M. J. LEE

M. J. LEE is a 1996 passenger vessel (inspected). The Coast Guard has recorded 41 inspections since 1997, most recently in May 2026, along with 29 deficiencies.

Records from 1997 to 2026. Most recent: inspection, 18 May 2026.

Built
1996
Last inspected
18 May 2026
Documentation
Valid · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

KOH462
446139
Flag
UNITED STATES
—
Maury page id
psix-446139

Inspections, by type

…with no type recorded1
Years with a record 25 calendar years (1997–2026)
The 41 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Registered dimensions (L × B × D)55.0 ft × 25.0 ft × 4.7 ft
Registered tonnagegross 54 / net 43
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderDIVERSIFIED MARINE INC · PORTLAND, OR, UNITED STATES · built 1996
Hull materialSteel
PropulsionElectric Motor
Hull shapeBox
Hull configurationMonohull
Hailing portCANBY, OR
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 6 May 2026 · expires 31 May 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it54 - Simplified, Gross Ton
43 - Simplified, Net Ton
30 - Dead Weight, Ton
101 - Displacement, Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

No FCC ship-station licence is recorded against this Official Number in the file of 6 September 2026. That is a fact about the licence file, not about the radio.

A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.

Inspection history · 41

18 May 2026 Annual Inspection
Physical examination · Sector Columbia River · USCG Northwest District (CGD-NW) · Activity 8420441
22 May 2025 Annual Inspection
Physical examination · Sector Columbia River · USCG Northwest District (CGD-NW) · Activity 8151245
7 May 2024 Annual Inspection
Physical examination · Sector Columbia River · USCG Northwest District (CGD-NW) · Activity 7909420
8 June 2023 Annual Inspection
Physical examination · Sector Columbia River · USCG Northwest District (CGD-NW) · Activity 7723964
9 June 2022 Hull Examination · COI Inspection
Physical examination · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 7431961
15 November 2021 Annual Inspection
Physical examination · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 7351534
25 October 2021 Administrative Inspection
Administrative · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 7360699
9 November 2020 Annual Inspection
Physical examination · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 7097204
4 November 2019 Annual Inspection · DAPI Audit
Physical examination · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 6850625
20 February 2019 Administrative Inspection
Administrative · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 6629145
5 November 2018 Annual Inspection
Physical examination · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 6577316
23 October 2017 COI Inspection
Physical examination · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 6306338
16 May 2017 Deficiency Check · Hull Examination
Physical examination · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 6297963
10 November 2016 Deficiency Check
Physical examination · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 6039082
24 October 2016 Annual Inspection
Physical examination · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 6028464
19 October 2015 Annual Inspection
Physical examination · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 5747340
27 October 2014 Annual Inspection
Physical examination · Sector Columbia River · USCG Northwest District (CGD-NW) · Activity 5009178
13 May 2014 Excursion Permit
Administrative · Sector Columbia River · USCG Northwest District (CGD-NW) · Activity 4857978
26 October 2010 Annual Inspection
Physical examination · Sector Portland · USCG Northwest District (CGD-NW) · Activity 3868364
3 February 2009 Annual Inspection · Plan Review "T" Boat
Physical examination · Sector Portland · USCG Northwest District (CGD-NW) · Activity 3369317
5 December 2007 Deficiency Check
Physical examination · Sector Portland · USCG Northwest District (CGD-NW) · Activity 3116962
27 November 2007 Annual Inspection
Physical examination · Sector Portland · USCG Northwest District (CGD-NW) · Activity 3101757
9 January 2007 Annual Inspection
Physical examination · Sector Portland · USCG Northwest District (CGD-NW) · Activity 2833689
7 June 2006 Examination of Repairs · Hull Examination
Physical examination · Sector Portland · USCG Northwest District (CGD-NW) · Activity 2671202
14 December 2004 Annual Inspection
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 2244022
12 July 2004 Plan Review "T" Boat
Administrative · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 2148019
16 December 2003 Annual Inspection
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1946369
17 December 2002 COI Inspection
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1718053
8 January 2002 Re-Inspection
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1474793
5 June 2001 Hull Examination
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1066855
9 January 2001 Re-Inspection
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1057074
25 January 2000 Deficiency Check
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 814756
6 January 2000 COI Inspection
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1420239
27 May 1999 Deficiency Check
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 805538
22 April 1999 Re-Inspection
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1458629
9 September 1998 Type not recorded
No type recorded · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 801588
18 June 1998 Deficiency Check
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 792948
26 March 1998 Re-Inspection
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1383839
25 February 1998 Deficiency Check
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 780542
23 September 1997 Administrative
Administrative · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 777849
23 January 1997 Initial Certification · Hull Examination · Plan Review "T" Boat · Initial Construction-Excluding Oversight
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1445141

Deficiency record · 29

Engineering › Bilge Water Management System › Strainer
Issued 16 May 2017 Resolved
Raise installed bilge strainers so that they can function as intended; inspector to verify the presence of inlet screens.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 16 June 2017
Resolution: Bilge strainer housing were raised off the deck approximately 1/2"; inlet screens were verified on all suction bells.
Construction/Loadline › Hull › Transverse Frame
Issued 16 May 2017 Resolved
Remove "fire-stop" caulking and install proper (ROCTEX) watertight blocks or fittings on electrical cables passing through bulkhead penetrations. As another alternative, RISE sleeves may be used in the MCT windows that do not have enough space for ROCTEX blocks.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 16 June 2017
Resolution: MCT penetrations were sealed satisfactorily.
Engineering › Sea-water System (primary cooling) › Piping
Issued 16 May 2017 Resolved
Provide threaded pipe caps on the two drain lines installed on the fire pump suction line to prevent accidental flooding of the void space. (Drain line presently have 1/4 valves.)
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 16 June 2017
Resolution: Drain lines were capped to prevent a potential source of flooding.
Electrical › Electrical Distribution System (service) › Grounding Conductor
Issued 16 May 2017 Resolved
Attach ground wires on the harmonic filters (2) in accordance with the approved drawings.
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 16 June 2017
Resolution: Grounding wires were installed for both harmonic filters located in the machinery void space.
Electrical › Electric Supply System (service) › Cable
Issued 16 May 2017 Resolved
Terminate all dead-end wires in a junction box, or remove unused wiring.
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 16 June 2017
Resolution: All unterminated/dead-end wiring identified during the dry-dock exam was removed from the vessel or properly terminated in a junction box.
Fire Fighting › Fire Pumps › Arrangement
Issued 16 May 2017 Resolved
Provide adequate structural support of the newly installed duplex strainer housing located adjacent to the sea-chest. (Fire pump suction line from the sea-chest.)
Action required: 705 - Other - as specified
Due 16 June 2017
Resolved 16 June 2017
Resolution: A bracket was built to support the duplex housing strainer located adjacent to the sea-chest.
Electrical › Electrical Distribution System (service) › Cable
Issued 24 October 2016 Resolved
PROPERLY RE-SECURE CABLE ON HYD. SYSTEM FILTER HOUSING (HYD. PRESSURE ALARM) SO THAT IT IS MADE WEATHERTIGHT AND TIED DOWN.
Condition: Improper Installation
Due 24 November 2016
Resolved 10 November 2016
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 24 October 2016 Resolved
PROVIDE FIRST AID KIT APPROVED BY COAST GUARD (160.041) OR EQUIVALENT.
Condition: Improper Installation
Due 24 November 2016
Resolved 10 November 2016
Lifesaving › Lifebuoys › Serviceable
Issued 27 October 2014 Resolved
Lifebuoys are worn. Renew all lifebuoys.
Due 27 November 2014
Resolved 24 November 2014
Resolution: Renewed all lifebuoys onboard.
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 27 October 2014 Resolved
Vessel to demonstrate recovery of helpless person from the water as per vessel's man overboard procedures to the satisfaction of attending marine inspector.
Due 27 November 2014
Resolved 24 November 2014
Resolution: SMI found man overboard drill conducted satisfactory
Lifesaving › Lifejacket/PFD (Type I) › Condition
Issued 27 November 2007 Resolved
Child lifejackets were Type II jackets. Replace with approved type I lifejacket IAW 46CFR180.71(c).
Due 31 December 2007
Resolved 5 December 2007
Resolution: Corrected
Engineering › Lubricating Oil Storage/Transfer System
Issued 16 December 2003 Resolved
Provide statement to MSO Portland Inspections Department delcaring that operational propulsion and steering tests were satisfactorily completed by master.
Due 16 January 2004
Resolved 5 January 2004
Fire Fighting › Fixed Fire Detection System
Issued 16 December 2003 Resolved
Provide copy of maintenance and operations manual for alarm monitor panel. LEGACY COMPONENT DESC: Control Panel
Due 16 January 2004
Resolved 5 January 2004
Fire Fighting › Fixed Fire Detection System
Issued 16 December 2003 Resolved
Provide statement of satisfactory operational test of (in accordance with maintenance and operational manual) fire detection alarms in Aux. Pump room and Mach. Enclosure. LEGACY COMPONENT DESC: Flame Detectors
Due 16 January 2004
Resolved 5 January 2004
Resolution: Tested with heat gun...thermometer and alarm tripped at 140 degrees...satisfactory
Electrical
Issued 6 January 2000 Resolved
Provide plans for installation of (2) 220 volt electric heaters in the control space/operating station. 46CFR184.210.
Condition: Unknown
Due 6 January 2000
Resolved 6 January 2000
Electrical
Issued 22 April 1999 Resolved
Remove household electrical multi-plug surge protector from the pilothouse.
Condition: Unknown
Due 22 April 1999
Resolved 22 April 1999
Documentation
Issued 22 April 1999 Resolved
Provide or revise the Chemical testing policy that includes U.S. Coast Guard regulations found in 33 CFR 95, 46 CFR 4, 46 CFR 16, & 49 CFR 40.
Condition: Unknown
Due 22 April 1999
Resolved 22 April 1999
Unknown
Issued 26 March 1998 Resolved
PROVIDE MEANS TO CONDUCT PASSENGER COUNT.
Condition: Unknown
Due 26 March 1998
Resolved 26 March 1998
Documentation
Issued 26 March 1998 Resolved
PROVIDE DOCUMENTATION OF DRUG TESTING PROGRAM AND COPY OF MIS ANNUAL REPORT.
Condition: Unknown
Due 26 March 1998
Resolved 26 March 1998
Lifesaving
Issued 26 March 1998 Resolved
CONDUCT DRILL WITH LOCAL DESIGNATED FACILITIES AND PROVIDE DOCUMENTATION TOTHIS OFFICE ATTESTING TO SAME.
Condition: Unknown
Due 26 March 1998
Resolved 26 March 1998
Electrical
Issued 26 March 1998 Resolved
REMOVE PORTABLE ELECTRIC HEATERS FROM VESSEL.
Condition: Unknown
Due 26 March 1998
Resolved 26 March 1998
Lifesaving
Issued 26 March 1998 Resolved
INSTALL RETROREFLECTIVE TAPE ON ONE RING BUOY.
Condition: Unknown
Due 26 March 1998
Resolved 26 March 1998
Lifesaving
Issued 26 March 1998 Resolved
PROVIDE LIFEJACKET DONNING PLACARDS FOR PFD'S ONBOARD (2 STYLES).
Condition: Unknown
Due 26 March 1998
Resolved 26 March 1998
Lifesaving
Issued 26 March 1998 Resolved
PROVIDE AN APPROVED FIRST AID KIT OR EQUIVALENT.
Condition: Unknown
Due 26 March 1998
Resolved 26 March 1998
Lifesaving
Issued 26 March 1998 Resolved
MARK LIFEJACKETS WITH VESSEL NAME ON BOTH SIDES FOR CHILD PFD'S.
Condition: Unknown
Due 26 March 1998
Resolved 26 March 1998
Documentation
Issued 23 January 1997 Resolved
PROVIDE CURRENT FCC RADIO SAFETY CERTIFICATE FOR VESSEL.
Condition: Unknown
Due 23 January 1997
Resolved 23 January 1997
Unknown
Issued 23 January 1997 Resolved
PROPERLY MARK RIVER GAUGE UP TO 72 FEET.
Condition: Unknown
Due 23 January 1997
Resolved 23 January 1997
Documentation
Issued 23 January 1997 Resolved
PROVIDE AND POST APPROPRIATE MASTER'S LICENSE PRIOR TO CARRYING VEHICLES ORPASSENGERS.
Condition: Unknown
Due 19 June 1997
Resolved 19 June 1997
Documentation
Issued 23 January 1997 Resolved
PROVIDE CURRENT FCC MARINE RADIO OPERATOR'S PERMIT FOR ALL VESSEL MASTERS.
Condition: Unknown
Due 23 January 1997
Resolved 23 January 1997

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.