BOW FAGUS is a 1995 tank ship. The Coast Guard has recorded 14 inspections since 2016, most recently in June 2024, along with 4 deficiencies and 1 operational control.
Records from 2016 to 2024. Most recent: inspection, 6 June 2024.
Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Tank Ship class in Maury's sources begin in 2016.
Every line above is a count of records the US Coast Guard wrote, or a date it recorded.
A blank resolution means none was recorded in this data; it does not establish that a
deficiency is outstanding. Years with a record are calendar years in which a record
exists, not years in service. What Maury does
not do.
Tonnage as PSIX records it48499 - Displacement, Metric Ton 37375 - Dead Weight, Metric Ton 23221 - Convention (Subpart B), Gross Ton 12176 - Convention (Subpart B), Net Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
Every record for this hull, in one document — $299
Every recorded inspection, 2016 to
2026 for this class, in one chronology · every deficiency, with system, dates
and resolution · operational controls imposed and removed · every name this
hull has been recorded under · the vessels it was inspected alongside, and when
· how its record compares with hulls of similar age and size, as a fact about the
population and never a judgement about this vessel.
This report is in development and is not for sale yet. There is
no date, and nothing is charged. Leave an email and we will tell you when it exists, once.
Used only to tell you when the report exists.
Not shared, not sold, and not added to a mailing list.
1799: Stowage of cargo samples shall be cell-divided in order to avoid shifting of the bottles at sea; samples which react with each other dangerously shall not be stowed close to each other.
During examination of cargo sample locker, PSCOs observed multiple unlabeled, unmarked samples and could not verify proper stowage segregation. Over a dozen glass sample bottles were stored directly on top of other glass sample bottles and next to other bottles, without cell division.
(17c) (IBC 16.5)
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 6 March 2018
Resolved 9 March 2018
Resolution: On-board deficiency check performed by PSCO. All samples properly labeled and stored.
Fire Fighting › Fixed Low-Expansion Foam Fire Extinguishing System › Foam Source
Issued 6 March 2018Resolved
Every ship shall be provided with a fixed deck foam system IAW the requirements of 11.3.2 to 11.3.12.
Foam analysis certificates from last 4 years show a pH of 5.5, 5.1, 5.7, and 5.9 for 2018, 2017, 2016, and 2015, respectively.
According to MSC Circular 1312, section 3.5, the pH of the foam concentrate shall be between 6-9.5. According to chemical safety data sheet for ATC FC-600 foa, typical pH is 7-8.5
Submit documentary evidence demonstrating that the pH of the deck foam is within a range acceptable to the Administration. If the foam's pH is no longer within acceptable limits IAW MSC Circular 1312, the foam must be replaced.
74 SOLAS (14) VII/10.1 IBC 11.3.1 (50ac)
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 6 April 2018
Resolved 16 March 2018
Resolution: Cleared deficiency based on correspondence between Odfjell technical department, DNV-GL, and Norway agreeing that foam will be replaced within 6 months (by September 2018).
Each vessel vapor connection flange face must have a 1/2 inch (12.7mm) permanent (i.e. welded) stud projecting outward at least 1.0 inches (25.9mm) from the flange face.
Multiple vapor connection flanges lack a permanently affixed stud, or stud is completely missing.
46CFR39.2001(j) 50c
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 6 April 2018
Resolved 9 March 2018
Resolution: Ob-board deficiency check conducted by [name withheld] were found to be welded.
Deck/Cargo › Cargo Transfer/Lightering (liquid) › Combustible Gas Indicator
Issued 8 May 2017Resolved
Ships carrying toxic of flammable products shall be equipped with at least two instruments calibrated for testing both toxic and flammable concentrations. PSC officer observed all span gas onboard is expired (07/28/2016 and FEB 2015)
Condition: Invalid
Action required: 705 - Other - as specified
Due 9 June 2017