Records from 1996 to 2025. Most recent: inspection, 13 February 2025.
Inspection history · 141
13 February 2025
Re-Inspection · Deficiency Check
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 8078993
21 November 2024
Deficiency Check · Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 8037948
20 November 2024
In-Service Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 8037659
22 August 2024
Deficiency Check · Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7986597
22 May 2024
COI Inspection · Deficiency Check
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7916899
9 May 2024
In-Service Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7909545
28 February 2024
Re-Inspection · Deficiency Check
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7871424
15 November 2023
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7823834
5 September 2023
Deficiency Check
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7785288
23 August 2023
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7774765
26 May 2023
Drydock Exam
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 7593803
27 April 2023
Deficiency Check · MTSA Verification · COI Inspection · Administrative Inspection
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 7691253
8 September 2022
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7554055
9 June 2022
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7472524
10 March 2022
COI Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7407765
31 January 2022
In-Service Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7388377
15 December 2021
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7368978
23 October 2021
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 7340085
27 August 2021
Re-Inspection · In-Service Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7300088
2 August 2021
Administrative Inspection · Deficiency Check
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7275160
10 June 2021
Re-Inspection · Administrative Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7221124
11 March 2021
COI Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7152876
23 February 2021
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 7147926
16 December 2020
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7112682
23 September 2020
Administrative Inspection · Deficiency Check · Examination of Repairs
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7064027
23 September 2020
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 7066621
6 September 2020
Damage Survey · Examination of Repairs
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7054082
3 September 2020
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7048932
16 August 2020
Administrative Inspection · In-Service Inspection · Deficiency Check
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7035172
15 August 2020
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 7035139
27 July 2020
Administrative Inspection · Deficiency Check
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 7017168
14 July 2020
Administrative Inspection
Administrative · Marine Safety Detachment Fort Macon · USCG East District (CGD-E) · Activity 7006785
14 July 2020
Type not recorded
No type recorded · Marine Safety Detachment Fort Macon · USCG East District (CGD-E) · Activity 7012960
15 June 2020
Administrative Inspection · Re-Inspection
Physical examination · Marine Safety Detachment Fort Macon · USCG East District (CGD-E) · Activity 6977283
26 May 2020
Deadweight Survey
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 6972620
26 September 2019
Examination of Repairs · COI Inspection · Hull Examination · Internal Structural Exam · MTSA Verification
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 6839713
19 June 2019
Deficiency Check · Re-Inspection · Administrative Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6718809
9 June 2019
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 6713032
21 March 2019
Re-Inspection · Administrative Inspection · MTSA Verification
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6646478
19 December 2018
Re-Inspection · Administrative Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6600147
13 December 2018
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 6619751
26 September 2018
COI Inspection · Administrative Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6548541
9 August 2018
Administrative Inspection
Administrative · Navigation Center · Activity 6505921
13 July 2018
Damage Survey · Deficiency Check
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6477754
13 July 2018
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 6490138
27 June 2018
Re-Inspection · Deficiency Check
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6457535
3 June 2018
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 6435690
28 March 2018
Administrative Inspection · Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6380193
15 March 2018
In-Service Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6372635
5 January 2018
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 6333045
21 December 2017
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 6327367
14 September 2017
Deficiency Check · COI Inspection · MTSA Verification
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 6266396
28 November 2016
Internal Structural Exam · Hull Examination · Examination of Repairs
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 6053528
6 September 2016
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 5993743
8 June 2016
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 5900864
1 March 2016
COI Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 5824524
2 February 2016
Examination of Repairs
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 5814378
3 December 2015
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 5774320
30 October 2015
Examination of Repairs
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 5754262
29 October 2015
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 5778870
3 September 2015
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 5233733
12 October 2014
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 5007042
23 August 2014
Type not recorded
No type recorded · Sector North Carolina · USCG East District (CGD-E) · Activity 4965838
8 May 2014
MTSA Verification · COI Inspection · Hull Examination · Administrative Inspection · Internal Structural Exam · Examination of Repairs
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 4853178
14 June 2012
Deficiency Check · Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 4343425
2 February 2012
Examination of Repairs · Construction Oversight
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 4248303
31 August 2011
Re-Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 4132273
1 December 2010
Re-Inspection · Deficiency Check
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3902550
15 September 2010
Re-Inspection
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3850268
8 September 2010
Type not recorded
No type recorded · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3846019
8 September 2010
In-Service Inspection
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3846149
28 March 2010
Type not recorded
No type recorded · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3704569
10 March 2010
Deficiency Check · MTSA Verification · COI Inspection
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3692281
16 February 2010
Periodic Inspection
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3717934
11 December 2009
Administrative Inspection
Administrative · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3648770
3 July 2009
Type not recorded
No type recorded · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3525508
25 April 2009
Type not recorded
No type recorded · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3462070
15 April 2009
Administrative Inspection
Administrative · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3454686
13 March 2009
Type not recorded
No type recorded · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3675395
11 March 2009
COI Inspection
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3431002
8 December 2008
Drydock Exam · Internal Structural Exam · Deficiency Check
Physical examination · Marine Safety Detachment Nags Head · USCG East District (CGD-E) · Activity 3376003
31 July 2008
Re-Inspection
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3284776
3 April 2008
COI Inspection · MTSA Verification
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3168414
18 July 2007
In-Service Inspection
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 3085210
16 April 2007
Type not recorded
No type recorded · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2909496
4 April 2007
COI Inspection · MTSA Verification
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2895017
23 February 2007
Deficiency Check
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2876562
29 September 2006
Hull Examination · Internal Structural Exam
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 2789916
15 September 2006
Type not recorded
No type recorded · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2779125
12 July 2006
Periodic Inspection
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2710431
5 April 2006
MTSA Verification · COI Inspection
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2615577
21 February 2006
Examination of Repairs
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2589295
14 February 2006
Type not recorded
No type recorded · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2585006
14 February 2006
Examination of Repairs
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2588998
25 January 2006
Re-Inspection
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2573197
15 December 2005
Type not recorded
No type recorded · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2556729
11 October 2005
Periodic Inspection
Physical examination · Marine Safety Unit Wilmington · USCG East District (CGD-E) · Activity 2511655
1 July 2005
Type not recorded
No type recorded · MSO WILMINGTON · USCG East District (CGD-E) · Activity 2426602
13 April 2005
MTSA Verification · COI Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 2331814
16 March 2005
Type not recorded
No type recorded · MSO WILMINGTON · USCG East District (CGD-E) · Activity 2311927
22 January 2005
Type not recorded
No type recorded · MSO WILMINGTON · USCG East District (CGD-E) · Activity 2290014
19 January 2005
Type not recorded
No type recorded · MSO WILMINGTON · USCG East District (CGD-E) · Activity 2283976
14 October 2004
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 2220102
14 October 2004
MTSA Verification
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 2231073
22 April 2004
COI Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 2059697
16 March 2004
Hull Examination
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 2022753
8 December 2003
Security Plan Review - ASP
Administrative · Marine Safety Center (MSC) · Activity 1961089
16 October 2003
Deficiency Check
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1929705
8 September 2003
Type not recorded
No type recorded · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1901512
17 July 2003
Damage Survey · Deficiency Check
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1849869
9 July 2003
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1807551
17 June 2003
Type not recorded
No type recorded · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1819593
12 May 2003
Damage Survey
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1791781
11 May 2003
Damage Survey
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1791756
17 January 2003
COI Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1728026
7 February 2002
COI Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1484699
20 November 2001
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1073910
31 October 2001
Type not recorded
No type recorded · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 771954
3 October 2001
Hull Examination
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1387182
16 August 2001
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1362402
10 May 2001
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1362196
8 February 2001
COI Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1444458
23 August 2000
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1465587
12 May 2000
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 823525
11 February 2000
COI Inspection · Hull Examination
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1470544
8 February 2000
Type not recorded
No type recorded · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1048167
17 September 1999
Deficiency Check
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1029299
19 August 1999
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1421716
17 May 1999
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1458639
18 February 1999
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1436167
18 November 1998
COI Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1408205
11 August 1998
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1473194
18 May 1998
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1469842
18 February 1998
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1381162
18 November 1997
COI Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1383725
20 August 1997
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1447749
29 May 1997
Re-Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1375020
31 December 1996
Administrative
Administrative · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1100181
13 December 1996
Deficiency Check
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1091341
5 December 1996
Type not recorded
No type recorded · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1186877
21 November 1996
Hull Examination · Initial Construction-Excluding Oversight · Inclining Experiment · Initial Certification
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1445139
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 13 February 2025
Resolved
All vessels must be provided with a satisfactory bilge system capable of pumping water from any water tight compartment. The bilge system was unable to take suction from void spaces B-2 and B-3.
Condition: Damaged By Earlier Event
Action required: 10 - Deficiency Rectified
Resolved 13 February 2025
Resolution: A of the bilge system manifold valves were opened and cleaned; the stop check valves were found to be hanging up on debris. Once completed the valves were reassembled and the system operated satisfactoriliy.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 13 February 2025
Resolved
The general construction and machinery installations on a vessel shall be such to minimize fire hazards. The exhaust turbo on the prime mover for the A-end generator is leaking oil.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 February 2025
Resolved 27 March 2025
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 13 February 2025
Resolved
Electrical equipment must be inspected at each periodic inspection to determine the electrical condition and performance. The A-end searchlight is not operational.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 27 February 2025
Resolved 27 March 2025
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 20 November 2024
Resolved
All machinery and equipment must be installed and maintained in such a manner as to afford adequate protection from causing fire, explosion, machinery failure, and personnel injury; vessel reported a failure of high water temp and high oil pressure alarms were discovered during operational checks on the Emergency Generator. Vessel is allowed to continue operations, should an emergent situation occur that demands use of the Emergency Generator, an on-scene watchs tander shall standby machinery to perform period temperature and pressure readings during operation until deficiency is corrected.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 4 December 2024
Resolved 21 November 2024
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 9 May 2024
Resolved
Predischarge delays that are not accurate to within +20 percent/-0 percent at 70 degrees Fahrenheit of their rating shall be replaced. The time delay on the engine room fixed CO2 system failed, the bottle is marked as a 30 second delay, during the test the delay was not activated until 40.9 seconds.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 23 May 2024
Resolved 22 May 2024
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 28 February 2024
Resolved
Before the vessel leaves port and at all times during the voyage, each lifesaving appliance must be in working order and ready for immediate use. Taking into account 199.190(h) vessel's 05 IBA HRU's expire the last day of Feb 2024.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 March 2024
Resolved 1 March 2024
Resolution: 05 HRU's replaced.
09 - Working and Living Conditions › 091 - Living Conditions › Sanitary Facilities
Issued 23 August 2023
Resolved
Except as specifically excluded by this section, separate public toilet spaces shall be provided for male and female passengers with at least the minimum equipment in each based upon the number of passengers permitted to be carried as set forth in table 72.25–15(a). The sole sink in the men's passenger washroom was found inoperable. Repair sink and demonstrate operation to the attending marine inspector.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 September 2023
Resolved 5 September 2023
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 23 August 2023
Resolved
Prime movers must meet § 58.01–5 and subpart 58.10 of this chapter. The number one ship service generator was reported by the crew to be losing approximately one pint of coolant per day of operation with an unknown cause. Diagnose source of coolant leak and effect repairs to the satisfaction of the attending marine inspector.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 September 2023
Resolved 5 September 2023
04 - Emergency Systems › N/A - No Subsystem › Emergency source of power - Emergency generator
Issued 8 September 2022
Resolved
The emergency power source must meet table 112.05-5(a) and have the capacity to supply all loads that are simultaneously connected to it for a period of 8 hours; vessel's EDG is overheating after while running under electrical load.
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 October 2022
Resolved 24 May 2023
Resolution: While vessel was in drydock, NCDOT cut holes in the bulkhead of the adjacent space to the EDG intake to allow for better air flow. EDG was ran for approximately 02 hours; All SAT.
09 - Working and Living Conditions › 092 - Working Conditions › Ventilation (Working spaces)
Issued 8 September 2022
Resolved
Each machinery space must be ventilated to ensure that, when machinery or boilers are operating at full power in all weather including heavy weather, an adequate supply of air is maintained for the operation of the machinery and for the safety, efficiency, and comfort of the crew; vessel's EDG space ventilation is insufficient for continuous operation of generator which causes it to overheat.
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 October 2022
Resolved 24 May 2023
Resolution: While vessel was in drydock, NCDOT cut holes in the bulkhead of the adjacent space to the EDG intake to allow for better air flow. EDG was ran for approximately 02 hours; All SAT.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 9 June 2022
Resolved
All engines must be suitable for intended service, designed and constructed in conformance w/ sub chapter F; Vessel’s #2 generator prime mover is leaking cooling water and requires re-fill daily. Vessel must have leak repaired at next Drydock.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 September 2022
Resolved 24 May 2023
Resolution: Cooling water piping was replaced while vessel was in drydock. All SAT.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 16 December 2020
Resolved
Electric installations on vessels must ensure maintenance of services necessary for safety under normal conditions and the protection of passengers and crew; the wire to the deck light of the A-end 01 passenger deck light is deteriorated and the insulation is holed.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 December 2020
Resolved 21 December 2020
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 23 September 2020
Resolved
Vital systems that are remotely controlled must be provided with effective primary control systems; the propulsion/steering control system is malfunctioning and presenting an error code which indicates a bad actuator.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 23 September 2020
02 - Structural Conditions › N/A - No Subsystem › Steering gear
Issued 6 September 2020
Resolved
Each power-driven steering-gear system must be provided with at least one steering-gear control system; Vessel lost control of Voith system from A-End controls. Provided technical report from a competent authority to the satisfaction of the attending Marine Inspector.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 8 September 2020
Resolution: Attended vessel and witnessed sea trials
02 - Structural Conditions › N/A - No Subsystem › Steering gear
Issued 16 August 2020
Resolved
Each power-driven steering-gear system must be provided with at least one steering-gear control system; Vessel lost control of Voith system from A-End controls. Provided technical report from a competent authority to the satisfaction of the attending Marine Inspector.
Condition: Design Flaw
Action required: 17 - Rectify deficiencies prior to departure
Resolved 20 August 2020
Resolution: Atteneded vessel and witnessed proper operation
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 15 July 2020
Resolved
Captain reported a loss of steering on the "A" end of the vessel to the Coast Guard. All repairs are to be made to the satisfaction of the attending marine inspector prior to movement.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 15 July 2020
Resolved 15 July 2020
Resolution: Maintenance crew trouble shot the system, found error codes identifying faulty longitudinal actuator for both the A and B end of vessel. Maintenance crew replaced both actuators. Tested steering at dock and underway. ALL SAT.
04 - Emergency Systems › N/A - No Subsystem › Man Overboard Drill (MOB)
Issued 15 June 2020
Resolved
Conduct MOB and demo. rescue boat drill. Prior to carring passengers due to not being properly manned at the time of inspection.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 27 July 2020
Resolution: Witnessed sat MOB Drill w/ resue Boat
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 15 June 2020
Resolved
Provide CG approved first aid kit in pilot house (missing out fit)
Action required: 705 - Other - as specified
Due 1 July 2020
Resolved 2 July 2020
Resolution: Photos provided of new approved first aid kit, SAT
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 15 June 2020
Resolved
Remove oil containers not approved, install flammable locker if needed/required.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 July 2020
Resolved 2 July 2020
Resolution: Statement provided from NCDOT that containers were removed from engine room. NCDOT provided new proposed containers for review. 2 metal containers allowed as per proposal.
02 - Structural Conditions › N/A - No Subsystem › Stability/strength/loading information and instruments
Issued 13 March 2020
Resolved
Vessel had deck/ramp pad modifications during drydock. Perform new stability test and receive new stability letter from the USCG prior to carrying passengers.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 26 May 2020
Resolution: Witnessed Deadweight Survey. Engineer is submitting to MCS for new stability letter.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 19 June 2019
Resolved
The pull box handle for the emergency generator space fixed CO2 system is broken, a wrench has been attached to the station as a means of opening the pull box; the handle must be replaced.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 21 June 2019
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 21 March 2019
Resolved
Installed CO2 system shall have an approved delayed discharge. The current time delay is a 30 second delay. When tested the delay lasted 43 seconds which is outside of the allowable variance. Replace and prove proper operation.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 3 April 2019
Resolution: The time dealy bottle has been replaced, see narrative for further information.
11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 21 March 2019
Resolved
Each passenger vsl under 500 GT must carry 1 rescue boat approved under 160.156. The grab line on both port and stbd side is deteriorating. Replace with same size line of UV protection.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 4 April 2019
Resolution: Grab lines have been replaced.
10 - Safety of Navigation › N/A - No Subsystem › Automatic Identification System (AIS)
Issued 26 September 2018
Resolved
The AIS is not transmitting all of the required data; enter the data points for the antenna distance from the bow, stern, port side, and stbd side. Additionally enter data point for the vessels draft.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 1 October 2018
10 - Safety of Navigation › N/A - No Subsystem › Automatic Identification System (AIS)
Issued 9 August 2018
Resolved
The vessel is currently not broadcasting (1) IMO number
Condition: Invalid
Due 10 September 2018
Resolved 26 September 2018
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 27 June 2018
Resolved
The prime mover for the emergency generator has three lube oil hoses that are not of an approved type; replace the hoses in question with SAE J1942 type hoses.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 27 July 2018
Resolved 23 July 2018
Fire Fighting › Ventilation Systems › Ventilation Fire Dampers
Issued 28 March 2018
Resolved
Vent closure handle is broken, louvers must be closed by hand, repair as necessary.
Action required: 705 - Other - as specified
Due 28 March 2018
Resolved 11 April 2018
Deck/Cargo › Vapor Control Systems › Flame Screens
Issued 21 December 2017
Resolved
Install a flame screen (30 X 30 mesh) in the fuel tank vent for the emergency generator day tank.
Due 4 January 2018
Resolved 4 January 2018
Engineering › Steering Gear System › Valve, Control
Issued 21 December 2017
Resolved
Properly label/color code the manual controls for the voith unit IAW the operating instructions.
Due 4 January 2018
Resolved 4 January 2018
Stability › Watertight Integrity › Watertight Subdivision Standard
Issued 25 September 2017
Resolved
Found WTDs #1, #3, & #4 unable to pass a chaulk test. Repair doors to the satisfaction of attending CG Marine Inspector. *Vessel may operate for prior to completing repairs for evacuation of Hatteras and/or Ocracoke Islands on an emergency route.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 28 September 2017
Resolution: Witnessed chalk test of watertight doors; all sat.
Communications › Alarms/Indicators › General Alarm
Issued 25 September 2017
Resolved
Found general alarm bell on the A-end passenger deck inoperable. Repair alarm.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 9 October 2017
Resolved 28 September 2017
Resolution: Witnessed operational test of general alarm; all sat.
Lifesaving › Lifebuoys › Serviceable
Issued 8 June 2016
Resolved
Replace the ring buoy on th 02 deck due to deterioration.
Due 22 June 2016
Resolved 8 June 2016
Documentation › Manuals/Policy Documentation › Steering Gear Changeover Instructions
Issued 8 June 2016
Resolved
Provide the vessel with with instructions for taking local control of the steering in each steering gear room.
Due 22 June 2016
Resolved 7 September 2016
Resolution: Instruction have been posted and equipment is marked and color coded.
Electrical › Electrical Distribution System (service) › Switch
Issued 3 September 2015
Resolved
Noted several motor controls without identification label on the exterior, insure proper labeling of all motor controllers IAW 111.70-3 (d).
Due 2 October 2015
Resolved 3 December 2015
Resolution: Item was previously corrected and not cleared in MISLE. Spot checked several controllers and all had appropriate labels.
Engineering › Diesel Engine (propulsion-direct drive) › Emergency shutdown
Issued 20 August 2014
Resolved
Low Lube oil pressure alarm and shutdown needs to operate as required. Shutdown not working on MDE's.
Action required: 705 - Other - as specified
Due 18 October 2014
Resolved 21 December 2017
Electrical › Electrical Distribution System (emergency) › Panelboard
Issued 20 August 2014
Resolved
EDG high temp and low lube oil alarms not indicating at either end of the bridge. Repair/replace and prove proper operation.
Action required: 705 - Other - as specified
Due 27 August 2014
Resolved 24 September 2014
Documentation › Certificates/Documents › FCC Safety Radiotelephony Certificate
Issued 14 June 2012
Resolved
Provide the vessel with an FCC Safety Radio Certificate
Condition: Invalid
Action required: 705 - Other - as specified
Due 29 June 2012
Resolved 29 June 2012
Documentation › Certificates/Documents › FCC Vessel Bridge-to-Bridge Radiotelephony Cert.
Issued 14 June 2012
Resolved
Provide the vessel with a Bridge to Bridge Certificate
Condition: Invalid
Action required: 705 - Other - as specified
Due 29 June 2012
Resolved 29 June 2012
Stability › Watertight Integrity › General
Issued 14 June 2012
Resolved
Repair the #2 WTD indicator switch
Action required: 705 - Other - as specified
Due 29 June 2012
Resolved 29 June 2012
Electrical › Electrical Distribution System (service) › Ground Detection
Issued 1 December 2010
Resolved
Determine the cause of the ground in the main switchboard and repair as necessary.
Action required: 705 - Other - as specified
Due 15 December 2010
Resolved 15 March 2011
Communications › Alarms/Indicators › Engineers' Assistance-needed Alarm
Issued 1 December 2010
Resolved
Repair the visual indicators as necessary on the alarm panel in the engine control room.
Due 15 December 2010
Resolved 21 December 2010
Lifesaving › Inflatable Liferafts › Float Free
Issued 1 December 2010
Resolved
Properly rig the liferafts to provide for float free arrangement.
Due 15 December 2010
Resolved 14 December 2010
Documentation › Manuals/Policy Documentation › Emergency Instructions
Issued 15 September 2010
Resolved
Provide the vessel with Emergency Intructions within the passenger accommodation space IAW 46 CFR 199.80 (c).
Due 30 September 2010
Resolved 21 September 2010
Communications › Audible Communications › SPD (Other)
Issued 9 March 2010
Resolved
Adjust speaker volume in engine control room so engineers can hear announcements IAW 46 CFR Sub H and 46 CFR 113.50-15.
Action required: 705 - Other - as specified
Due 10 April 2010
Resolved 12 April 2010
Communications › Internal Communications System › Sound-powered Telephone
Issued 9 March 2010
Resolved
Procure more appropriate sound powered phones, conduct training on emergency steering and conduct a steering drill in the presence of a CG marine Inspector IAW 46 CFR part 58.
Action required: 705 - Other - as specified
Due 30 June 2010
Resolved 1 December 2010
Communications › Alarms/Indicators › Lube Oil Low Pressure Alarm
Issued 9 March 2010
Resolved
Test the L/O and J/W alarms on both M/E's and both SSDG's in the presence of a CG marine inspector IAW 46 CFR Sub F.
Action required: 705 - Other - as specified
Due 10 April 2010
Resolved 12 April 2010
Lifesaving › Launching Appliances › Davit
Issued 9 March 2010
Resolved
Renew the Voith unit hydraulic fitting on the Pilot house deck IAW 46 CFR Part 58.
Action required: 705 - Other - as specified
Due 10 April 2010
Resolved 12 April 2010
Engineering › Compressed Air System (control) › Valve
Issued 9 March 2010
Resolved
Test the pressure vessel relief valve in the presence of a CG marine inspector IAW 46 CFR Sub F.
Action required: 705 - Other - as specified
Due 10 April 2010
Resolved 12 April 2010
Lifesaving › Launching Appliances › Davit
Issued 9 March 2010
Resolved
Conduct rescue boat davit maintenance IAW shipboard maintenance program and 46 CFR Sub W.
Action required: 705 - Other - as specified
Due 10 April 2010
Resolved 12 April 2010
Lifesaving › Rescue Boat Equipment › Sea-anchor
Issued 9 March 2010
Resolved
Provide a sea anchor for rescue boat IAW 46 CFR Sub W.
Action required: 705 - Other - as specified
Due 10 April 2010
Resolved 12 April 2010
Fire Fighting › Fire Main › Valves
Issued 9 March 2010
Resolved
Make repairs to the "A" end fire station valve IAW 46 CFR Sub H.
Action required: 705 - Other - as specified
Due 10 April 2010
Resolved 12 April 2010
Electrical › Electrical Distribution System (service) › Switch
Issued 16 February 2010
Resolved
Install remote propulsion shut downs on the navigation bridge IAW 46 CFR 62.35-5.
Action required: 705 - Other - as specified
Due 30 October 2010
Resolved 1 March 2012
Resolution: Witness new installations.
Electrical › Electrical Distribution System (emergency) › Switch
Issued 16 February 2010
Resolved
Install bilge high level alarms in all spaces (except peaks) IAW 46 CFR 62.35-50.
Action required: 705 - Other - as specified
Due 16 March 2010
Resolved 4 May 2010
Resolution: After deliberation with the NCDOT Ferry Division managers and the MI''s at Sector NC, I am satisfied that high bilge alarms are not required on this vessel based on the level of manning.
Engineering › Steering Gear System › Piping
Issued 11 December 2009
Resolved
Determine the cause of the hydraulic fluid leak in the "A" end Voith unit and make repairs as necessary. The repairs are to be carried out to the satisfaction of an attending USCG Marine Inspector.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 16 February 2010
Navigation › Piloting/Steering › Compass Deviation Table
Issued 11 March 2009
Resolved
Current Compass Deviation Table is From 2000, provide the vessel with a current deviation table.
Action required: 705 - Other - as specified
Due 30 April 2009
Resolved 24 April 2009
Resolution: Compass was swung and a new Deviation Table provided.
Fire Fighting › Fire Pumps › Power Source
Issued 11 March 2009
Resolved
Fire Pump has a 5 second delay between pressing the start button and the time the pump comes online.
Determine cause of problem with the fire pump and make repairs to the satisfaction of a CG Marine Inspector.
Action required: 701 - Prior to carriage of passengers/cargo
Due 10 April 2009
Resolved 12 March 2009
Resolution: Replaced both low speed coil contactors in the fire pump control panel.
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 31 July 2008
Resolved
Update the first aid kit as necessary, several items are expired.
Action required: 705 - Other - as specified
Due 30 August 2008
Resolved 27 August 2008
Operations/Management › Drills/Instruction › Launching/Recovery of Survival Craft
Issued 4 April 2007
Resolved
Crew did not demonstrate adequate proficiency in rescue boat recovery operations. Crew required to conduct satisfactory man overboard drill utilizing onboard cable launching system
Action required: 705 - Other - as specified
Due 19 April 2007
Resolved 20 May 2007
Resolution: Conducted satisfactory audit of security officer procedures.
Personnel › Training › Fast Rescue Boat
Issued 29 September 2006
Resolved
Demonstrate crew drill proficiency with new rescue boat launching, operation and recovery IAW 46 CFR 199.176. Demonstrate to the satisfaction of the attending marine inspector, prior to carrying passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Due 16 February 2007
Resolved 25 February 2007
Resolution: Satisfactory rescue boat operations observed by CG Inspectors.
Accommodation/Occupational Safety › Occupational Safety › Deck Rail
Issued 29 September 2006
Resolved
Install suitable rails IWO rescue boat davit operating station (for davit operator) IAW 46 CFR 72.40-5.
Action required: 701 - Prior to carriage of passengers/cargo
Due 14 February 2007
Resolved 25 February 2007
Resolution: Rails installed at davit operating station
Fire Fighting › Fire Pumps › Pressure
Issued 21 February 2006
Resolved
NCDOT personnel observed fire pump operating with low output pressure. Vessel taken out of service pending repair.
Action required: 705 - Other - as specified
Due 21 February 2006
Resolved 21 February 2006
Resolution: NCDOT maintenance personnel replaced fire pump and conducted successful operational test in presence of attending USCG Inspector.
Fire Fighting › Fire Main › Condition
Issued 14 February 2006
Resolved
Routine inspection of Fire Main piping reveled wastage.
Condition: Unknown
Action required: 705 - Other - as specified
Due 14 February 2006
Resolved 14 February 2006
Resolution: NCDOT personnel replaced approximately 2 ft section of Fire Main piping. USCG Inspector witnessed satisfactory test of repairs.
Lifesaving › Lifebuoys
Issued 22 April 2004
Resolved
Provide servicable self activating flashing strobe light for 1 of the 4 required ring buoys. LEGACY COMPONENT DESC: Self-igniting Lights
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 22 May 2004
Resolved 22 April 2004
Resolution: Provided servicable self activating flashing strobe light for 1 of the 4 required ring buoys prior to the completion of the inspection.
Engineering › Steering Gear System
Issued 17 July 2003
Resolved
SHOW PROPER OPERATION OF STEERING SYSTEM PRIOR TO CARRYING PASSENGERS FOR HIRE.
Condition: Damaged By Earlier Event
Due 18 July 2003
Resolved 18 July 2003
Operations/Management › Drills/Instruction
Issued 9 July 2003
Resolved
PROVIDE PROOF OF MAN OVERBOARD DRILLS BEING CONDUCTED WHILE UNDERWAY. DRILLS MUST BE CONDUCTED WHILE UNDERWAY A MINIMUM OF ONCE PER MONTH AND ALL CREWS MUST PERFORM USING RESCUE BOAT. LEGACY COMPONENT DESC: Man Overboard Recovery
Condition: Design Flaw
Due 9 August 2003
Resolved 8 September 2003
Lifesaving › Embarkation Appliances/Stations
Issued 9 July 2003
Resolved
RELOCATE RESCUE LADDER TO A MORE SUITABLE AREA TO MAKE IT MORE READILY AVAILABLE DURING RESCUE OPERATIONS. LEGACY COMPONENT DESC: Accessability
Condition: Design Flaw
Due 9 August 2003
Resolved 8 September 2003
Operations/Management › Drills/Instruction
Issued 9 July 2003
Resolved
CONDUCT ENOUGH MAN OVERBOARD DRILLS UNDERWAY TO DETERMINE SUITABILITY OR UNSUITABILITY OF THE CURRENT RESCUE BOAT IN INCLEMENT WEATHER. LEGACY COMPONENT DESC: Man Overboard Recovery
Condition: Unknown
Due 9 October 2003
Resolved 16 October 2003
Engineering › Shafting/Propeller Arrangements
Issued 12 May 2003
Resolved
SHOW PROPER OPERATION OF VOITH OMNI DRIVE UNIT ON "A" END. LEGACY COMPONENT DESC: Propeller (controllable pitch)
Due 19 May 2003
Resolved 15 May 2003
Fire Fighting › Fire Pumps
Issued 12 May 2003
Resolved
SHOW PROPER OPERATION OF FIRE PUMPS. NO PASSENGERS FOR HIRE UNTIL CLEARED. LEGACY COMPONENT DESC: Gland Sealing
Condition: Unknown
Due 19 May 2003
Resolved 15 May 2003
Construction/Loadline
Issued 19 August 1999
Resolved
PROVE PROPER OPERATION OF WTD #2.
Condition: Unknown
Due 19 August 1999
Resolved 19 August 1999
Accommodation/Occupational Safety
Issued 5 December 1996
Resolved
PRIOR TO OPERATING, PROPERLY LABEL EMERGENCY ESCAPE HATCHES LOCATED IN FWD/AFT PROPULSION COMPARTMENTS.
Condition: Unknown
Due 5 December 1996
Resolved 5 December 1996
Documentation
Issued 21 November 1996
Resolved
VESSEL MUST HAVE A STABILITY LETTER ISSUED BY THE COAST GUARD BEFORE THE VESSEL IS PLACED IN SERVICE (46 CFR 170.120(a)). WHEN ISSUED THIS LETTER MUST BE POSTED IN THE PILOTHOUSE OF THE VESSEL (46 CFR 78.12-1). THIS REQUIREMENT TO BE COMPLETED PRIOR TO COMPLIANCE DATE.
Condition: Unknown
Due 21 November 1996
Resolved 21 November 1996
Fire Fighting
Issued 21 November 1996
Resolved
COMPLETE FIRE DRILLS REQUIRED BY 46 CFR 78.17-50 PRIOR TO OPERATION WITH PASSENGERS NO LATER THAN COMPLIANCE DATE.
Condition: Unknown
Due 21 November 1996
Resolved 21 November 1996
Lifesaving
Issued 21 November 1996
Resolved
COMPLETE LIFESAVING DRILLS REQUIRED BY 46 CFR 78.17-50 PRIOR TO OPERATING WITH PASSENGERS NO LATER THAN COMPLIANCE DATE.
Condition: Unknown
Due 21 November 1996
Resolved 21 November 1996