC: Ducts
Due 11 August 2002
Resolved 16 August 2002
Fire Fighting › Miscellaneous Items
Issued 11 July 2002
Resolved
Provide spanner wrench at main deck hose station.
Due 11 August 2002
Resolved 16 August 2002
Lifesaving › Embarkation Appliances/Stations
Issued 11 July 2002
Resolved
Provide second boarding ladder for rescue boat. LEGACY COMPONENT DESC: Accessability
Due 11 August 2002
Resolved 16 August 2002
Accommodation/Occupational Safety › Potable Water System
Issued 11 July 2002
Resolved
Remove PVC piping at new main deck bar installation. LEGACY COMPONENT DESC: piping
Due 11 August 2002
Resolved 16 August 2002
Communications › Alarms/Indicators › General Alarm
Issued 17 April 2002
Resolved
Prove operation of general alarm bell on 3rd deck.
Due 19 April 2002
Resolved 19 April 2002
Resolution: Corrected.
Communications › Alarms/Indicators › General Alarm
Issued 17 April 2002
Resolved
Provide sign at general alarm bell on 3rd deck.
Due 17 May 2002
Resolved 19 April 2002
Resolution: Corrected.
Operations/Management
Issued 17 April 2002
Resolved
Provide muster list for approval.
Due 17 May 2002
Resolved 25 April 2002
Resolution: Corrected.
Operations/Management › Drills/Instruction
Issued 17 April 2002
Resolved
Provide training records for all persons on muster list.
Due 17 May 2002
Resolved 25 April 2002
Resolution: Corrected.
Accommodation/Occupational Safety › Occupational Safety › Receptacle Outlet
Issued 17 April 2002
Resolved
Properly install 110v duplex box in 3rd deck high limit cage.
Due 17 May 2002
Resolved 19 April 2002
Resolution: Corrected.
Accommodation/Occupational Safety › Occupational Safety › Portable Electric Equipment/Appliances
Issued 17 April 2002
Resolved
Remove extension cord made of marine cable in 3rd deck aft galley.
Due 17 May 2002
Resolved 19 April 2002
Resolution: Corrected.
Accommodation/Occupational Safety › Occupational Safety › Receptacle Outlet
Issued 17 April 2002
Resolved
Provide outlet cover on 110v duplex receptacle and install outlet boxes in 3rd deck cage.
Due 17 May 2002
Resolved 19 April 2002
Resolution: Corrected.
Accommodation/Occupational Safety › Occupational Safety
Issued 17 April 2002
Resolved
Provide sign on emergency escape hatch at stern main deck slots.
Due 17 May 2002
Resolved 19 April 2002
Resolution: Corrected.
Lifesaving › Embarkation Appliances/Stations
Issued 17 April 2002
Resolved
Repair/ replace boarding ladder for port rescue boat.
Due 17 May 2002
Resolved 19 April 2002
Resolution: Corrected. Replaced with temp aluminum ladder. Vessel to fabricate a new ladder,
Electrical › Lighting (emergency) › Battery Operated Lantern
Issued 17 April 2002
Resolved
Repair/replace inoperative emergency light in aft hold deck office space.
Due 17 May 2002
Resolved 19 April 2002
Resolution: Corrected.
Fire Fighting › Automatic Sprinkler System
Issued 23 January 2002
Resolved
Conduct internal examine of sprinkler storage tank at next COI inspection. LEGACY COMPONENT DESC: Pressure Tank
Condition: Unknown
Due 23 January 2003
Resolved 17 April 2002
Resolution: Corrected.
Fire Fighting › Structural Fire Protection - General
Issued 23 January 2002
Resolved
Repair fire screen doors # 8,11,17
Condition: Improper/Lack of Maintenance
Due 25 April 2002
Resolved 17 April 2002
Resolution: Corrected.
Fire Fighting › Means of Escape
Issued 23 January 2002
Resolved
Install labels on main deck stb side doors fwd and aft stating this is not a exit.
Condition: Improper/Lack of Maintenance
Due 26 April 2002
Resolved 17 April 2002
Resolution: Corrected.
Fire Fighting › Means of Escape
Issued 23 January 2002
Resolved
Provide proper directions for egress on 2nd deck Stb aft.
Condition: Improper/Lack of Maintenance
Due 26 April 2002
Resolved 17 April 2002
Resolution: Corrected.
Fire Fighting
Issued 8 November 2001
Resolved
Provide the correct number of qualified and trained deckhands as required on the Certificate of Inspection.
Condition: Unknown
Due 8 November 2001
Resolved 11 December 2001
Personnel › Manning/Qualifications › Minimum Safe Manning
Issued 8 November 2001
Resolved
Minimum Safe Manning - Missing
Due 8 November 2001
Resolved 8 November 2001
Fire Fighting
Issued 11 September 2001
Resolved
Renew Recalled sprinkler heads in sprinkler system._x001C_
Condition: Unknown
Due 11 November 2001
Resolved 17 April 2002
Resolution: Corrected.
Lifesaving
Issued 11 September 2001
Resolved
PROVIDE TRAINING CHECK LIST AND ADDITIONAL TRAINING TO SENIOR DECKHANDS.
Condition: Unknown
Due 19 October 2001
Resolved 17 April 2002
Resolution: Corrected.
Documentation
Issued 24 April 2001
Resolved
PROVIDE PROOF OF MEETING TITLE 33 CFR 130 CERTIFICATE OF FINANCIAL RESPONSIBILITY(COFR) REQUIREMENTS BY OBTAINING A CURRENT VALID COFR AND PROVIDING PROOF TO THIS OFFICE.
Condition: Unknown
Due 15 May 2001
Resolved 15 May 2001
Engineering
Issued 26 July 2000
Resolved
BAND PADDLE WHEEL BOARDS OR REPLACE THOSE WITH FRACTURES GREATER THAN 12 INCHES AT EITHER ENDS AS NECESSARY (FRACTURES LESS THAN 12 INCHES MAY BE BANDED).
Condition: Unknown
Due 26 July 2000
Resolved 26 July 2000
Fire Fighting
Issued 4 November 1998
Resolved
IAW NFPA 13, INSTALL RETURN LOOPS ON THE TWO (2) SPRINLKER HEADS WHICH_x001C_ WERE RELOCATED PORT SIDE MAIN DECK IN VICINITY OF "WHEEL OF FORTUNE" GAMINGMACHINES.
Condition: Unknown
Due 4 November 1998
Resolved 4 November 1998
Electrical
Issued 4 August 1998
Resolved
SUBMIT PROPOSAL TO [name withheld] TO CORRECT 24 VOLT ENGINE ROOM PANEL POWER SUPPLY.
Condition: Unknown
Due 7 September 1998
Resolved 27 August 1998
Lifesaving
Issued 30 April 1998
Resolved
PROVIDE LOGS OF DRILLS AND TRAINING FOR ALL PERSONS ON MUSTER LIST IAW 46 CFR 199.180.
Condition: Unknown
Due 30 April 1998
Resolved 7 May 1998
Fire Fighting
Issued 30 April 1998
Resolved
MODIFY AEVADS MESSAGING TO PROVIDE SEPERATE ZONE FOR EACH STAIRTOWER.
Condition: Unknown
Due 20 June 1998
Resolved 26 June 1998
Lifesaving
Issued 30 April 1998
Resolved
MARK LIFESAVING EQUIPMENT IAW 46 CFR 199.178.
Condition: Unknown
Due 18 May 1998
Resolved 18 May 1998
Accommodation/Occupational Safety
Issued 5 August 1997
Resolved
PROVIDE FIRE LOAD CALCULATIONS FOR HOLD DECK SPACES TO MSO NEW ORLEANS FOR APPROVAL.
Condition: Unknown
Due 5 August 1997
Resolved 5 August 1997
Fire Fighting
Issued 5 August 1997
Resolved
INSULATE ALL PIPING WITHIN A-60 BOUNDARIES WITH CG APPROVED A-60 INSULATION.
Condition: Unknown
Due 5 August 1997
Resolved 5 August 1997
Lifesaving
Issued 7 May 1997
Resolved
PROVIDE DOCUMENTATION OF ANNUAL SERVICING OF LIFERAFTS.
Condition: Unknown
Due 7 May 1997
Resolved 7 May 1997
Construction/Loadline
Issued 8 August 1996
Resolved
PROVE PROPER OPERATION OF CLASS III WTD'S IN HOLD DECK IN ALL MODES.
Condition: Unknown
Due 8 August 1996
Resolved 8 August 1996
Documentation
Issued 7 May 1996
Resolved
SUBMIT REVISED CALCULATIONS FOR NEW STABILITY LETTER/DEAD WEIGHT SURVEY. INCLUDE ALL REVISIONS IN FIRELOAD/WEIGHT WITH THIS SUBMITTAL.
Condition: Unknown
Due 7 May 1996
Resolved 7 May 1996
Fire Fighting
Issued 7 May 1996
Resolved
REPAIR OR REPLACE FOR PROPER OPERATION, THE AUTOMATIC OPERATING VENTILATIONLOUVER MOTOR UNITS, IN THE EMERGENCY GENERATOR ROOM
Condition: Unknown
Due 7 May 1996
Resolved 7 May 1996
Fire Fighting
Issued 1 February 1996
Resolved
Prove proper operation of fire damperon main deck port side aft.
Condition: Unknown
Due 1 February 1996
Resolved 1 February 1996
Fire Fighting
Issued 1 February 1996
Resolved
Provide proper gap of maximum 1/8 inch between all fire doors.
Condition: Unknown
Due 1 February 1996
Resolved 1 February 1996
Fire Fighting
Issued 1 February 1996
Resolved
Establish fire load of less than three pounds per square foot on second casino deck.
Condition: Unknown
Due 1 February 1996
Resolved 1 February 1996
Fire Fighting
Issued 1 February 1996
Resolved
Provide proper clearances for fire screen doors on hold deck. (Max 1/2 inch)
Condition: Unknown
Due 1 February 1996
Resolved 1 February 1996
Fire Fighting
Issued 1 February 1996
Resolved
Prove proper alarm and AEVADS message sequence in accordance with_x001C_ NVIC 8-93.
Condition: Unknown
Due 1 February 1996
Resolved 1 February 1996
Fire Fighting
Issued 1 February 1996
Resolved
Prove proper operation of relief valves on sprinkler tanks.
Condition: Unknown
Due 1 February 1996
Resolved 1 February 1996
Engineering
Issued 1 February 1996
Resolved
Prove proper operation of Z-drive propulsion from all stations.
Condition: Unknown
Due 1 February 1996
Resolved 1 February 1996
Accommodation/Occupational Safety
Issued 9 August 1995
Resolved
PROVE SMALL COOKING GRILL IN DELI MEETS UL 197 & THE MARINE SUPPLEMENT IAW 46 CFR 111.77-3.
Condition: Unknown
Due 9 August 1995
Resolved 9 August 1995
Electrical
Issued 9 August 1995
Resolved
PROPERLY TERMINATE DEAD-ENDED WIRING IN ELECTRICAL PANELS AND BATTERY BOXESIN EMERGENCY GENERATOR ROOM.
Condition: Unknown
Due 9 August 1995
Resolved 9 August 1995
Fire Fighting
Issued 9 August 1995
Resolved
PROVIDE CORRECT TYPE AND NUMBER OF SPARE SPRINKLERS IAW NFPA 13.
Condition: Unknown
Due 9 August 1995
Resolved 9 August 1995
Fire Fighting
Issued 25 May 1995
Resolved
PROVE PROPER OPERATION OF VENTILLATION LOUVERS IN THE EMERGENCY GENERATOR ROOM.
Condition: Unknown
Due 25 May 1995
Resolved 25 May 1995
Fire Fighting
Issued 25 May 1995
Resolved
REPLACE GAUGE TO SPRINKLER SYSTEM SWITCH IN OVERHEAD NEAR [name withheld] AND SURVEILANCE ROOM.
Condition: Unknown
Due 25 May 1995
Resolved 25 May 1995
Navigation
Issued 25 May 1995
Resolved
MAKE PROPER REPAIRS AND PROVE OPERATION OF VESSELS SOUND POWERED TELEPHONE SYSTEM.
Condition: Unknown
Due 25 May 1995
Resolved 25 May 1995
Lifesaving
Issued 25 May 1995
Resolved
PROVIDE DOCUMENTATION OF EXPIRATION DATE OF HYDROSTATIC RELEASES ON ALL LIFERAFTS OR REPLACE.
Condition: Unknown
Due 25 May 1995
Resolved 25 May 1995
Fire Fighting
Issued 1 February 1995
Resolved
PROVIDE(SUBMIT) REVISED TEST PROCEDURES FOR FIRE DETECTION SYSTEM AND AEVADS.
Condition: Unknown
Due 1 February 1995
Resolved 1 February 1995
Lifesaving
Issued 1 February 1995
Resolved
INSTALL AND PROVE PROPER OPERATION OF POWER OPERATED WINCHES FOR P/S RESCUEBOATS TO THE SATISFACTION OF THE ATTENDING MARINE INSPECTOR.
Condition: Unknown
Due 1 February 1995
Resolved 1 February 1995
Lifesaving
Issued 1 February 1995
Resolved
SUBMIT VESSEL CONTINGENCY PLAN TO COGNIZANT OCMI FOR APPROVAL.
Condition: Unknown
Due 1 February 1995
Resolved 1 February 1995
Fire Fighting
Issued 1 February 1995
Resolved
SUBMIT REVISED SPRINKLER MANUAL THAT IS VESSEL SPECIFIC ON THE OPERATION, MAINTENANCE, AND TESTING IAW 46 CFR 76.25-35(j).
Condition: Unknown
Due 1 February 1995
Resolved 1 February 1995
Lifesaving
Issued 9 January 1995
Resolved
INSTALL AND PROVE PROPER OPERATION OF POWER OPERATED WINCHES FOR P/S RESCUEBOATS TO THE SATISFACTION OF THE ATTENDING MARINE INSPECTOR.
Condition: Unknown
Due 15 March 1995
Resolved 3 April 1995
Fire Fighting
Issued 9 January 1995
Resolved
PROVIDE (SUBMIT) REVISED TEST PROCEDURES FOR FIRE DETECTION SYSTEM AND AEVADS.
Condition: Unknown
Due 1 March 1995
Resolved 3 April 1995
Lifesaving
Issued 9 January 1995
Resolved
SUMIT VESSEL CONTINGENCY PLAN TO COGNIZANT OCMI FOR APPROVAL.
Condition: Unknown
Due 1 March 1995
Resolved 3 April 1995
Fire Fighting
Issued 9 January 1995
Resolved
SUBMIT REVISED SPRINKLER MANUAL THAT IS VESSEL SPECIFIC ON THE OPERATION, MAINTENANCE, AND TESTING IAW 46 CFR 76.25-35(j).
Condition: Unknown
Due 1 March 1995
Resolved 3 April 1995