MAURY USCG vessel records Sign in
← All vessels

DIAMOND QUEEN

DIAMOND QUEEN is a 1956 passenger vessel (inspected). The Coast Guard has recorded 62 inspections since 1984, most recently in April 2026, along with 91 deficiencies and 1 casualty investigation in 2009.

Records from 1984 to 2026. Most recent: inspection, 28 April 2026.

Built
1956
Last inspected
28 April 2026
Documentation
Valid · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

WCV6835
Flag
UNITED STATES
367727220
Maury page id
psix-43206

Inspections, by type

…with no type recorded3
Years with a record 41 calendar years (1984–2026)
The 62 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Registered dimensions (L × B × D)87.8 ft × 25.0 ft × 7.2 ft
Registered tonnagegross 94 / net 63
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderMARINETTE MARINE CORP · MARINETTE, WI, UNITED STATES · built 1956
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeNot recorded
Hull configurationNot recorded
Hailing portGROSSE ILE, MI
Trade endorsementsCoastwise, unrestricted, Recreational, Registry
DocumentationValid · issued 23 July 2026 · expires 31 July 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it94 - Regulatory (Subpart C or D), Gross Ton
63 - Regulatory (Subpart C or D), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

WDI7290MMSI 367727220 · active · compulsorily equipped · granted 3 April 2026, expires 14 April 2036
WCV6835MMSI 367044310 · expired · compulsorily equipped · granted 8 October 2005, cancelled 13 February 2016
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown. A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.

Inspection history · 62

28 April 2026 Annual Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 8357191
15 August 2025 In-Service Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 8210473
27 June 2025 Deficiency Check
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 8168798
2 June 2025 Annual Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 8149603
16 August 2024 In-Service Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 7982624
13 May 2024 COI Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 7911143
28 September 2023 In-Service Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 7796486
1 May 2023 MTSA/ISPS Verification · Annual Inspection · Deficiency Check · In-Service Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 7678989
28 April 2022 Annual Inspection · Deficiency Check
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 7439352
14 October 2021 Internal Structural Exam · Drydock Exam
Physical examination · Marine Safety Unit Cleveland · USCG Great Lakes District (CGD-GL) · Activity 7332594
28 April 2021 Deficiency Check · Annual Inspection · Administrative Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 7185035
13 November 2020 Drydock Extension
Administrative · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 7097797
29 June 2020 Deficiency Check · Annual Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 6990172
25 April 2019 COI Inspection · DAPI Audit
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 6669244
30 April 2018 Annual Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 6402233
28 April 2017 Annual Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 6134755
21 July 2016 Deficiency Check
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 5948138
13 May 2016 Annual Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 5876273
2 November 2015 Internal Structural Exam · Drydock Exam
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 5756113
13 July 2015 Deficiency Check
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 5183055
18 June 2014 Deficiency Check
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 4892379
9 August 2011 Administrative Inspection
Administrative · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 4110206
5 November 2010 DAPI Audit
Administrative · Marine Safety Unit Toledo · USCG Great Lakes District (CGD-GL) · Activity 3887885
13 October 2010 Drydock Exam
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 3870429
24 January 2009 Type not recorded
No type recorded · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 3400449
8 May 2008 Deficiency Check
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 3201991
16 April 2008 MTSA Verification · Re-Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 3185263
23 April 2007 MTSA Verification · COI Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 2916791
25 April 2006 MTSA Verification · Re-Inspection
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 2710772
14 October 2005 Hull Examination
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 2514468
21 April 2005 Re-Inspection · MTSA Verification
Physical examination · Sector Detroit · USCG Great Lakes District (CGD-GL) · Activity 2378054
27 April 2004 Re-Inspection
Physical examination · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 2055404
29 December 2003 Security Plan Review - ASP
Administrative · Marine Safety Center (MSC) · Activity 1977743
24 April 2003 Re-Inspection
Physical examination · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 1780562
24 April 2002 COI Inspection
Physical examination · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 1608554
23 August 2001 Deficiency Check
Physical examination · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 1069267
12 April 2001 Re-Inspection
Physical examination · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 1064820
5 April 2000 Re-Inspection
Physical examination · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 1361750
25 January 2000 Administrative
Administrative · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 814869
29 April 1999 COI Inspection
Physical examination · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 1411854
26 March 1998 Re-Inspection
Physical examination · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 1381222
23 April 1997 Re-Inspection
Physical examination · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 1445195
5 June 1996 Administrative
Administrative · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 1181457
16 May 1996 COI Inspection
Physical examination · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 1433042
30 November 1995 Plan Review "T" Boat
Administrative · MSO DETROIT · USCG Great Lakes District (CGD-GL) · Activity 873846
21 September 1995 Excursion Permit
Administrative · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 872840
10 August 1995 Hull Examination · COI Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1179161
27 June 1994 Deficiency Check
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1023836
1 June 1994 Administrative
Administrative · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1171682
18 May 1994 COI Inspection
Physical examination · MSO SAULT STE MARIE · USCG Great Lakes District (CGD-GL) · Activity 1171672
1 June 1993 COI Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1149472
2 June 1992 COI Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1264542
4 June 1991 COI Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1219630
5 June 1990 COI Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 925408
21 May 1990 Hull Examination
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1232748
17 May 1989 COI Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1196651
16 May 1988 COI Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 887361
6 April 1987 COI Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1021289
23 May 1986 Deficiency Check
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 998111
14 May 1986 COI Inspection
Physical examination · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 993796
22 May 1985 Type not recorded
No type recorded · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1291737
8 November 1984 Type not recorded
No type recorded · MIO ST. IGNACE · USCG Great Lakes District (CGD-GL) · Activity 1282879

Deficiency record · 91

13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 28 April 2026 Resolved
Except as otherwise provided in paragraphs (b), (c), (d), and (e) of this section, all engines must be water cooled and meet the requirements of this paragraph. (1) The engine head, block, and exhaust manifold must be water-jacketed and cooled by water from a pump that operates whenever the engine is operating. (3) A closed fresh water system may be used to cool the engine. Cooling line had a steady leak on Port M/E. Arrest leak as necessary.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 June 2026
Resolved 4 May 2026
Resolution: Seal replaced.
04 - Emergency Systems › N/A - No Subsystem › Emergency fire pump and its pipes
Issued 2 June 2025 Resolved
A power-driven fire pump shall be installed on each mechanically propelled "S" vessel which is a ferry vessel or which is permitted to carry more than 49 passengers, and on each mechanically propelled "L" vessel. Fire pump failed during testing. Bilge pump satisfactory tested in lieu of fire pump. Repair fire pump.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 July 2025
Resolved 27 June 2025
Resolution: Fire pump repaired
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 13 May 2024 Resolved
Port Main Engine has an excessive oil leat at valve cover gasket, aft end of engine on both the out board and in board side. Repair/replace gasket to arrest leak and remove oil from the bilge.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 13 May 2024
Resolved 15 May 2024
Resolution: Verified gaskets replaced. Tested engine at operating RPM with no leaks. Verfied oil removed from bilge.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 13 May 2024 Resolved
No marine employer shall engage or employ any person to serve as a crew member unless the individual passes a chemical test for dangerous drugs for that employer. List of P.R.-employment tested crew not available at inspection. Provide list of all crew who were drug tested and enrolled in the company's DAPI program.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 May 2024
Resolved 17 May 2024
Resolution: DAPI provided to CG
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 13 May 2024 Resolved
Security drill and exercises. Drills shall be preformed every three months. Exercise shall be preformed every 18 months. Drills and exercise has not been preformed. Conduct drill and exercise and provide documentation.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 May 2024
Resolved 17 May 2024
Resolution: Drills and exercise conducted
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 13 May 2024 Resolved
Fire Service report not available. Provide proof of record of portable fire extinguishers service.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 13 May 2024
Resolved 13 May 2024
Resolution: Verified tags on portable units. Reiterated expectation that inspection reports are to be made available at next inspection.
04 - Emergency Systems › N/A - No Subsystem › Abandon ship drills
Issued 13 May 2024 Resolved
Fire, abandon ship, and man overboard drills shall be preformed at least every three months. Drills not conducted prior to season and with new crew. Conduct and log drills and provide to CG Marine Inspector prior to carrying passengers.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 13 May 2024
Resolved 15 May 2024
Resolution: Satisfactory fire drill conducted.
09 - Working and Living Conditions › 091 - Living Conditions › Other (food)
Issued 13 May 2024 Resolved
A vessel must carry either a first-aid kit that meets the requirements in 46 CFR 199.175(b)(10) or a kit with equivalent contents and instructions. For equivalent kits, the contents must be stowed in a suitable, watertight container that is marked “First-Aid Kit”. A first-aid kit must be easily visible and readily available to the crew. The vessels first aid kit contained expired items, renew/replace expired items.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 13 May 2024
Resolved 13 May 2024
Resolution: Crew replaced expired kits.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 13 May 2024 Resolved
A vessel must be provided with a satisfactory arrangement for draining any watertight compartment, other than small buoyancy compartments, under all practicable conditions. Marine Inspector, when testing bilge pump and piping, observed prolonged difficulty drawing suction through bilge piping system.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 13 May 2024
Resolved 13 May 2024
Resolution: Reiterated importance of maintaining bilge suction system in ready to operate conditions.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 1 May 2023 Resolved
Replace closure device on fuse panel in engine room and forward space
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 2 May 2023
Resolution: New closure devices have been ordered and will be installed when recieved.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 1 May 2023 Resolved
Replace holed fire hose on upper deck
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 2 May 2023
Resolution: New fire hose has been installed
04 - Emergency Systems › N/A - No Subsystem › Means of communication between safety centre and other control stations
Issued 1 May 2023 Resolved
Repair public address sytem
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 2 May 2023
Resolution: PA has been repaired
01 - Certificates & Documentation › 011 - Ships Certificates › USCG Certificate of Documentation (COD)
Issued 28 April 2022 Resolved
Person in command must produce the original Certificate of Documentation. Original not on-board.
Action required: 10 - Deficiency Rectified
Resolved 1 May 2023
Resolution: COD on board
10 - Safety of Navigation › N/A - No Subsystem › Magnetic compass
Issued 28 April 2022 Resolved
Magnetic compass is missing deviation card.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 5 May 2022
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 28 April 2022 Resolved
The method of opening a means of escape must be obvious, rapid, and of adequate strength. Means of escape from engine room was not obivous. Advised to label handle in direction to open.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 5 May 2022
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 28 April 2022 Resolved
All observed unsafe practices, fire hazards and other hazardous situations must be corrected and guards and protective devices must be in satisfactory condition. Flammable items not in flammable locker.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 5 May 2022
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 28 April 2022 Resolved
Incorrect donning placards posted for lifejackets. Vessel to post correct placards at each location lifejackets are stowed.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 June 2022
Resolution: Verified with vessel rep that placards were updated and onlocation.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 28 April 2022 Resolved
Port main engine not running- emeregency stop to be verified once repairs are completed.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 5 May 2022
02 - Structural Conditions › N/A - No Subsystem › Permanent means of access
Issued 28 April 2022 Resolved
Twist on type connectors may not be used for making joints in cables, facilitating a conductor splice, or extending the length of a circuit. Twist on type connectors found being used in engine room.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 5 May 2022
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 28 April 2022 Resolved
Each vessel must be equipped with a portable battery light at the access to the propulsion machinery. Batteries were found to be dead and need replacing
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 5 May 2022
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 28 April 2022 Resolved
Gears, couplings, flywheels and all machinery capable of injuring personnel shall be provided with adequate covers or guards. Install guard forward of main engine.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 15 June 2022
Resolution: Verified with vessel rep that cover has been installed.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 28 April 2022 Resolved
Piping, valves, and fittings in a fire main system must comply with part 119. Valve at the upper section found to be leaking. Replace.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 5 May 2022
01 - Certificates & Documentation › 011 - Ships Certificates › Cargo Ship Safety Radio (including exemption)
Issued 28 April 2021 Resolved
Obtain valid marine radio operator permit and update call sign posted.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2021
Resolved 12 May 2021
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 28 April 2021 Resolved
Conduct fire and man overboard drill in the presence of marine inspector. Drills not conducted in 2020 as required.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 May 2021
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 28 April 2021 Resolved
Test PA system and rudder angle indicator and gauges at operating station.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 May 2021
05 - Radio Communications › N/A - No Subsystem › Main installation
Issued 28 April 2021 Resolved
Update VHF radios with DSC capability - see CG-CVC policy letter 15-06(CH2).
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2021
Resolved 16 June 2021
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 28 April 2021 Resolved
Flexible fuel lines must meet J1942.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2021
Resolved 16 June 2021
01 - Certificates & Documentation › 013 - Documents › Signs, indications
Issued 28 April 2021 Resolved
Decks should be marked with maximum passenger capacity IAW stability letter in 1" numbers at entrance to deck.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2021
Resolved 17 May 2021
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 28 April 2021 Resolved
Renew first aid kit to meet required items IAW 46 CFR 160.041-4. Contents found expired.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2021
Resolved 12 May 2021
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 28 April 2021 Resolved
Mark both sides of emergency escape in at least 2" letters "EMERGENCY EXIT_- KEEP CLEAR"
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2021
Resolved 17 May 2021
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 28 April 2021 Resolved
Replace battery in lifebuoy. Found expired and incorrect model.
Action required: 701 - Prior to carriage of passengers/cargo
Due 6 June 2021
Resolved 12 May 2021
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 28 April 2021 Resolved
Provide approved bracket for fire extinguisher in engine room and "galley" below deck.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2021
Resolved 16 June 2021
09 - Working and Living Conditions › 092 - Working Conditions › Lighting (Working spaces)
Issued 28 April 2021 Resolved
Provide covers for lights in engine room.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2021
Resolved 16 June 2021
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 28 April 2021 Resolved
Provide metal supports every 24" for electrical in such manner to prevent chaffing or damage. Plastic tie wraps must be limited to bundling or retention of multiple cable installations and NOT used as means of support.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 June 2021
Resolved 19 August 2021
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 28 April 2021 Resolved
An adult life jacket must be provided for each person carried on board, in addition, a number of child size lifejackets equal to at least 10% of the number of persons permitted, or such greater number as necessary to provide a life jacket for each person being carried. Several life jackets destroyed and removed from the vessel. Owner advised that 100% of life jackets would be inspected until a full renewal has taken place given the age of the life jackets.
Action required: 10 - Deficiency Rectified
Resolved 16 June 2021
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 29 June 2020 Resolved
All piping, valves and fittings of the fire main and hydrant shall be in accordance with good marine practice. Bronze fire main fitting on starboard main deck was cracked. Replace.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 7 August 2020
Resolution: observed replaced fitting
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 29 June 2020 Resolved
Each ring life buoy with a floating water light must have a lanyard of at least 3' in length but not more than 6' securing the water light around the body of the ring life buoy. Water light line is deteriorated. Replace.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 7 August 2020
Resolution: observed newly replaced line
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 29 June 2020 Resolved
A vessel on a rivers route must carry 3 hand red flare and 3 hand orange smoke distress signals (for substitutions see paragraph c). Distress signals were found to be expired.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 7 August 2020
Resolution: observed new distress signals
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 29 June 2020 Resolved
An adult life jacket must be provided for each person carried on board, in addition, a number of child size lifejackets equal to at least 10% of the number of persons permitted, or such greater number as necessary to provide a life jacket for each person being carried. 3 lifejackets were found to be in poor condition. Replace all lifejackets as necessary.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 7 August 2020
Resolution: observed satisfactory life jackets
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 29 June 2020 Resolved
Portable fire extinguishers must be located so that they are clearly visible and readily accessible. Mounting brackets for the extinguisher on the second deck starboard side and operating station were broken or improper for the size of fire extinguisher. Replace with proper bracket meeting the manufacturer's specification.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 July 2020
Resolved 7 August 2020
Resolution: observed new mounting bracket
10 - Safety of Navigation › N/A - No Subsystem › Charts
Issued 29 June 2020 Resolved
As appropriate for the voyage, a vessel must carry adequate and up to date charts. Charts and Navigation rules were not up to date.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 July 2020
Resolved 7 August 2020
Resolution: observed updated charts and pubs
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 29 June 2020 Resolved
On a vessel of at least 26' in length, a visual and audible alarm must be provided at each operating station. Bilge alarm labels were found to be mislabeled. Provide accurate labels for each space.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 July 2020
Resolved 7 August 2020
Resolution: oberved properly labeled bilge alarms
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 29 June 2020 Resolved
Contact Sector Detroit to conduct drills and underway portion of exam to include steering test.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 July 2020
Resolved 7 August 2020
Resolution: Completed satisfactory MOB drills, see narrative for feedback. Discussed fire scenarios with crew.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Covers (hatchway-, portable-, tarpaulins, etc.)
Issued 25 April 2019 Resolved
Renew retro-reflective tape on 26 child life jackets.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 9 May 2019
Resolved 29 June 2020
10 - Safety of Navigation › N/A - No Subsystem › Charts
Issued 25 April 2019 Resolved
Provide new charts, light list, and coast pilot.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 May 2019
Resolved 29 June 2020
01 - Certificates & Documentation › 012 - Crew Certificates › Evidence of Basic Training
Issued 25 April 2019 Resolved
Vessel is not logging security drills or training. Log all future security training and drills.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 May 2019
Resolved 29 June 2020
01 - Certificates & Documentation › 012 - Crew Certificates › Other (STCW)
Issued 25 April 2019 Resolved
Update senior deck hand list.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 May 2019
Resolved 29 June 2020
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 25 April 2019 Resolved
Renew retro-reflective tape on 25 adult, and 21 child. 3 adult need the vessel name and 8 child also need the vessel name.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 10 May 2019
Resolved 29 June 2020
Engineering › Fuel Oil Service System › Valve
Issued 28 April 2017 Resolved
Properly mark fuel shutoff with direction of actuation.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 15 May 2017
Resolved 11 June 2018
Communications › Alarms/Indicators › Bilge Alarm
Issued 28 April 2017 Resolved
Make permanent repairs to bilge high water level indication panel on the bridge.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 May 2017
Resolved 11 June 2018
Fire Fighting › Portable CO2 Fire Extinguisher › Mounting Bracket
Issued 28 April 2017 Resolved
Install approved bracket for extinguisher within the reefer flat area.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 15 May 2017
Resolved 11 June 2018
Construction/Loadline › Structures › Manhole
Issued 13 May 2016 Resolved
Emergency escape hatch requires maintenance.
Action required: 705 - Other - as specified
Due 31 May 2016
Resolved 20 July 2016
Resolution: Access lubricated and operational.
Construction/Loadline › Structures › Manhole
Issued 13 May 2016 Resolved
MArk Emergency escape hatch "Emergency Exit Keep Clear"
Action required: 705 - Other - as specified
Due 31 May 2016
Resolved 20 July 2016
Resolution: Emergency escape marked properly.
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 13 May 2016 Resolved
Ring Buoy light is cracked in multiple spots and requires renewal.
Action required: 705 - Other - as specified
Due 31 May 2016
Resolved 20 July 2016
Resolution: Ring buoy floatable light renewed.
Lifesaving › Lifebuoys › Buoyant Lifeline
Issued 13 May 2016 Resolved
Renew aft ring buoy lifeline (60 ft)
Action required: 705 - Other - as specified
Due 31 May 2016
Resolved 20 July 2016
Resolution: Line renewed.
Lifesaving › Lifejacket/PFD (Type I) › Condition
Issued 13 May 2016 Resolved
Removed 07 adult and 02 child lifejackets from service. Ensure each passenger is provided a type I PFD and each child is provided a type I PFD per COI.
Action required: 705 - Other - as specified
Due 31 May 2016
Resolved 20 July 2016
Resolution: 9 Jackets removed and replaced with new.
Operations/Management › Drug and Alcohol Testing › EAP Display Requirements
Issued 5 November 2010 Resolved
Hotline number not posted.
Due 12 November 2010
Resolved 5 November 2010
Resolution: Corrected on teh spot: Hotline number posted.
Operations/Management › Drug and Alcohol Testing › Recordkeeping
Issued 5 November 2010 Resolved
Substance Abuse Professional name and contact information not available at time of inspection.
Due 12 November 2010
Resolved 8 November 2010
Resolution: SAP name and contact info provided.
Operations/Management › Drug and Alcohol Testing › Testing, Random
Issued 5 November 2010 Resolved
Random testing not spread evenly throughout the year. No evidence of first quarter testing conducted. Marine Employer must provide an acknowledgement letter from Comprehensive Testing Solutions for addition of first quarter testing.
Due 12 November 2010
Resolved 8 November 2010
Resolution: Documentation provided for random drug testing spread evenly throughout the year.
Navigation › Piloting/Steering › Magnetic Compass
Issued 16 April 2008 Resolved
Replace light bulb in magnetic compass.
Action required: 705 - Other - as specified
Resolved 6 May 2008
Electrical › Electric Supply System (service) › Cable
Issued 16 April 2008 Resolved
Cap off or remove open ended wire in main space next to bilge alarm pannel.
Action required: 705 - Other - as specified
Resolved 6 May 2008
Fire Fighting › Means of Escape › Escape Route Signs
Issued 16 April 2008 Resolved
provide a fire control plan and post where in a place the passengers can view it.
Action required: 705 - Other - as specified
Resolved 6 May 2008
Lifesaving › Lifefloat › Retroreflective Material
Issued 16 April 2008 Resolved
Provide new SOLAS approved tape on all life floats.
Action required: 705 - Other - as specified
Resolved 6 May 2008
Lifesaving › Lifefloat › Floating Electric Waterlight
Issued 16 April 2008 Resolved
Repair bracket on after-most water light.
Action required: 705 - Other - as specified
Resolved 6 May 2008
Lifesaving › Lifebuoys › Buoyant Lifeline
Issued 16 April 2008 Resolved
Provide 60' life line.
Action required: 705 - Other - as specified
Resolved 6 May 2008
Documentation › Manifests/Lists › Muster List/Emergency Instructions
Issued 27 April 2004 Resolved
Post crew station bill visibly onboard vessel.
Due 30 May 2004
Resolved 1 May 2004
Resolution: Vessel owner provided crew station bill for vessel.
Documentation › Markings/Placards › Capacity Marking
Issued 27 April 2004 Resolved
Provide placards on upper decks indicating maximum allowable persons per stability letter.
Condition: Improper/Lack of Maintenance
Due 30 May 2004
Resolved 1 May 2004
Resolution: Placards were placed on upper decks indicating maximum allowable persons.
Lifesaving › Buoyant Apparatus › General
Issued 27 April 2004 Resolved
Mark buoyant apparatus with vessel name and capacity.
Due 30 May 2004
Resolved 1 May 2004
Resolution: All buoyant apparatus marked with vessel name and capacity.
Lifesaving › Lifebuoys › Not on Board
Issued 27 April 2004 Resolved
Replace worn lifebuoy.
Condition: Unknown
Due 30 May 2004
Resolved 29 April 2004
Resolution: Lifebuoy replaced on the spot.
Fire Fighting › Fire Main › Condition
Issued 27 April 2004 Resolved
Replace elbow joint at fire main outlet to stop leaking.
Condition: Improper/Lack of Maintenance
Due 31 May 2004
Resolved 1 May 2004
Resolution: Elbow joint replaced with new joint.
Electrical › Electrical Distribution System (service) › Switch
Issued 27 April 2004 Resolved
Hardwire raw water pumps into a switch assembly.
Condition: Improper Installation
Due 31 May 2004
Resolved 14 May 2004
Resolution: Raw water pumps were hardwired into one switch.
Documentation › Certificates/Documents › FCC SSL
Issued 27 April 2004 Resolved
Post FCC Station license and renewal visibly onboard vessel.
Due 31 May 2004
Resolved 1 May 2004
Resolution: FCC Station licence and renewal card posted in pilot house.
Lifesaving › Lifejacket/PFD (General) › Quantity
Issued 27 April 2004 Resolved
Provide 300 lifejackets onboard vessel.
Due 29 April 2004
Resolved 29 April 2004
Resolution: Missing lifejackets were replaced on the spot.
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 27 April 2004 Resolved
Provide corrosion resistant clip from lifebuoy to water light.
Due 15 May 2004
Resolved 1 May 2004
Resolution: Detachable corrosion resistant clip provided on lifebuoy.
Operations/Management › Drills/Instruction
Issued 24 April 2003 Resolved
Complete drills
Due 10 June 2003
Resolved 11 June 2003
Lifesaving › Buoyant Apparatus
Issued 24 April 2003 Resolved
Provide retro-reflective tape for both sides of the Bouyant apparatus. LEGACY COMPONENT DESC: retro-reflective tape
Due 10 June 2003
Resolved 11 June 2003
Operations/Management › Drills/Instruction
Issued 24 April 2003 Resolved
Post emergency procedure instructions.
Due 10 June 2003
Resolved 11 June 2003
Documentation › Certificates/Documents
Issued 24 April 2002 Resolved
Post all certificates, decals, and letters as required.
Due 22 May 2002
Resolved 11 July 2002
Communications › Alarms/Indicators
Issued 24 April 2002 Resolved
Provide audible bilge alarm for bridge. LEGACY COMPONENT DESC: Bilge Alarm
Due 22 May 2002
Resolved 11 July 2002
Lifesaving › Lifejacket/PFD (Type I) › Condition
Issued 24 April 2002 Resolved
Renew 16 adult lifejackets.
Due 8 May 2002
Resolved 8 May 2002
Lifesaving › Lifejacket/PFD (Type I) › Retroreflective Material
Issued 24 April 2002 Resolved
Renew retro reflective tape on 3 adult lifejackets.
Due 8 May 2002
Resolved 8 May 2002
Personnel › Manning/Qualifications
Issued 24 April 2002 Resolved
Assure 50% of crew can prove they have completed required 1st aid/cpr training. LEGACY COMPONENT DESC: CPR Certified Personnel
Due 22 May 2002
Resolved 11 July 2002
Electrical › Lighting (service)
Issued 24 April 2002 Resolved
Rewire and provide lens cover for lighting fixture in aft, port side of engineroom. LEGACY COMPONENT DESC: Lighting Fixture
Condition: Improper Installation
Due 22 May 2002
Resolved 11 July 2002
Documentation › Logs/Records
Issued 24 April 2002 Resolved
Provide proper maintenance of required training and maintenance log. LEGACY COMPONENT DESC: Logbook/Record (unofficial)
Condition: Improper/Lack of Maintenance
Due 22 May 2002
Resolved 11 July 2002
Operations/Management › Passenger Operations
Issued 24 April 2002 Resolved
Provide means to leave passenger count ashore.
Due 15 May 2002
Resolved 11 July 2002
Accommodation/Occupational Safety
Issued 18 May 1994 Resolved
Repair water supply piping to wash basins.
Condition: Unknown
Due 18 May 1994
Resolved 18 May 1994
Accommodation/Occupational Safety
Issued 18 May 1994 Resolved
Provide ventilation louvers to doors on bridge console.
Condition: Unknown
Due 18 May 1994
Resolved 18 May 1994
Accommodation/Occupational Safety
Issued 18 May 1994 Resolved
Repair top of sewage tank.
Condition: Unknown
Due 18 May 1994
Resolved 18 May 1994
Accommodation/Occupational Safety
Issued 18 May 1994 Resolved
Mark upper deck entrances with maximum persons allowed by stability letter (223).
Condition: Unknown
Due 18 May 1994
Resolved 18 May 1994
Engineering
Issued 1 June 1993 Resolved
Remove oil from bilge in the forward fuel tank compartment.
Condition: Unknown
Due 4 June 1993
Resolved 4 June 1993
Fire Fighting
Issued 1 June 1993 Resolved
Repair and prove operation of Main Engine direct drive fire pump.
Condition: Unknown
Due 4 June 1993
Resolved 4 June 1993

Casualty record · 1

24 January 2009Routine · role: Involved in a Marine Casualty · serious marine incident, as classified · activity 3400449
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it, and the bridge, lock or dam the investigation names where it names one. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.