SEA HUNTER

SEA HUNTER is a 1997 passenger vessel (inspected). The Coast Guard has recorded 60 inspections since 1997, most recently in March 2026, along with 48 deficiencies, 1 operational control and 2 casualty investigations between 2011 and 2020.

Records from 1997 to 2026. Most recent: inspection, 24 March 2026.

Built
1997
Last inspected
24 March 2026
Documentation
Valid · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

WCX6852
453850
Flag
UNITED STATES
367306150, 368412720
Maury page id
psix-453850

Inspections, by type

…with no type recorded4
Years with a record 28 calendar years (1997–2026)
The 60 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Registered dimensions (L × B × D)62.0 ft × 19.0 ft × 7.5 ft
Registered tonnagegross 59 / net 47
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderRESMONDO BOAT WORKS INC · PERDIDO BEACH, AL, UNITED STATES · built 1997
Hull materialFRP (Fiberglass)
PropulsionDiesel Reduction
Hull shapeShip
Hull configurationMonohull
Hailing portORANGE BEACH, AL
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 21 November 2025 · expires 30 November 2026
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it47 - Simplified, Net Ton
59 - Simplified, Gross Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

WDQ2991MMSI 368412720 · active · compulsorily equipped · granted 8 April 2025, expires 8 April 2035
WCX6852MMSI 367306150 · active · compulsorily equipped · granted 6 June 2017, expires 19 August 2027
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown. A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.

Inspection history · 60

24 March 2026 Annual Inspection · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 8331121
24 February 2025 Administrative Inspection · COI Inspection · Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 8083836
5 February 2025 Drydock Exam
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 8075046
25 September 2024 In-Service Inspection · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 8009367
16 April 2024 Annual Inspection · Administrative Inspection · Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7896122
7 November 2023 In-Service Inspection · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7823980
16 October 2023 Plan Review "T" Boat · In-Service Inspection · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7809060
27 April 2023 Annual Inspection · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7676958
9 March 2023 Administrative Inspection · Plan Review "T" Boat
Administrative · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7648508
16 February 2023 Drydock Exam · Hull Examination · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7637852
3 February 2023 In-Service Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7631812
16 May 2022 Annual Inspection · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7455326
7 October 2021 Administrative Inspection · In-Service Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7349648
26 April 2021 Administrative Inspection · Annual Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7185424
5 February 2021 Hull Examination · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 7136525
28 June 2020 Type not recorded
No type recorded · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6998600
29 April 2020 Administrative Inspection · COI Inspection · DAPI Audit · Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6945531
2 March 2020 Deficiency Check · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6919097
16 January 2020 Administrative Inspection
Administrative · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6890992
24 September 2019 In-Service Inspection · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6814658
8 April 2019 Annual Inspection · DAPI Audit · Deficiency Check · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6658467
20 February 2019 Administrative Inspection · Hull Examination · Internal Structural Exam
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6628752
27 June 2018 Type not recorded
No type recorded · USCGC JACOB POROO (WPC 1125) · USCG Heartland District (CGD-H) · Activity 6469537
3 May 2018 Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6405102
16 April 2018 Annual Inspection · Deficiency Check · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6392715
20 June 2017 Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6181849
15 March 2017 Annual Inspection · DAPI Audit · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6106552
6 March 2017 Internal Structural Exam · Administrative Inspection · Hull Examination
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6099525
4 April 2016 Annual Inspection · DAPI Audit · Deficiency Check · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 5846657
12 January 2016 Administrative Inspection
Administrative · Sector Mobile · USCG Heartland District (CGD-H) · Activity 5796042
1 May 2014 Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 4848764
4 June 2012 Examination of Repairs · Annual Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 4333295
27 September 2011 Type not recorded
No type recorded · Sector Mobile · USCG Heartland District (CGD-H) · Activity 4155123
9 March 2010 COI Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 3688407
13 April 2009 Annual Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 3440459
2 March 2009 Hull Examination
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 3426335
29 April 2008 Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 3196628
26 March 2008 Deficiency Check · Annual Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 3164817
11 April 2007 Deficiency Check
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 2904726
3 April 2007 Annual Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 2900546
6 March 2007 Hull Examination
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 2882519
28 March 2006 Annual Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 2610925
19 September 2005 Damage Survey
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 2496494
22 February 2005 COI Inspection
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 2297156
25 January 2005 Hull Examination
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 2280768
26 February 2004 Annual Inspection
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 2013734
27 March 2003 Annual Inspection
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1758911
11 February 2003 Hull Examination
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1741264
30 November 2002 Type not recorded
No type recorded · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1715508
10 June 2002 Deficiency Check
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1670370
15 March 2002 Annual Inspection
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1490089
11 April 2001 Re-Inspection
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1066481
28 March 2001 Hull Examination
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1062403
27 March 2000 COI Inspection
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1047113
9 March 1999 Hull Examination · Re-Inspection
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1360767
26 February 1998 Deficiency Check · Re-Inspection
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1447804
30 September 1997 Deficiency Check
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1117327
25 August 1997 Deficiency Check
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1120086
23 July 1997 Hull Examination · Plan Review "T" Boat · Initial Certification · Initial Construction-Excluding Oversight
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1383631
16 July 1997 Inclining Experiment
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1364283

Deficiency record · 48

07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 2 April 2025 Resolved
All machinery and equipment must be installed and maintained in such a manner as to afford adequate protection from causing fire, explosion, machinery failure, and personnel injury. STBD engine exhaust pipe and both STBD and PORT engine shaft bulkhead penetrations were not vapor-tight impairing pre-engineered system functionality for designed space.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 7 April 2025
Resolution: Vessel provided photographic evidence of correction, all sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 2 April 2025 Resolved
A generator or motor designed for 40 °C (104 °F) may be used in 50 °C (122 °F) ambient locations provided the generator or motor is derated to 80 percent of the full load rating, and the rating or setting of the overcurrent devices is reduced accordingly. Observed both generators were designed with an ambient temperature of 40°C , but were not derated to 80% of the full load rating, and the rating or setting of the overcurrent devices weren't reduced accordingly.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 16 April 2025
Resolution: Breakers on both generators were derated to below 80% load capacity, all sat.
01 - Certificates & Documentation › 012 - Crew Certificates › Other (STCW)
Issued 2 April 2025 Resolved
Marine employers must establish programs for the chemical testing for dangerous drugs on a random basis of crewmembers on inspected vessels. Vessel could not provide satisfactory proof of random drug test program for all crew members.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 14 April 2025
Resolution: Provided proof of operator and deckhand enrollment in a drug consortium, all sat.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 2 April 2025 Resolved
One ship station license will be granted for operation of all maritime services transmitting equipment on board a vessel. Vessel was unable to provide a valid FCC Station License. Cite: 47 CFR 80.13(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 14 April 2025
Resolution: Vessel provided a valid station license, all sat.
01 - Certificates & Documentation › 012 - Crew Certificates › Certificates for radio personnel
Issued 2 April 2025 Resolved
Operation of transmitters of any ship station must be performed by a person holding a commercial radio operator license or permit of the class required below. Operator on board did not hold a commercial radio operator license. Cite: 47 CFR 80.155
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 14 April 2025
Resolution: Operator obtained a marine radio operator permit.
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 30 April 2024 Resolved
The float-free link required must be certified and of the proper strength for the size of the life float. Marine Inspector observed life float link to be missing information tag and was unable to verify. Replace.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 May 2024
Resolved 27 June 2024
Resolution: Received evidence of float free link and certification.
01 - Certificates & Documentation › 012 - Crew Certificates › Medical certificate
Issued 30 April 2024 Resolved
The medical certificate will be issued for various periods of time based upon the endorsements the mariner holds. Marine Inspector observed missing medical card for vessels Captain. Provide evidence of.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 May 2024
Resolved 14 June 2024
Resolution: Recived evidence of valid medical certificate.
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 5 May 2020 Resolved
Vessel required to carry nautical charts and tables for the intended voyage. Vessel did not have up to date charts for operating area. Replace expired charts and provide proof to marine inspector.
Action required: 10 - Deficiency Rectified
Due 19 May 2020
Resolved 7 May 2020
Resolution: Vessel operator provided updated charts for the vessel's operating area.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 5 May 2020 Resolved
EPIRB Hydrostatic release is expired. Each disposable hydrostatic release must be marked with an expiration date of two years after the date on which the unit is installed. Provide new hydrostatic release installation to marine inspector. Vessel is restricted to operations not to exceed three nautical miles from shore.
Action required: 10 - Deficiency Rectified
Resolved 7 May 2020
Resolution: Vessel operator installed a new disposable hydrstatic release for the EPIRB, that is valid for two years.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 24 September 2019 Resolved
Machinery Space Boundaries on a general purpose resin vessel must be lined with noncombustible panels or insulation approved by Commandant. Noted no panels are installed in overhead of machinery spaces. Rectify deficiencies prior to the carriage of overnight passengers.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 11 March 2020
Resolution: Noted satisfactory installation of noncombustible insulation material approved by Commandant on the overhead of machinery spaces.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 30 April 2019 Resolved
Vessel is required to have an alcohol testing kit. The alcohol testing kit is expired. Provide an alcohol testing kit.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 May 2019
Resolved 7 May 2019
Resolution: A valid alcohol testing kit was provided on board the vessel with, an expiry date of 31 July 2020.
Operations/Management › Drug and Alcohol Testing › Testing, Equipment
Issued 15 May 2017 Resolved
The alcohol testing kits provided were expired. Replace with new kits IAW 46 CFR 16.240 and 46 CFR 4.06.
Action required: 705 - Other - as specified
Due 15 June 2017
Resolved 20 June 2017
Resolution: Alcohol strips were on board and available for inspection
Navigation › Piloting/Steering › Inland Navigation Rules
Issued 15 May 2017 Resolved
Navigation Rules book was not the current edition. Replace with current edition.
Action required: 705 - Other - as specified
Due 15 June 2017
Resolved 20 June 2017
Resolution: Current edition was purchased and available for inspection
Engineering › Bilge Water Management System › Piping
Issued 15 May 2017 Resolved
Bilge system piping in engine room, beneath berthing, and in the lazzerette are not authorized. Replace PVC piping with rigid non-metallic hose with approved fittings IAW 46 CRF 182.
Action required: 705 - Other - as specified
Due 31 October 2017
Resolved 3 May 2018
Fire Fighting › Fixed Fire Detection System › Smoke Detectors
Issued 15 May 2017 Resolved
The berthing rooms do not have independent modular smoke detecting units. Install smoke detecting units in each berthing room IAW 46 CFR 181.450
Action required: 705 - Other - as specified
Due 15 June 2017
Resolved 20 June 2017
Resolution: Approved smoke detectors were purchased and installed
Electrical › Electrical Distribution System (service) › Metallic Enclosure/Frame
Issued 15 May 2017 Resolved
The wire supports were missing on wires in lazerrette. Install metal supports spaced no more than 24 inches apart IAW 46 CFR 183.340.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 15 June 2017
Resolved 20 June 2017
Resolution: Appropriate amount of supports were installed
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 15 May 2017 Resolved
During the man over board drill, it was discussed that the ladder to assisst in recovering an unconscious person had been removed from the vessel and was in storage. The ladder must be put back and carried on vessel IAW 46 CFR 176.800 and 46 CFR 182.512
Action required: 705 - Other - as specified
Due 15 June 2017
Resolved 20 June 2017
Resolution: Ladder was provided and appropriate for application.
Fire Fighting › Fixed Fire Detection System › Detector/Call Point Grouping
Issued 15 May 2017 Resolved
Install a fire dectection system sensor to the galley area, IAW 46 CFR 177.410 This system has been installed for over 20 years with no sensor in galley area and is why I am giving the owner till the start of next season to install.
Action required: 705 - Other - as specified
Due 1 March 2018
Resolved 20 June 2017
Resolution: Fire detection system was installed in galley area and tested satisfactorily.
Fire Fighting › Fixed Gas Fire Extinguishing System › Tanks
Issued 14 April 2016 Resolved
Pre-engineered fire system condemned and removed. Install new system and provide servicing report from certified tech prior to carrying passengers.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 14 May 2016
Resolved 28 April 2016
Resolution: New pre-engineered system installed. Tested override and verified installation.
Operations/Management › Drug and Alcohol Testing › Testing, Equipment
Issued 14 April 2016 Resolved
Alcohol testing device not on board. Provide approved method of alcohol testing.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 28 April 2016
Resolution: Alcohol testing provided.
Operations/Management › Drug and Alcohol Testing › EAP Training Requirements
Issued 14 April 2016 Resolved
EAP training documentation not provided for crew. Provide documentation.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 28 April 2016
Resolution: Owner provided documentation of required EAP training for supervisors and crew.
Communications › Radio Communications › VHF Radiotelephone
Issued 14 April 2016 Resolved
Installed VHF radio not DSC equipped. Install or replace radio with approved type.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 28 April 2016
Resolution: Installed new VHF radio with DSC function.
Accommodation/Occupational Safety › Occupational Safety › Deck Rail
Issued 14 April 2016 Resolved
Cracked welds in tower IVO upper platform on port and stbd ladders. No crew permitted in upper tower until appropriate repairs made.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 28 April 2016
Resolution: Cracked welds properly repaired.
Engineering › Pressure Vessel › Relief Valve
Issued 14 April 2016 Resolved
Hot water heater pressure relief valve rated for 150psi. Replace valve with 100psi rated valve.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 28 April 2016
Resolution: Replaced pressure relief valve with 75 psi valve.
Fire Fighting › Means of Escape › Escape Route Signs
Issued 14 April 2016 Resolved
Forward emergency exit not labeled on outside of exit. Label exit "Emergency Exit - Keep Clear."
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 14 May 2016
Resolved 28 April 2016
Resolution: Exit properly stenciled.
Communications › Radio Communications › EPIRB
Issued 26 March 2008 Resolved
Provide EPRIB registration, Vessel restrited to within 3 miles of land.
Action required: 705 - Other - as specified
Due 28 March 2008
Resolved 26 March 2008
Engineering › Bilge Water Management System › Not Installed
Issued 26 March 2008 Resolved
Demonstrate proper operation of the engine room high water indicator light at the pilot house.
Action required: 705 - Other - as specified
Due 26 April 2008
Resolved 29 April 2008
Documentation › Logs/Records › Logbook (official)
Issued 3 April 2007 Resolved
Provide current training logbook, lifesaving maintenance record book, and bridge log in accordance with 46 CFR 185.430 and 185.720.
Action required: 705 - Other - as specified
Due 3 May 2007
Resolved 11 April 2007
Resolution: Provided a bridge log, lifesaving maintenance record book and a current training log book.
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 3 April 2007 Resolved
Provide a Coast Guard approved First Aid Kit in accordance with 46 CFR 184.710.
Action required: 705 - Other - as specified
Due 3 May 2007
Resolved 11 April 2007
Resolution: Provided a Coast Guard approved first aid kit.
Electrical › Electric Generation Source (service) › Generator
Issued 3 April 2007 Resolved
Properly clean the windings on the port generator in accordance with 46 CFR 185.520.
Action required: 705 - Other - as specified
Due 3 May 2007
Resolved 11 April 2007
Resolution: The winding on the port generator were properly cleaned.
Engineering › Bilge Water Management System › Pump
Issued 3 April 2007 Resolved
Prove proper operation of the bilge pump in the fuel space in accordance with 46 CFR 182.520.
Action required: 705 - Other - as specified
Due 3 May 2007
Resolved 11 April 2007
Resolution: Proved the operation of the bilge pump in the fuel space.
Engineering › Bilge Water Management System › Piping
Issued 3 April 2007 Resolved
Properly mount the bilge discharge line in the lazarette to keep from chafing with starboard tiller arm in accordance with 46 CFR 182.520.
Action required: 705 - Other - as specified
Due 3 May 2007
Resolved 11 April 2007
Resolution: The bilge discharge line in the lazarette was properly mounted.
Electrical › Electrical Distribution System (service) › Junction Box
Issued 3 April 2007 Resolved
Make the junction box with GFI plug on the inboard side of the port engine watertight in accordance with 46 CFR 183.340.
Action required: 705 - Other - as specified
Due 3 May 2007
Resolved 11 April 2007
Resolution: The GFI outlet was made water tight.
Engineering › Shafting/Propeller Arrangements › Stern Gland
Issued 3 April 2007 Resolved
Properly secure the port and starboard shaft log from excessive leaking in accordance with 46 CFR 176.802.
Action required: 705 - Other - as specified
Due 3 May 2007
Resolved 11 April 2007
Resolution: The packing glands were tighten on the port and starboard shaft to secure the excessive leaks.
Fire Fighting › Means of Escape › Blocked
Issued 3 April 2007 Resolved
Prove proper operation of the emergency escape hatch in accordance with 46 CFR 177.500.
Action required: 705 - Other - as specified
Due 3 May 2007
Resolved 11 April 2007
Resolution: Proved proper operation of the emergency escape hatch.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 3 April 2007 Resolved
Prove proper operation of the emergency lighting in accordance with 46 CFR 183.432, to the satisfaction of a Coast Guard Marine Inspector. Until then no overnight trips are authorized.
Action required: 705 - Other - as specified
Due 3 May 2007
Resolved 11 April 2007
Resolution: Proved proper operation of the emergency lighting.
Navigation
Issued 26 February 1998 Resolved
PROVIDE ON BOARD COPY OF RULES OF THE ROAD HANDBOOK OR EQUIVALENT AS PER 46CFR 184.420.
Condition: Unknown
Due 26 March 1998
Resolved 23 March 1998
Lifesaving
Issued 26 February 1998 Resolved
MARK LIFEFLOAT WITH NAME OF VESSEL AND CAPACITY OF LIFEFLOAT AS PER 46 CFR 185.604(A).
Condition: Unknown
Due 26 March 1998
Resolved 23 March 1998
Documentation
Issued 23 July 1997 Resolved
PROVIDE AND PROPERLY POST VESSEL'S STABILITY LETTER IAW 46 CFR 176.306.
Condition: Unknown
Due 23 August 1997
Resolved 26 August 1997
Accommodation/Occupational Safety
Issued 23 July 1997 Resolved
PROVIDE 392 SQUARE INCHES OF FREEING PORT AREA FOR THE VESSEL'S COCKPIT DECK IAW 46 CFR 178.450.
Condition: Unknown
Due 23 August 1997
Resolved 23 March 1998
Construction/Loadline
Issued 23 July 1997 Resolved
PROVE THE PROPER OPERATION OF THE GRAY WATER SUMP SUBMERSIBLE BILGE PUMP IAW 46 CFR 182.520.
Condition: Unknown
Due 23 August 1997
Resolved 26 August 1997
Electrical
Issued 23 July 1997 Resolved
SHORTEN THE WIRE, OR INSTALL 8 AWG WIRE, IN WAY OF THE BRIDGE AIR CONDITIONING IAW 46 CFR 183.340(P).
Condition: Unknown
Due 23 August 1997
Resolved 26 August 1997
Engineering
Issued 23 July 1997 Resolved
PROVIDE MACHINERY GUARDS FOR THE BELTS IN THE MAIN ENGINES IAW 46 CFR 176.830.
Condition: Unknown
Due 23 August 1997
Resolved 26 August 1997
Documentation
Issued 23 July 1997 Resolved
PROVIDE ON BOARD FCC SAFETY CERTIFICATE IAW 47 CFR 80.903.
Condition: Unknown
Due 23 August 1997
Resolved 30 September 1997
Documentation
Issued 23 July 1997 Resolved
PROVIDE ON BOARD VALID FIRST AID/CPR CARDS FOR 50% OF THE CREW IAW COAST GUARD NVIC 1-91.
Condition: Unknown
Due 23 August 1997
Resolved 26 August 1997
Documentation
Issued 23 July 1997 Resolved
PROVIDE ON BOARD VALID FCC OPERATOR'S LICENSE IAW 47 CFR 80.155.
Condition: Unknown
Due 23 August 1997
Resolved 26 August 1997
Documentation
Issued 23 July 1997 Resolved
PROVIDE ON BOARD VALID FCC STATION LICENSE IAW 47 CFR 80.15.
Condition: Unknown
Due 23 August 1997
Resolved 26 August 1997
Electrical
Issued 23 July 1997 Resolved
INSTALL PANELLING AROUND, OR REMOVE FROM VESSEL, LOOSE ELECTRICAL OUTLET BOX IN THE MAIN ACCOMODATION SPACE IAW 46 CFR 183.340.
Condition: Unknown
Due 23 August 1997
Resolved 26 August 1997

Casualty record · 2

13 June 2011Routine · role: Involved in a Marine Casualty · serious marine incident, as classified · activity 4060137
28 June 2020Routine · role: Involved in a Marine Casualty · serious marine incident, as classified · 1 dead · activity 6998600
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it, and the bridge, lock or dam the investigation names where it names one. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.