Records from 2016 to 2026. Most recent: inspection, 17 July 2026.
Documentation record
Registered dimensions (L × B × D)46.0 ft × 16.5 ft × 8.0 ft
Registered tonnagegross 40 / net 32
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderHUNT SHIPYARD · HARVEY, LA, UNITED STATES · built 1966
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeShip
Hull configurationMonohull
Hailing portPEEKSKILL, NY
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 28 May 2026 · expires 31 May 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it40 - Simplified, Gross Ton
32 - Simplified, Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Inspection history · 17
17 July 2026
Annual Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 8440379
2 July 2025
Annual Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 8172485
12 March 2025
Internal Structural Exam · Drydock Exam
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 8092303
1 May 2024
COI Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7898025
18 November 2023
Administrative Inspection
Administrative · Sector New York · USCG Northeast District (CGD-NE) · Activity 7826766
14 December 2022
Drydock Exam · Deficiency Check
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7606512
5 October 2022
Annual Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7571056
6 July 2021
Administrative Inspection · COI Inspection · Deficiency Check
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7240927
8 March 2021
Administrative Inspection · Hull Examination · Internal Structural Exam · Examination of Repairs
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7151756
19 October 2020
DAPI Audit · Annual Inspection · Deficiency Check
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7080756
7 October 2020
Administrative Inspection
Administrative · Sector New York · USCG Northeast District (CGD-NE) · Activity 7073619
24 September 2019
Deficiency Check · Annual Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6819966
6 March 2019
Examination of Repairs · Drydock Exam · Hull Examination
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6637511
13 August 2018
Annual Inspection · Deficiency Check
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6510246
12 July 2017
Annual Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6207118
7 July 2016
COI Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 5932633
12 April 2016
Internal Structural Exam · Drydock Exam
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 5851709
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 18 November 2023
Resolved
To maintian a valid Certifiate of Inspection you must complete your annual inspection within the periods specified in 176.500(b)(1). The vessels' COI has lapsed in validity.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 2 May 2024
Resolution: Vessel has conducted a COI renewal exam and is issued a new 5 year COI.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 6 July 2021
Resolved
Stations in the maritime service must be licensed by the FCC either individually or by fleet.
Station authorization license is expired. Renewal required.
47CFR80.13(a)
50C
Action required: 50 - Rectify deficiencies w/in 30 days
Due 5 August 2021
Resolved 15 July 2021
Resolution: Received copy of new station Authorization.
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 24 September 2019
Resolved
Coast Pilot and Light List need to be updated.
46 CFR 184.420
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 4 October 2019
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 24 September 2019
Resolved
Retro tape on life rings was DOT and needs to be replaced with SOLAS tape.
46 CFR 185.604
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 4 October 2019
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 24 September 2019
Resolved
Replace all 3 orange smoke signals or get 2 additional red hand flares. Vessel restricted to day time ops until rectified.
46 CFR 185.614
Action required: 705 - Other - as specified
Due 24 September 2019
Resolved 25 September 2019
Resolution: vessel operator sent pictures of purchased flares.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 24 September 2019
Resolved
Monthly inspections of fire extinguishers need to be conducted and documented.
46 CFR 176.810(b)(1)(ii)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 4 October 2019
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 24 September 2019
Resolved
CO2 bottles need to be stored off of the deck.
46 CFR 181.20-30(e)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 4 October 2019
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 24 September 2019
Resolved
Fixed fire extinguishing engine shut down pressure switch did not work. Fix the switch to make it operate as intended.
46 CFR 181.05-5
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 8 June 2020
Resolution: Attending Marine Inspectors conducted a satisfactory def check.
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 24 September 2019
Resolved
Install CO2 diagram at fire fighting operating station.
46 CFR 181.20-15(d)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 1 November 2019
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 24 September 2019
Resolved
Emergency fuel shut off valves to each tank needs to be installed from outside the space.
46 CFR 182.20-40(b)(3)
Action required: 705 - Other - as specified
Due 31 October 2019
Resolved 8 June 2020
Resolution: Attending Marine Inspectors conducted a satisfactory def check.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 24 September 2019
Resolved
Remove combustibles from E/R.
46 CFR 182.01-5
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 4 October 2019
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 13 August 2018
Resolved
A vessel that is exposed to salt water more than three months in any 12 month period since the last examination must undergo a drydock examination and an internal structural at least once every two years. Make vessel available for dry dock and internal structural examinations.46 CFR 176.600(C)(1)
Action required: 705 - Other - as specified
Due 1 May 2019
Resolved 19 October 2020
Resolution: Vessel received drydock in MAR2019, placed on two year drydock interval.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 13 August 2018
Resolved
The alcohol testing of each individual must be conducted within 2 hours of when the SMI occurred, unless precluded by safety concerns directly related to the incident. Vessel's alcohol test strips are expired, provide DOT approved alcohol testing method.46 CFR 4.06-3(a)(i)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 August 2018
Resolved 20 August 2018
Resolution: Operator submitted pictures showing new test kits.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 13 August 2018
Resolved
Electrical equipment on a vessel must be installed and maintained to Protect passengers, crew, other persons, and the vessel from electrical hazards, including fire, caused by or originating in electrical equipment, and electrical shock. Power cable from battery to battery charger box is fraying presenting hazard to vessel and personnel.46 CFR 183.200(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 August 2018
Resolved 16 August 2018
Resolution: Operator sent pictures showing the reapirs made to cable and protective cover.
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 13 August 2018
Resolved
Shutoff vavles must be fitted in fuel supply lines and must be operable from outside the space. Cable for closing valve from outside the space failed to close the valve. 46 CFR 182.20-40(b)(3)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 August 2018
Resolved 15 August 2018
Resolution: Proved function of remote shutoff via email submitted video of the cable and valve in operation.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 13 August 2018
Resolved
Each overnight accomodation space must be fitted with an independent modulular smoke detection and alarm unit. The battery in the smoke detection/alarm unit was dead, rendering the unit nonfunctional. 46 CFR 181.405(c)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 August 2018
Resolved 15 August 2018
Resolution: Resolved via email video of fresh battery in unit and function check.
Documentation › Certificates/Documents › FCC Safety Radiotelephony Certificate
Issued 12 July 2017
Resolved
Vessel is restricted to 1000 feet from shore until radiotelephony certificate is renewed.
Condition: Invalid
Action required: 705 - Other - as specified
Due 12 July 2020
Resolved 13 August 2018
Resolution: Renewed certificate.
Engineering › Pressure Vessel › Relief Valve
Issued 7 July 2016
Resolved
Pressure relief valve was missing from the pressure vessel.
Action required: 705 - Other - as specified
Resolved 7 July 2016
Resolution: Operator provided a relief valve set to 150 PSI, corrected deficiency on the spot.