Records from 1995 to 2025. Most recent: inspection, 9 December 2025.
A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.
Inspection history · 83
9 December 2025
Annual Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 8280367
10 July 2025
Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 8182323
15 April 2024
Annual Inspection
Physical examination · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7895828
1 December 2022
Deficiency Check · Annual Inspection
Physical examination · Outer Continental Shelf National Center of Expertise · Activity 7603121
22 June 2022
Administrative Inspection
Administrative · USCG Heartland District (ocs) · USCG Heartland District (CGD-H) · Activity 7499331
18 February 2021
COI Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7142285
25 June 2020
Annual Inspection · MTSA Verification
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 7145255
25 November 2019
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6862129
23 August 2019
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6792551
7 June 2019
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6706485
23 May 2019
COI Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6696377
30 October 2018
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6570909
24 July 2018
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6489615
22 March 2018
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6397779
6 December 2017
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6319340
17 May 2017
In-Service Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6152598
22 February 2017
Administrative Inspection · Construction Oversight
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6092840
17 February 2017
Administrative Inspection · Construction Oversight
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6090355
26 January 2017
Deficiency Check · Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6079669
4 October 2016
Deficiency Check
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6020058
20 September 2016
Annual Inspection · Construction Oversight
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6004926
12 September 2016
Construction Oversight · Administrative Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5998596
29 June 2016
Administrative Inspection
Administrative · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5923951
30 March 2016
COI Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5844365
6 October 2014
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 4999905
18 March 2014
Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 4817424
28 February 2012
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 4252694
5 January 2012
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 4219264
5 August 2011
Damage Survey
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 4109743
5 August 2011
Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 4110233
29 July 2011
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 4102276
26 October 2010
Administrative Inspection · Internal Structural Exam · Hull Examination
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3884363
23 March 2010
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3715720
22 March 2010
DAPI Audit · Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3715635
24 March 2009
Annual Inspection · Administrative Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3441588
9 July 2008
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3264674
9 May 2008
Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3205393
9 April 2008
Annual Inspection · Administrative Inspection · MTSA Verification
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3185521
10 May 2007
Hull Examination
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2925925
26 March 2007
Construction Oversight · MTSA Verification · Annual Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2896012
26 January 2007
Construction Oversight
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2863276
7 April 2006
COI Inspection
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2619274
20 March 2006
Damage Survey
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2606539
18 March 2006
Type not recorded
No type recorded · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2608270
11 January 2006
Examination of Repairs
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2574522
10 January 2006
Damage Survey
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3213538
4 December 2005
Construction Oversight
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 2574500
29 August 2005
Type not recorded
No type recorded · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 2531667
15 July 2005
MTSA Verification
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 2427944
16 June 2005
Annual Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 2425659
11 May 2005
Administrative Inspection
Administrative · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 2426450
14 April 2005
In-Service Inspection · Examination of Repairs
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 2286800
19 August 2004
Administrative Inspection · Annual Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 2167392
19 August 2004
MTSA Verification
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 2201341
6 July 2004
Administrative Inspection
Administrative · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 2123169
4 December 2003
Examination of Repairs
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1957597
22 May 2003
Annual Inspection · Construction Oversight
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1799249
10 March 2003
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1749978
17 October 2002
In-Service Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1699023
12 August 2002
Examination of Repairs
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1660896
20 May 2002
Hull Examination · Annual Inspection
Physical examination · MIDET HARVEY CANAL DETAIL · USCG Heartland District (CGD-H) · Activity 1618599
22 March 2002
Damage Survey
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1495751
20 March 2002
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1495966
10 May 2001
COI Inspection · Hull Examination
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1469701
5 April 2001
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1062227
23 August 2000
Deficiency Check
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 821159
19 May 2000
Re-Inspection · Hull Examination
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1460447
27 May 1999
Administrative
Administrative · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 1081512
21 May 1999
COI Inspection · Hull Examination
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1448002
5 March 1999
Administrative
Administrative · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 801868
12 May 1998
Re-Inspection · Hull Examination
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 791928
30 June 1997
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 763044
21 May 1997
COI Inspection
Physical examination · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1465328
9 May 1997
Type not recorded
No type recorded · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 190874
23 April 1997
Hull Examination · Initial Construction-Excluding Oversight
Physical examination · MSO Corpus Christi · USCG Heartland District (CGD-H) · Activity 1459288
23 October 1996
Administrative
Administrative · MSO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1160161
18 September 1996
Type not recorded
No type recorded · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 1438486
12 September 1996
Construction Oversight
Physical examination · Activities Europe · Activity 1262776
12 September 1996
Initial Construction-Excluding Oversight
Physical examination · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 1374843
15 August 1996
Construction Oversight
Physical examination · Activities Europe · Activity 951482
3 May 1996
Construction Oversight
Physical examination · Activities Europe · Activity 951481
3 November 1995
Construction Oversight
Physical examination · Activities Europe - OLD · USCG Northeast District (CGD-NE) · Activity 1265283
19 July 1995
Construction Oversight
Physical examination · Activities Europe - OLD · USCG Northeast District (CGD-NE) · Activity 1265450
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 2 December 2022
Resolved
The emergency equipment provided, regardless of whether or not required by this subchapter, shall be maintained in good condition at all times. The annual servicing report from Fire Safety Systems (FSS) listed discrepancies and required corrective actions for portable and fixed fire extinguishing and suppression systems and fire detection system. While corrective actions were in process, crew could not show that all items had been sufficiently addressed. Implement corrective actions and provide documentation proving completion of discrepant items in the July2022 FSS annual servicing report.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 January 2023
Resolved 20 December 2022
Resolution: Provided documentation (purchase orders notated with line item status) addressing discrepant items in the annual servicing report.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 2 December 2022
Resolved
The emergency equipment provided, regardless of whether or not required by this subchapter, shall be maintained in good condition at all times. During spot checks of the lifesaving capsules onboard, observed the winch brake on Lifeboat #4 to be "stuck" and preventing the boat from being lowered from the stowed position in the davit. While the crew was able to free the brake, this is an atypical occurrence on this particular make/model of equipment. Also observed a removed cotter pin on top of the winch for Lifeboat #1. While the winch was satisfactorily tested, it was not apparent if the cotter pin was missing or left over from servicing. The servicing reports for the four boats currently onboard (#1, 2, 4 and 5) also had corrective items listed without documentation attesting to completion. Confer with Survival Systems International (SSI) (OEM and the last service provider) to determine why the brake stuck on Lifeboat #4 and any mitigations to prevent future occurrences and ensure that brake components on Lifeboat #1 were correctly restored to operational condition. Provide documentation showing discrepancy corrections for items listed in the July/September2022 SSI servicing reports.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 January 2023
Resolved 19 December 2022
Resolution: 12Dec- SSI service reports provided verifying brake were correctly assembled and fully operational on the four LB stations listed. Recommended mitigation to prevent stuck brakes was to lower the boats twice per month. 19Dec- annual report def's corrected.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 2 December 2022
Resolved
Each holder of a lease or permit under the Act shall ensure that all places of employment within the lease area or within the area covered by the permit on the OCS are maintained in compliance with workplace safety and health regulations of this part and, in addition, free from recognized hazards. Observed several stowage cabinets in the SW Column upper utility level not secured that could tip during dynamic motion of the facility, a spare portable extinguisher improperly secured for an extended period in Turbine Generator Room #2 (ZAN-702) and an eyewash station outside of the N door to the MCC Room lacking enough pressure to displace the protective cover. These examples pose a risk to personnel onboard that can easily be overlooked. Conduct a full walk-through of the facility to ensure that all such hazards are correctly mitigated. A statement from the PIC attesting to completion of the same is sufficient documentation to show completion of this requirement.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 January 2023
Resolved 12 December 2022
Resolution: Provided documentation showing the correction of all cited examples in the deficiency. Addt'l eyewash stations were found that required pressure regulator adjustments or eyewash heads that require replacement (PO provided for the latter).
04 - Emergency Systems › N/A - No Subsystem › Emergency fire pump and its pipes
Issued 23 May 2019
Resolved
Each holder of a lease shall ensure that all places of employment on the OCS are maintained in compliance with workplace safetyand in addition free from recognized hazards. The compressed air start piping on the fire pumps is rusted and deteriorated. Make repairs to wasted piping necessary to start fire pump. 33CFR142.4
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 23 June 2019
Resolved 12 August 2019
Resolution: Received email including pictures of completed replacement of the firepump piping.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 23 May 2019
Resolved
Each cable installation must meet sections 25, except 25.11 of IEEE 45-2002. Cable installations through bulkheads in elec. workshop (2) were installed incorrectly. Audit and make repairs to incorrectly installed transits. 46CFR111.60-5(a)
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 23 June 2019
Resolved 18 June 2019
Resolution: Received email confirmation of completion.
01 - Certificates & Documentation › 013 - Documents › Cargo information
Issued 23 May 2019
Resolved
The transfer procedures required by 33CFR 155.720 must contain... Ensure transfer procedures contain all required information. 33 CFR 155.750(a)
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 23 June 2019
Resolved 18 June 2019
Resolution: Received email confirmation showing completion.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 23 May 2019
Resolved
Diesel vent wasted on the storage tank (southwest hull column), crop and renew. 46CFR 56.50-85
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 23 July 2019
Resolved 15 July 2019
Resolution: Received email from [name withheld] stating gooseneck has been refurbished.
Operations/Management › Drills/Instruction › Launching/Recovery of Survival Craft
Issued 26 January 2017
Resolved
Operating instructions for launching lifeboats are missing at multiple locations. Post lifeboat launching instructions.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 17 May 2017
Resolution: Instructions were posted
Documentation › Manifests/Lists › Muster List/Emergency Instructions
Issued 26 January 2017
Resolved
Emergency instructions for donning lifejackets are missing at both muster locations. Provide instructions for donning lifejackets.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 27 January 2017
Resolution: Printed out instructions and posted by crew. Cleared during inspection.
Lifesaving › Liferaft Equipment › Instructions (immediate action)
Issued 26 January 2017
Resolved
Liferafts are not marked with appropriate symbols for stowage or numbered. Mark all liferafts and stowage locations.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 17 May 2017
Resolution: Proper symbols were installed and liferafts numbered.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 26 January 2017
Resolved
Emergency lights throughout the unit are not marked or improperly marked. Conduct survey of unit and mark all emergency lights.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 17 May 2017
Resolution: All E-lights were idnetified and marked.
Lifesaving › Lifejacket/PFD (General) › Marking
Issued 26 January 2017
Resolved
Lifejackets for the FRB are of recreational/whitewater rafting use and are not CG approved. Replace lifejackets or workvests with CG approved type.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 17 May 2017
Resolution: Incorrect lifejackets were removed and USCG approved ones were placed in use.
Fire Fighting › Means of Escape › Landings
Issued 26 January 2017
Resolved
3 of the 4 emergency egress ladders leading to the waterline are secured due to unsafe/excessive corrossion. At a minimum, two means of escape are required from the unit. Repair or replace egress ladders for use.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 17 May 2017
Resolution: Unit now has 2 widely seperated emergency escapes.
Lifesaving › Launching Appliances › Block
Issued 26 January 2017
Resolved
Liferafts stowed at SW column are stowed such that rafts are unable to launch. Reinstall liferafts for float free launching.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 17 May 2017
Resolution: Liferafts have been configured for float free launching as best as possible.
Accommodation/Occupational Safety › Potable Water System › General
Issued 26 January 2017
Resolved
Multiple eyewash stations throughout unit have inadequate/low pressure. Flush and prove proper operation of all eyewash stations.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 17 May 2017
Resolution: Eyewash station now have proper pressure
Fire Fighting › Structural - A Class Divisions › Main Galleys
Issued 26 January 2017
Resolved
An "A" class boundary in dry stores above the ANSIL system does not appear to be an approved installation, with red firestop installed over fiberglass containing multiple holes. Provide documentation that installation is approved.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 6 June 2018
Resolution: MSC Letter authorizing a one off equivalency. C2-1800623. Ensured all condicitons were met during a def check exam.
Fire Fighting › Structural - A Class Divisions › Doors
Issued 26 January 2017
Resolved
Galley door leading from deck 1 to dry stores does not self close. Adjust door to properly close to maintain Class "A" fire boundary.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 27 January 2017
Resolution: Door adjusted and closes properly. Corrected during inspection.
Fire Fighting › Structural - A Class Divisions › Doors
Issued 26 January 2017
Resolved
Laundry door latch does not close, allowing a gap which could allow for the spread of fire and smoke from a laundry fire to spread on upper accommodiation corridor. Replace latch to correct class "A" fire boundary.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 30 January 2017
Resolution: Received email from [name withheld] (shell) with pictures of new latch installed, correcting issue. Cleared def.
Operations/Management › Drills/Instruction › Fire
Issued 26 January 2017
Resolved
Fire and abandonship drills were poorly executed. Fire teams were unable to quickly don firefighting equipment or activate installed face mask comms equipment. Also, during abandonship drill a missing man pulled by the CG during the drill was mistakenly accounted for. OIM shall provide documentation to CG of proper donning and use of firefighting equipment.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 17 May 2017
Resolution: Unit has retrainned all personnel.
Documentation › Safety/Response Plans/Programs › Fire Control Plans
Issued 26 January 2017
Resolved
General arrangement and FCP has been revised multiple times and is inaccurate and must be reviewed and re-approved by the CG.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 17 May 2017
Resolution: Shell provided new plans. USCG inspectors walked plan. Def cleared.
Fire Fighting › Structural - A Class Divisions › Stairways
Issued 26 January 2017
Resolved
HVAC chase door on 3rd deck in stairwell has been drilled with four holes, compromising A class boundary. Replace chase door.
Action required: 705 - Other - as specified
Due 27 February 2017
Resolved 17 May 2017
Resolution: Door was replaced.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 26 January 2017
Resolved
Obstruction lights are not flashing in unison nor displaying proper flashing characteristics (60 times a min). Repair or replace obstruction lights.
Due 27 February 2017
Resolved 17 May 2017
Resolution: Obstruction lights are now flashing in unision.
Engineering › Gas Turbine (propulsion-electric) › Vent Damper
Issued 26 January 2017
Resolved
Louver for #2 generator room does not fully close, compromising FM200 system seal. Repair or replace louver.
Due 27 February 2017
Resolved 27 January 2017
Fire Fighting › Structural - A Class Divisions › Service Spaces
Issued 30 March 2016
Resolved
Laundry chute door does not latch closed. Repair latch to original condition.
Due 30 April 2016
Resolved 18 April 2016
Resolution: Received email from OIM stating latch was repaired.
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 30 March 2016
Resolved
The fire doors to the main stairtower on the first and third deck were modified and holes drilled into the door. Renew fire doors with approved fire doors.
Due 30 September 2016
Resolved 4 October 2016
Resolution: Recieved email from vessel rep with door approval and pictures of installed doors.
Deck/Cargo › Cargo Transfer (solid) › General
Issued 20 March 2006
Resolved
Provide laboratory analysis of remining sections of boom hoist wire rope to include % of stranding, breaking strength, extent of corrosion, wastage, elongation, amoumt of residual lubrication present, ect...and any mention of adverse reaction to wire ropes from flare boom heat. Legacy component desc: crane.
Condition: Unknown
Due 21 May 2006
Resolved 21 May 2006
Resolution: Analysis provided.
Deck/Cargo › Cargo Transfer (solid) › General
Issued 20 March 2006
Resolved
Provide status breifing to [name withheld] as to the progress of the investigation to date to include photographs, witness statements, copies of inspection records, audit records, and most recent proof of load test on #3 crane. Coordinate with [name withheld] for this presentation.
Condition: Unknown
Due 21 May 2006
Resolved 17 April 2006
Deck/Cargo › Cargo Transfer (solid) › General
Issued 20 March 2006
Resolved
Provide final investigation report to [name withheld] when complete.
Condition: Unknown
Due 21 May 2006
Resolved 21 May 2006
Resolution: Report provided.
Deck/Cargo › Cargo Transfer (solid) › General
Issued 20 March 2006
Resolved
# 3 crane shall not be placed into service until all repairs are complete. A post repair proof laod test must be witnessed by USCG Inspector from New Orleans.
Condition: Unknown
Due 21 May 2006
Resolved 17 April 2006
Resolution: Completed load test to API standards.
Lifesaving › Rescue Boat › Construction
Issued 16 June 2005
Resolved
Provide CG Approval for rescue boat and davit or prove one lifeboat can act as the required rescue boat.
Due 17 July 2005
Resolved 27 June 2005
Accommodation/Occupational Safety › Occupational Safety › Deck Rail
Issued 16 June 2005
Resolved
Provide eye wash stations that provide clear water to all stations.
Due 17 July 2005
Resolved 6 July 2005
Electrical › Lighting (service) › Lighting Fixture
Issued 16 June 2005
Resolved
Prove TODCO tracer monitor on drill floor alarms or shuts down upon loss of purge.
Due 17 July 2005
Resolved 6 July 2005
Fire Fighting › Firemans Outfit › Helmet
Issued 16 June 2005
Resolved
Prove equivilency for ANSI 2-89.1-1989 on firemans helmets or provide this standard.
Due 17 July 2005
Resolved 27 June 2005
Fire Fighting › Portable Dry Chemical Fire Extinguisher
Issued 23 May 2002
Resolved
Replace red tagged portable fire extinguishers in warehouse. LEGACY COMPONENT DESC: Service
Condition: Placed in Improper Service
Due 30 May 2002
Resolved 26 May 2002
Stability
Issued 20 May 2002
Resolved
Update Stability letter to reflect revision to Operating manual Volume 1 Rev 1 dated 8/20/00.
Due 23 June 2002
Resolved 26 May 2002
Deck/Cargo
Issued 20 May 2002
Resolved
Conduct proof test on crane #1 IAW 46 CFR 107.260 and 107.259. Provide proof of annual exam and demonstrate exam findings and recommendations.
Due 23 June 2002
Resolved 6 June 2002
Engineering › Compressed Air System (control)
Issued 20 May 2002
Resolved
Provide original ASME UA-1 reports for two each instrument air recievers and one waste heat volume bottle with UT report in lieu of internal exam. LEGACY COMPONENT DESC: Receiver/Bottle
Due 23 June 2002
Resolved 6 June 2002
Deck/Cargo
Issued 20 May 2002
Resolved
Provide report of disposition of all discrepencies noted on annual exam report of crane 3 inspection.
Due 23 June 2002
Resolved 6 June 2002
Construction/Loadline › Hull
Issued 20 May 2002
Resolved
Complete underwater portion of cycle "c" exam and replace valves in SW seachest and open SW sea chest for internal exam with CG marine inspector present. LEGACY COMPONENT DESC: Bottom Plating
Due 31 December 2002
Resolved 23 May 2003
Deck/Cargo
Issued 22 March 2002
Resolved
PROVIDE LABORATORY ANALYSIS OF REMAINING SECTIONS OF BOOM HOIST WIRE ROPE TO INCLUDE % OF STRANDING, BREAKING STRENGTH, EXTENT OF CORROSION, WASTAGE, ELONGATION, AMOUNT OF RESIDUAL LUBRICATION PRESENT ECT...AND ANY MENTION OF ADVERSE REACTION TO WIRE ROPES FROM FLARE BOOM HEAT. LEGACY COMPONENT DESC: CRANE
Condition: Improper/Lack of Maintenance
Due 22 April 2002
Resolved 1 June 2002
Deck/Cargo
Issued 22 March 2002
Resolved
PROVIDE STATUS BRIEFING TO [name withheld] AS TO THE PROGRESS OF THE INVESTIGATION TO DATE TO INCLUDE PHOTOGRAPHS, WITNESS STATEMENTS, COPIES OF INSPECTION RECORDS, AUDIT RECORDS AND MOST RECENT PROOF LOAD TEST. COORDINATE THIS PRESENTATION WITH [name withheld] @ [phone withheld]. LEGACY COMPONENT DESC: CRANE
Condition: Improper/Lack of Maintenance
Due 22 April 2002
Resolved 1 June 2002
Deck/Cargo
Issued 22 March 2002
Resolved
PROVIDE FINAL INVESTIGATION REPORT TO [name withheld] COMPLETE. LEGACY COMPONENT DESC: CRANE
Condition: Improper/Lack of Maintenance
Due 22 April 2002
Resolved 1 June 2002
Deck/Cargo
Issued 22 March 2002
Resolved
#2 CRANE SHALL NOT BE PLACED BACK INTO SERVICE UNTIL ALL REPAIRS ARE COMPLETE, WITNESSED AND A POST REPAIR PROOF LOAD TEST IS WITNESSED BY THE U.S. COAST GUARD. LEGACY COMPONENT DESC: CRANE
Condition: Improper/Lack of Maintenance
Due 22 April 2002
Resolved 23 May 2003
Documentation
Issued 19 May 2000
Resolved
Provide onboard at all times not less than five (5) lifeboatmen as requiredby 46 CFR 109.323(c)(1). If licensed individuals are serving in capacity of lifeboatmen, they must be endorsed as "Lifeboatman" on their license or hold a valid AB card or other MMD endorsed as "Lifeboatman".
Condition: Unknown
Due 19 May 2000
Resolved 19 May 2000
Documentation
Issued 23 April 1997
Resolved
Obtain Stability Letter from MSC before any drilling or production operations take place.
Condition: Unknown
Due 23 April 1997
Resolved 23 April 1997
Fire Fighting
Issued 23 April 1997
Resolved
Complete testing of No.1 and No.2 main fire pumps' operation and automationbefore any drilling or production operations takes place.
Condition: Unknown
Due 23 April 1997
Resolved 23 April 1997