KENNEDY

KENNEDY is a 1967 school ship. The Coast Guard has recorded 166 inspections since 1981, most recently in October 2025, along with 227 deficiencies — 3 with no resolution recorded —, 1 operational control and 5 casualty investigations between 2008 and 2025.

Records from 1981 to 2025. Most recent: inspection, 28 October 2025.

Built
1967
Last inspected
28 October 2025
Documentation
Not in the documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

6621662 View on MarineTraffic leaves Maury; a third-party site, nothing from it is stored here
Flag
UNITED STATES
338919000
Maury page id
psix-45599

Inspections, by type

…with no type recorded37
…past their stated due date3
Years with a record 42 calendar years (1981–2025)
The 166 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the School Ship class in Maury's sources begin in 1981.

Documentation record

Tonnage as PSIX records it13886 - Convention (Subpart B), Gross Ton
4165 - Convention (Subpart B), Net Ton
This hull's Official Number is not in the NVDC file dated 10 September 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.

Radio station licence

KVMUMMSI 338919000 · active · compulsorily equipped · granted 24 November 2022, expires 27 November 2032
KVMUMMSI not assigned · expired · compulsorily equipped · granted 27 January 1993, cancelled 27 January 1998 · licensed under a name not among this hull’s recorded names (not shown)
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown. A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.

Inspection history · 166

28 October 2025 Administrative Inspection
Administrative · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8319288
16 July 2025 Type not recorded
No type recorded · Sector Northern New England · USCG Northeast District (CGD-NE) · Activity 8200100
23 June 2025 Type not recorded
No type recorded · Sector Northern New England · USCG Northeast District (CGD-NE) · Activity 8168625
22 April 2025 Administrative Inspection · Excursion Permit
Administrative · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 8117075
10 February 2025 Drydock Extension
Administrative · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8099512
5 January 2025 Administrative Inspection · COI Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8121607
11 September 2024 In-Service Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8008737
31 May 2024 COI Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7904785
6 May 2024 Administrative Inspection
Administrative · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7907396
19 April 2024 In-Service Inspection
Physical examination · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 7898347
1 April 2024 Administrative Inspection
Administrative · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7888135
12 February 2024 Administrative Inspection
Administrative · Sector New York · USCG Northeast District (CGD-NE) · Activity 7864961
17 January 2024 Excursion Permit
Administrative · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7850544
12 December 2023 COI Inspection · Administrative Inspection · In-Service Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7838143
9 November 2023 Administrative Inspection
Administrative · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 7815237
5 June 2023 In-Service Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7703313
30 May 2023 Administrative Inspection
Administrative · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 7700941
5 May 2023 Administrative Inspection
Administrative · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7681941
7 April 2023 In-Service Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7664665
24 March 2023 Administrative Inspection
Administrative · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7656137
3 February 2023 Administrative Inspection
Administrative · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7631704
14 December 2022 Administrative Inspection · COI Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7604440
8 September 2022 Internal Structural Exam · Drydock Exam · COI Inspection · Administrative Inspection
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 7554053
31 August 2022 In-Service Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7549012
17 August 2022 Administrative Inspection
Administrative · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7536536
24 May 2022 In-Service Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7457899
4 April 2022 Examination of Repairs · In-Service Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7424323
23 February 2022 Administrative Inspection · Internal Structural Exam · Drydock Extension
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7402940
27 September 2021 Deficiency Check · COI Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7324441
6 July 2021 In-Service Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7227284
28 May 2021 Deficiency Check · In-Service Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7215413
14 December 2020 In-Service Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7111555
6 October 2020 COI Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 7073703
16 March 2020 Administrative Inspection · Drydock Exam
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6927585
10 January 2020 Administrative Inspection · Deficiency Check
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6887030
9 December 2019 Damage Survey
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6883255
12 June 2019 Administrative Inspection · In-Service Inspection · COI Inspection · Examination of Repairs · DAPI Audit · MTSA Verification
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6706456
25 September 2018 MTSA Verification · COI Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6545751
27 August 2018 Administrative Inspection
Administrative · Navigation Center · Activity 6524185
27 August 2018 In-Service Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6524572
24 July 2018 Administrative Inspection
Administrative · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 6489640
1 May 2018 In-Service Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6403069
13 March 2018 Drydock Exam
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6371098
26 February 2018 Deficiency Check
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6361903
19 September 2017 Administrative Inspection
Administrative · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 6270251
1 September 2017 Administrative Inspection · Deficiency Check
Physical examination · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 6256877
1 September 2017 Deficiency Check
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6269983
30 August 2017 Type not recorded
No type recorded · Sector New York · USCG Northeast District (CGD-NE) · Activity 6255077
30 August 2017 In-Service Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6257101
21 August 2017 COI Inspection · Excursion Permit · MTSA Verification · Administrative Inspection · Examination of Repairs
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6242178
27 July 2017 In-Service Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6214959
19 July 2017 Deficiency Check
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6216197
18 May 2017 Drydock Extension
Administrative · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 6149594
28 February 2017 Drydock Exam · Internal Structural Exam
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 6096375
27 September 2016 Deficiency Check · In-Service Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 6010380
22 August 2016 COI Inspection · MTSA Verification · Excursion Permit
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 5980556
25 May 2016 Excursion Permit
Administrative · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 5886660
22 March 2016 Damage Survey
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 5839078
17 August 2015 MTSA/ISPS Verification · MARPOL Annex I Examination · MARPOL Annex V Examination · Excursion Permit · COI Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 5218440
19 August 2014 COI Inspection · MARPOL Annex V Examination · Excursion Permit · Examination of Repairs · MARPOL Annex I Examination · MTSA/ISPS Verification · Deficiency Check
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 4961258
25 June 2014 In-Service Inspection
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 4922087
16 June 2014 Deficiency Check · Welding Related Inspections Qualification Testing · In-Service Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 4890532
1 December 2011 Administrative Inspection
Administrative · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 4199648
20 September 2011 Administrative Inspection · MARPOL Annex VI Survey · MTSA/ISPS Verification · COI Inspection · Deficiency Check
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 4151814
30 August 2011 In-Service Inspection · Examination of Repairs · Deficiency Check · Excursion Permit
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 4131923
4 August 2011 Examination of Repairs
Physical examination · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 4105911
1 August 2011 Deficiency Check · Damage Survey
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 4101918
5 January 2011 Type not recorded
No type recorded · Sector Boston · USCG Northeast District (CGD-NE) · Activity 3933660
16 September 2010 MARPOL Annex VI Survey · Examination of Repairs · Deficiency Check · Administrative Inspection · MTSA/ISPS Verification · COI Inspection · DAPI Audit
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 3858000
1 September 2010 Administrative Inspection
Administrative · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 3839396
19 March 2009 Deficiency Check · Internal Structural Exam · Drydock Extension
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 3436135
6 January 2009 Administrative Inspection
Administrative · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 3389715
30 September 2008 COI Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 3330368
21 August 2008 Excursion Permit
Administrative · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 3302447
9 July 2008 Construction Oversight
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 3262583
23 March 2008 Type not recorded
No type recorded · Sector Southeastern New England · USCG Northeast District (CGD-NE) · Activity 3184699
24 September 2007 COI Inspection · Deficiency Check
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 3065081
4 June 2007 Hull Examination · Internal Structural Exam
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 2951407
28 March 2007 Deficiency Check
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 2896869
15 March 2007 Administrative Inspection
Administrative · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 2888621
18 September 2006 COI Inspection
Physical examination · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 2734626
31 May 2006 Administrative Inspection
Administrative · Marine Safety Unit Cape Cod · USCG Northeast District (CGD-NE) · Activity 2666544
16 September 2005 Deficiency Check · In-Service Inspection · COI Inspection
Physical examination · MSFO CAPE COD · USCG Northeast District (CGD-NE) · Activity 2493793
9 September 2005 In-Service Inspection
Physical examination · MSFO CAPE COD · USCG Northeast District (CGD-NE) · Activity 2488202
2 August 2005 Security Plan Amendment Review - VSP
Administrative · Marine Safety Center (MSC) · Activity 2448704
20 May 2005 Security Plan Amendment Review - VSP
Administrative · Marine Safety Center (MSC) · Activity 2363429
12 May 2005 Deficiency Check · MTSA/ISPS Verification
Physical examination · MSFO CAPE COD · USCG Northeast District (CGD-NE) · Activity 2350732
3 May 2005 Security Plan Amendment Review - VSP
Administrative · Marine Safety Center (MSC) · Activity 2348224
4 January 2005 Examination of Repairs
Physical examination · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 2268698
1 September 2004 Internal Structural Exam · Hull Examination
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 2190903
26 August 2004 Permit to Proceed
Administrative · MSFO CAPE COD · USCG Northeast District (CGD-NE) · Activity 2179353
7 August 2004 Attraction Vessel Exam
Physical examination · MSFO CAPE COD · USCG Northeast District (CGD-NE) · Activity 2160705
24 June 2004 MTSA/ISPS Verification
Physical examination · Commandant (CG-CVC) · Activity 2109087
22 March 2004 COI Inspection
Physical examination · MSFO CAPE COD · USCG Northeast District (CGD-NE) · Activity 2030478
29 January 2004 Security Plan Review - VSP
Administrative · Marine Safety Center (MSC) · Activity 1996761
14 April 2003 Underwater Inspection in lieu of Drydock
Physical examination · MSFO CAPE COD · USCG Northeast District (CGD-NE) · Activity 1824853
2 April 2003 COI Inspection · MARPOL Annex I Examination · Internal Structural Exam · Construction Oversight · Examination of Repairs
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1700590
14 August 2002 Type not recorded
No type recorded · MSO PROVIDENCE · USCG Northeast District (CGD-NE) · Activity 1661481
8 May 2001 Deficiency Check
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1063693
20 February 2001 Deficiency Check
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1058073
12 October 2000 Type not recorded
No type recorded · MSO PROVIDENCE · USCG Northeast District (CGD-NE) · Activity 823561
14 July 2000 Administrative
Administrative · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1051795
5 May 2000 Deficiency Check
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 818139
3 December 1999 Hull Examination
Physical examination · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1463537
25 October 1999 COI Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1397260
25 November 1998 Re-Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 805861
12 November 1997 Type not recorded
No type recorded · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 35305
10 November 1997 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1111385
23 October 1997 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 777402
1 October 1997 Deficiency Check · COI Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1368436
25 September 1997 Hull Examination
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1378192
14 April 1997 Administrative
Administrative · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1092697
8 April 1997 Examination of Repairs
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1104756
28 March 1997 Type not recorded
No type recorded · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1096242
7 November 1996 Type not recorded
No type recorded · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1170612
21 June 1996 Examination of Repairs
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1390373
2 April 1996 COI Inspection
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1422658
7 March 1996 Type not recorded
No type recorded · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1078523
23 February 1996 Type not recorded
No type recorded · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 885078
2 November 1994 Administrative
Administrative · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1175594
8 August 1994 Administrative
Administrative · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 866452
1 June 1994 Re-Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 852717
23 March 1993 Deficiency Check
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1148493
19 March 1993 Deficiency Check
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1448416
26 February 1993 Deficiency Check
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1463038
22 January 1993 Deficiency Check
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1447209
17 December 1992 Hull Examination · COI Inspection · Examination of Repairs
Physical examination · MSO PORTLAND, OREGON · USCG Northwest District (CGD-NW) · Activity 1356162
14 February 1992 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 961919
6 February 1992 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 955493
17 December 1991 Deficiency Check
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 953211
22 October 1991 Type not recorded
No type recorded · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1245831
16 September 1991 COI Inspection
Physical examination · MSO WILMINGTON · USCG East District (CGD-E) · Activity 1244502
31 July 1991 Type not recorded
No type recorded · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1251190
23 July 1991 Type not recorded
No type recorded · MSO WILMINGTON · USCG East District (CGD-E) · Activity 528240
2 July 1991 Type not recorded
No type recorded · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1002427
7 May 1991 Hull Examination
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 922877
22 March 1991 Type not recorded
No type recorded · MSO WILMINGTON · USCG East District (CGD-E) · Activity 500618
31 December 1990 Type not recorded
No type recorded · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1226339
6 December 1990 Type not recorded
No type recorded · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 924651
8 September 1990 Type not recorded
No type recorded · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 929584
9 August 1990 Re-Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1213030
10 January 1990 Type not recorded
No type recorded · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 910422
18 July 1989 COI Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 890808
17 March 1989 COI Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1041627
11 February 1988 Re-Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1021822
9 March 1987 Deficiency Check
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1320272
27 February 1987 Deficiency Check
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1312671
5 February 1987 COI Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1011452
13 May 1986 Credit Drydock
Administrative · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 987089
13 May 1986 Examination of Repairs
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 988302
8 March 1986 Type not recorded
No type recorded · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 440346
18 June 1985 Type not recorded
No type recorded · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 982386
4 June 1985 Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1289562
17 May 1985 Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 979565
4 February 1985 Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1285902
25 January 1985 Type not recorded
No type recorded · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 974895
23 January 1985 Type not recorded
No type recorded · MSO PORT ARTHUR · USCG Heartland District (CGD-H) · Activity 978268
4 September 1984 Type not recorded
No type recorded · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 975878
19 March 1984 Type not recorded
No type recorded · MSU GALVESTON · USCG Heartland District (CGD-H) · Activity 1280593
9 November 1983 Type not recorded
No type recorded · MIO HOUSTON · USCG Heartland District (CGD-H) · Activity 1276604
8 August 1983 Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 967296
21 January 1983 Type not recorded
No type recorded · MIO HOUSTON · USCG Heartland District (CGD-H) · Activity 1276534
14 October 1982 Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1277033
19 July 1982 Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 968351
21 April 1982 Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 963543
12 February 1981 Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 967871

Deficiency record · 227

11 - Life Saving Appliances › N/A - No Subsystem › Rescue boats
Issued 19 April 2024 Resolved
Cargo ships shall carry at least one rescue boat complying with the requirements of section 5.1 of the Code. The rescue boat has a crack IVO the keel. Temporary repairs are authorized, permanent repairs to be conducted at next dockside availability. Permanent repairs to be made to the satisfaction of the attending Marine Inspector.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 19 April 2025
Resolved 6 May 2024
Resolution: Permanent repairs completed.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 19 April 2024 No resolution recorded
The fire integrity of the divisions shall be maintained at openings and penetrations. The Officer Laundry, Aft upper, door casing is misaligned, cannot be closed properly. Vessel to overhaul and provide closure to meet the regulation at next drydock.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 19 April 2026 — due date passed with no resolution recorded
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 19 April 2024 Resolved
Stairways and lift trunks which penetrate more than a single deck shall be surrounded by at least "A-0" class divisions and be protected by self-closing doors at all levels. Numerous stair tower self-closing doors need adjustments to ensure they close even under any supplied ventilation.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 May 2024
Resolved 6 May 2024
Resolution: FSD have been adjusted and close properly.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 19 April 2024 No resolution recorded
Metallic band strapping used for cable support should be steel and corrosion treated if not a corrosion-resistant material. Cable retention devices should be installed not less than every 610 mm on vertical runs and not less than every 2.5 m on horizontal runs. Vertical wire runs in the machinery space noted for plastic zip-tie type fasteners. Provide metallic IAW with regulation.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 May 2024 — due date passed with no resolution recorded
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 19 April 2024 No resolution recorded
Exhaust ducts from laundries and drying rooms of category (13) spaces as defined in paragraph 2.2.3.2.2 shall be fitted with: suitably located hatches for inspection and cleaning. The dryer exhausts in the Officer laundry are of vertical installation. Process for scheduled clean/inspection to be implemented to the satisfaction of the attending Marine Inspector.
Condition: Damaged By Earlier Event
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 May 2024 — due date passed with no resolution recorded
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 19 April 2024 Resolved
The purpose of this regulation is to limit the fire growth potential in every space of the ship ...The purpose of this regulation is to limit the fire growth potential in every space of the ship. Vessel had high alcohol content hand sanitizer being stored in linen closest. Relocated all flammable products to the appropriate storage.
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 3 May 2024
Resolved 6 May 2024
Resolution: Sanitizer has been relocated to a CO2 protected space.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 14 December 2022 Resolved
Complete underway testing of the main turbine low lube oil trip, and overspeed trip. Provide objective evidence of completion to the CGMI to include statement from the Chief Engineer, License number and signature.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 11 January 2023
Resolution: Received a letter from the KENNEDY's Chief Engineer attesting to the completion of the required tests. Letter has been uploaded into vessel documents.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 14 December 2022 Resolved
MSC Letter E2-1904271 directed the submittal of Periodic Safety Test Procedures for the alarm and monitoring system upgrade in accordance with 46 CFR 61.40. Submit PSTP to the Marine Safety Center for approval and provide approval documentation to the local OCMI.
Action required: 705 - Other - as specified
Due 5 February 2023
Resolved 30 May 2023
Resolution: See Activity Number 7700941
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 14 December 2022 Resolved
PSTP for Burner Management and Combustion Control, Rev. 7 is Not Approved by the USCG. Further more MSC Letter E2-1704764 for Rev. 6 was returned for revision. Submit ICI Doc No: TSK 800-03, Rev. 7, "Burner Management and Combustion Control System Periodic Safety Test Procedure", dated 07JAN2018 or most current version witnessed by a Coast Guard Marine Inspector to the Marine Safety Center for approval and provide approval documentation to the local OCMI.
Action required: 705 - Other - as specified
Due 5 February 2023
Resolved 30 May 2023
Resolution: See Activity Number 7700941
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 14 December 2022 Resolved
Number one main feed / coffin pump has high vibration alarm. Upon investigation the pump will need to be rebuilt due to water in oil, Tech rep onsite. Complete repairs and test to the satisfaction of the Coast Guard Marine Inspector (CGMI).
Action required: 10 - Deficiency Rectified
Resolved 6 January 2023
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 14 December 2022 Resolved
Piping, Including Flanges, conveying vapors, gases or liquids whose temperature exceeds 150'F shall be suitably insulated where necessary to preclude injury to personnel. Multiple areas of missing or damaged insulation. Replace or repair insulation on all piping systems that exceed 150'F to the satisfaction of the CGMI.
Action required: 10 - Deficiency Rectified
Resolved 6 January 2023
01 - Certificates & Documentation › 012 - Crew Certificates › Evidence of Basic Training
Issued 28 November 2022 Resolved
Onboard a seagoing vessel to which this subpart applies, no person may assign any person to perform shipboard duties, and no person may perform those duties, unless the person performing them has received - (1) Training in personal survival techniques as set out in the standard of competence under Regulation VI/1 of the STCW Convention (incorporated by reference, see § 15.103 of this part); or (2) Sufficient familiarization training or instruction. two OS and 3 other crew did not have STCW endorsement. Replacements were brought on board for OS.
Condition: Invalid
Action required: 10 - Deficiency Rectified
Resolved 28 November 2022
Resolution: Replacements were brought on board for OS.
02 - Structural Conditions › N/A - No Subsystem › Bulkheads - cracking
Issued 23 February 2022 Resolved
If, during an internal structural examination, damage or deterioration to the hull plating or structural members is discovered, the OCMI may require the vessel to be drydocked. Diesel fuel was disovered in the port side cofferdam hotwell.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 4 March 2022
Resolution: Completed successful pressure testing of cofferdam hotwell tank at 2 lbs. No leak discovered.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-op. damage
Issued 23 February 2022 Resolved
If, during an internal structural examination, damage or deterioration to the hull plating or structural members is discovered, the OCMI may require the vessel to be drydocked. Deflection of 05 bulkheads, as well as minor cracking near the top longitudinals as a result, was discovered in the #6 Port side Dry Ballast tank. Must be repaired at vessel's next drydock.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 28 November 2022
Resolution: Repairs were completed
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-corrosion
Issued 23 February 2022 Resolved
If, during an internal structural examination, damage or deterioration to the hull plating or structural members is discovered, the OCMI may require the vessel to be drydocked. A cracked weld was discovered in Port Side Dry Ballast tank #6 at frame 155, at the 3rd longitudinal inboard, roughly 7 feet inboard of the tank inner wall. Must be repaired at vessel's next drydock.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 28 November 2022
Resolution: Repairs were completed
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 27 September 2021 Resolved
“E” lighting signage is missing throughout the vessel. Apply the appropriate signage as per 46 CFR 131.840
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 December 2021
Resolved 4 January 2022
Resolution: Appropriate signage verified.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 8 October 2020 Resolved
PSTPs shall be conducted PTCP
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 31 December 2020
Resolved 4 June 2021
Resolution: Test procedures were conducted wih no issues found
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 8 October 2020 Resolved
Vessel must conduct MOB, Fire and Abandon ship and security drills.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 31 December 2020
Resolved 28 May 2021
Resolution: All drills were sat
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 8 October 2020 Resolved
Operationally test engineering equipment to include, SSTGs, Safety valve easing gear and safety valves.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Due 31 December 2020
Resolved 28 May 2021
Resolution: ALl tests were completed satisfactory
02 - Structural Conditions › N/A - No Subsystem › Decks - corrosion
Issued 9 December 2019 Resolved
Aft peak tank top plating for the upper tween deck and fwd peak chain locker sump bottom #1 & #2 breast hooks plating gauging indicates remaining thickness in localized areas does not meet ABS rules. The aft peak upper tween tank top was found to be over 30% wastage, which is conidered excessive allowable limits.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 29 February 2020
Resolved 10 June 2020
Resolution: cleared to satisfaction of attending marine inspector.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 28 November 2018 Resolved
Vessel must complete a fire and abandonship drill with vessel crew and cadets prior to getting underway.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 28 November 2018
Resolved 11 January 2019
Resolution: Witnessed a security drill, fire drill, and abandonship drill.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 28 November 2018 Resolved
Vessel must demonstrate PSTPs for both main boilers, steam turbines, SSTGs, and Aux Generator.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 28 November 2018
Resolved 9 January 2019
Resolution: Witnessed PSTPs for main boilers, SSTGs, and Aux generator in AMR space.
01 - Certificates & Documentation › 012 - Crew Certificates › Certificates for master and officers
Issued 28 November 2018 Resolved
Vessel must provide licenses and documents for ship's crew.
Condition: Invalid
Action required: 60 - Rectify deficiencies prior to movement
Due 28 November 2018
Resolved 11 January 2019
Resolution: Inspected crew licenses and TWICs.
14 - Pollution Prevention › 141 - MARPOL Annex I › Oil discharge monitoring and control system
Issued 25 September 2018 Resolved
Vessel must demonstrate ship's OWS.
Condition: Invalid
Action required: 60 - Rectify deficiencies prior to movement
Due 28 November 2018
Resolved 28 December 2018
Resolution: Witnessed testing of the OWS.
10 - Safety of Navigation › N/A - No Subsystem › Automatic Identification System (AIS)
Issued 27 August 2018 Resolved
Vsl is broadcasting: NAME with Vsl type precursor (NAME must not include Vsl type precursors, e.g. F/V, M/V).
Condition: Invalid
Action required: 705 - Other - as specified
Due 27 September 2018
Resolved 11 January 2019
Resolution: Vessel corrected AIS to broadcast just the vessel's name with no precursor.
Lifesaving › Launching Appliances › Falls
Issued 19 September 2017 Resolved
Renew falls for LB/RB #5, LB/RB #6, and FASS/FSR at next dry-dock NLT 31 March 2018. Not to exceed 5 years from 13 SEP 2013.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 31 March 2018
Resolved 12 January 2018
Resolution: Vessel replaced the falls for LBs #5 and #6 along with the rescue boat.
Electrical › Electric Generation Source (service) › Generator
Issued 30 August 2017 Resolved
Auto regulator on #2 steam turbine generator failed.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 5 September 2017
Resolved 1 September 2017
Resolution: Vessel replaced the faulty voltage regulator with an in-kind replacement. Following replacement, the turbo generator online and tested the regulator by adding and shedding load. The voltage regulator responded satisfactorily.
Engineering › Steam Boiler (propulsion) › Fuel Oil Burner
Issued 21 August 2017 Resolved
Tag out LSMGO system for both boilers. In addition, install new and approved fuel oil hoses for the LSMGO burner front. Test system with USCG prior to putting new system in service.
Condition: Invalid
Action required: 705 - Other - as specified
Due 25 February 2018
Resolved 26 February 2018
Resolution: Verified vessel installed new, approved metallic fuel hoses.
Stability › Watertight Integrity › Watertight Subdivision Standard
Issued 6 January 2017 Resolved
The class III sliding watertight door located between # and #4 hold has small hydraulic weep within the hydraulic cylinder behind the bulkhead. The bulkhead will need to be removed to identify the exact location of the weep. ABS, CG, and MARAD Rep are confident the door still operates as designed; however, it needs to be corrected. Vessel is to provide a corrective action to the CG.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 March 2017
Resolved 19 July 2017
Resolution: Vessel was able to repair the class III watertight door leak and demostrated to CG; all sat.
Accommodation/Occupational Safety › Ventilation › General
Issued 6 January 2017 Resolved
The portside supply fan flex joint coupling is wasted. Repair or replace during credit drydock.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 March 2017
Resolved 27 August 2018
Resolution: Vessel replaced portside supply fan flex joint coupling with a new one.
Fire Fighting › Fire Hoses › Condition
Issued 27 September 2016 Resolved
Hydrostatically test 73 (43 1.5" and 30 2.5") fire hoses in the presence of a CG Marine Inspector. Prior to getting U/W.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 September 2016
Resolved 11 October 2016
Resolution: Witness Hydrostatically testing of 73 (43 1.5" and 30 2.5") fire hoses; all sat.
Fire Fighting › Portable CO2 Fire Extinguisher › Service
Issued 27 September 2016 Resolved
Service fixed fire fighting system, semi-portable systems, and portable extinguishers prior to getting U/W.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 September 2016
Resolved 3 January 2017
Resolution: Vessel provided servicing reports for the vessel's portable, semi-portable, and fixed fire fighting extiguishers; all sat.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 27 September 2016 Resolved
Demonstrate fixed system C02 time delay to the satisfaction of a CG Marine Inspector. Prior to getting u/w.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 September 2016
Resolved 3 January 2017
Resolution: Vessel demostrated the fixed CO2 fire fighting time delays to the Coast Guard; all sat.
Lifesaving › Lifeboat › Propulsion Engine
Issued 25 May 2016 Resolved
Lifeboat #6 does not function/operate as designed. Reduced overall passenger count by the amount #6 lifeboat is designed to carry.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 9 September 2016
Resolved 30 August 2016
Resolution: The engine for lifeboat #6 was tested; all sat.
Engineering › Steam Turbine (propulsion) › Casing
Issued 22 March 2016 Resolved
Several cracks found in casing.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Resolved 1 April 2016
Resolution: Vessel will conduct annual boroscope inspections on LPT with ABS, CG and MARAD.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 29 September 2015 Resolved
AMR spac delay failed the test.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 September 2015
Resolution: Deay has been repaired.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Piping
Issued 29 September 2015 Resolved
Stanchion base fwd of hawse pipes middle was wasted.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 September 2015
Resolution: Vessel replaced middle stanchion.
Fire Fighting › Ventilation Systems › Ducts
Issued 23 September 2015 Resolved
Supply ventialtion automatic damper in EDG space would not close when EDG was shutdown.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 September 2015
Resolution: Venitlation was tested satisfactory.
Fire Fighting › Automatic Sprinkler System › Testing Switches (Alarm/Sprinklers)
Issued 23 September 2015 Resolved
rate and rise of heat actuator not functioning in battery.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 September 2015
Resolution: rep rectified heat actuator.
Fire Fighting › Ventilation Systems › Ventilation Fire Dampers
Issued 23 September 2015 Resolved
venilation dampers not functioning in the UPS room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 September 2015
Resolution: vessel rectified ventialtion dampers.
Deck/Cargo › Towing › Chocks
Issued 23 September 2015 Resolved
Renewe stanchion base fwd of hawse pipe middle stanchion.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 September 2015
Resolution: Vessel repaired stanchion.
Engineering › Diesel Engine (auxiliary) › Overspeed Device
Issued 24 August 2015 Resolved
LED light did not illuminate when test was conducted nor did the alarm activate.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 24 August 2015
Resolution: Vessel fixed electronics and alarm for over speed.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 23 August 2015 Resolved
AMR and OIL transfer delays failed.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 29 August 2015
Resolution: Vessel rectified delays,
Navigation › Collision/Grounding Avoidance › Radar
Issued 18 August 2015 Resolved
3m Radar was not integrated with AIS.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 24 August 2015
Resolution: 3m radar has now been intergrated with AIS.
Electrical › Electric Generation Source (service) › Circuit Breaker
Issued 18 August 2015 Resolved
The switch board panel is missing a blank.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 24 August 2015
Resolution: Vessel installed a blank in the switch board panel.
Fire Fighting › Structural - A Class Divisions › Doors
Issued 17 August 2015 Resolved
the engine room door displayed a yellow light kighlighting a failure.
Action required: 705 - Other - as specified
Resolved 24 August 2015
Resolution: Engine room door display has been rectified.
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 17 August 2015 Resolved
Ring buoy lights batteries have expired.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 24 August 2015
Resolution: Vessel replaced batteries in water lights.
Lifesaving › Embarkation Appliances/Stations › Accessability
Issued 17 August 2015 Resolved
The embarkation lighting is out in several areas.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 24 August 2015
Resolution: Vessel replaced lights.
Lifesaving › Lifeboat › Propulsion Starting System
Issued 17 August 2015 Resolved
life boat #1 battery is dead.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 24 August 2015
Resolution: Vessel charged battery.
Lifesaving › Rescue Boat Equipment › Instructions (engine start/operation)
Issued 17 August 2015 Resolved
Multiple items were missing from rescue boat.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 24 August 2015
Resolution: Vessel repalced items that were missing from rescue boat.
Lifesaving › Lifebuoys › Self-Activitating Smoke Signals
Issued 17 August 2015 Resolved
Orange smoke on ring buoy is not CG approved.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 24 August 2015
Resolution: Vessel replced smoke with CG approved design smoke.
Fire Fighting › Fire Hydrants › Condition
Issued 17 August 2015 Resolved
#1 fire pump does not work in remote operation.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 24 August 2015
Resolution: Vessel fixed electrical controls for local and remote control of the #1 Fire pump.
Engineering › Steam Boiler (propulsion) › Superheater
Issued 17 August 2015 Resolved
Steam pipe in super heater escaping through a pin hole leak.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 24 August 2015
Resolution: Vessel rep installed a doubler over the pin hole leak.
Engineering › Steam Boiler (propulsion) › Automation Equipment
Issued 17 August 2015 Resolved
Conduct PSTP using approved PSTP rev 5.
Condition: Invalid
Action required: 705 - Other - as specified
Resolved 8 January 2016
Resolution: COnducted PSTP using Rev 5 satisfactory.
Communications › Public Address System › Loudspeaker
Issued 22 November 2011 Resolved
Prove proper operation of public address speakers in list provided to [name withheld].
Action required: 705 - Other - as specified
Resolved 27 December 2011
Resolution: All speakers operational. Deficiency cleared.
Engineering › Steam Boiler (propulsion) › Automation Equipment
Issued 20 September 2011 Resolved
Complete DVTP/FMEA & PSTP revision & documentation process for Boiler Burner Management/Combustion Control systems, to wit: Inclusion of field changes to FMEA & test procedures; Addition of summary indicator audible/visual alarm for loss of PLC output control; Resubmission of FMEA & test documentation with changes to OCMI & MSC for verification & final approval.
Action required: 705 - Other - as specified
Due 13 January 2013
Resolved 9 January 2013
Resolution: Testing completed. PSTP Rev04 submitted to [name withheld] for review & approval
Fire Fighting › Structural - A Class Divisions › Service Spaces
Issued 20 September 2011 Resolved
Prove proper operation of UPS room ventilation damper closure caused by under/low voltage to vent damper control circuit . Provide prior to end of scheduled dry-dock.
Action required: 705 - Other - as specified
Due 30 May 2012
Resolved 6 July 2012
Electrical › Lighting (emergency) › Lighting Fixture
Issued 23 December 2010 Resolved
Correct emergency lighting fixtures and/or labels in the attached list.
Action required: 705 - Other - as specified
Due 1 July 2011
Resolved 31 August 2011
Lifesaving › Lifeboat › Embarkation/Disembarkation Capabilities
Issued 5 November 2010 Resolved
Replace damaged stanchion on starboard aft quarter of lifeboat #5
Action required: 705 - Other - as specified
Resolved 6 December 2010
Resolution: New stanchion was replaced. Deficiency cleared.
Stability › Weathertight Integrity › General
Issued 27 October 2010 Resolved
Repair light/leaks in cargo hatches as identified with vessel representatives.
Action required: 705 - Other - as specified
Resolved 23 December 2010
Resolution: Gasket tested with water. Deficiency cleared.
Operations/Management › Lifesaving › Op Readiness/Maintenance/Inspection
Issued 27 October 2010 Resolved
Conduct maintenance, documentation and operational testing of all lifeboats IAW 46 CFR 167.35-1 and 46 CFR 199.190.
Action required: 705 - Other - as specified
Resolved 13 December 2010
Resolution: Reviwed lifesaving log. All lifeboats were opearated in the davits for propulsion and steering. Provisions were spot checked in each. Deficiency cleared.
Fire Fighting › Automatic Sprinkler System › Testing Means for Pump
Issued 27 October 2010 Resolved
Conduct satisfactory PMS and testing IAW NFPA 25 on the automatic sprinkler pump.
Action required: 705 - Other - as specified
Due 6 January 2011
Resolved 7 January 2011
Resolution: Pump will be churned and documented in the engineer''s log book.
Documentation › Markings/Placards › Warning Signs
Issued 27 October 2010 Resolved
Provide missing instruction placards for manual operation in the quarterdeck cabinet.
Action required: 705 - Other - as specified
Resolved 3 January 2011
Stability › Weathertight Integrity › General
Issued 16 September 2010 Resolved
Conduct chalk tests to the engine room hatch on port side and two vents on starboard forward main deck.
Action required: 705 - Other - as specified
Resolved 13 December 2010
Resolution: Engine room hatch and two vents on starboard side of main deck were chalk tested satisfactorily. Deficiency cleared.
Stability › Watertight Integrity › General
Issued 16 September 2010 Resolved
Properly repair the open/close indicator light on the #140 Upper 'tween sliding watertight door.
Action required: 705 - Other - as specified
Resolved 6 December 2010
Resolution: Indicator light operating properly. Deficiency cleared.
Lifesaving › Lifeboat › Propulsion Starting System
Issued 16 September 2010 Resolved
Replace batteries on the #7 lifeboat or demonstrate satisfactory operation (maintain a charge).
Action required: 705 - Other - as specified
Resolved 13 December 2010
Resolution: Lifeboat was tested in the davits. Deficiency cleared.
Fire Fighting › Automatic Sprinkler System › Pump
Issued 16 September 2010 Resolved
Make permanent repairs to sprinkler pump packing gland fasteners. A licensed engineer is to perform daily examination of packing gland retaining bolts to ensure they remain tight and have not shifted.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 July 2011
Resolved 1 August 2011
Resolution: Witnessed operation of newly installed pump. Deficiency cleared.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 16 September 2010 Resolved
Provide a automatic CO2 activated pressure switch to secure the F/O transfer pump upon activation of the CO2 fixed firefighting system
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 July 2011
Resolved 13 December 2011
Resolution: Tested CO2 activated pressure switch. Deficiency cleared.
Fire Fighting › Structural - A Class Divisions › Machinery Spaces
Issued 16 September 2010 Resolved
Provide approved plans, and address SFP for EGEN Space; existing steel door not rated/ not self closing, ventilation trunk no damper, bulkhead insulation. (door is orig construction, ventilation new install and insulation new install 2003 (voluntary SOLAS p/MARAD).
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 July 2011
Resolved 4 January 2012
Fire Fighting › Structural - A Class Divisions › Service Spaces
Issued 16 September 2010 Resolved
Provide approved plans, and address SFP for UPS Space : ventilation trunk no damper, bulkhead insulation, ventilation /cooling not adequate for space heat dissipation.(Installed in 2003 voluntary SOLAS p/MARAD).
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 July 2011
Resolved 4 January 2012
Fire Fighting › Structural - A Class Divisions › Control Stations
Issued 16 September 2010 Resolved
Provide "A" class door between chart room/bridge and corridor, as depicted on FCP.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 July 2011
Resolved 31 August 2011
Construction/Loadline › Structures › Transverse Bulkhead
Issued 19 March 2009 Resolved
Transverse bulkhead frame 42, pinhole fuel oil leak in oil tight collar. 2nd tank top long outboard of inboard long bulkhead. Cause appears to be start stop of weldment when installed.
Condition: Design Flaw
Action required: 17 - Rectify deficiencies prior to departure
Due 1 April 2009
Resolved 15 December 2009
Resolution: Leak temporarily repaired. Permanent repair to be completed next dry-dock
Stability › Watertight Integrity › General
Issued 8 January 2009 Resolved
Submit proposal for permanent repairs for the wasted area on Focsle deck IWO port anchor windlass.
Condition: Unknown
Action required: 705 - Other - as specified
Due 15 March 2009
Resolved 15 December 2009
Resolution: Proposal submitted, permanent repairs to be completed during next dry-dock.
Documentation › Certificates/Documents › Cargo Ship Safety Radio Certificate
Issued 8 January 2009 Resolved
Ensure all vessel documents reflect name change of vessel.
Action required: 705 - Other - as specified
Due 1 March 2009
Resolved 15 December 2009
Accommodation/Occupational Safety › Occupational Safety › Rubbish/Waste Materials
Issued 8 January 2009 Resolved
Ensure vessel is fully secured for sea.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 9 January 2009
Resolution: Vsl secured for sea.
Operations/Management › Drug and Alcohol Testing › EAP Display Requirements
Issued 30 September 2008 Resolved
Ensure EAP is fully implemetned onboard vessel (training/signage).
Action required: 705 - Other - as specified
Due 15 January 2009
Resolved 15 December 2009
Engineering › Steam Boiler (propulsion) › Blowdown System
Issued 9 July 2008 Resolved
Prior to lighting fires in ships boilers a NDT of all 12 header drains inside these boilers shall be performed and all necessary repairs made to satisfaction of USCG Marine Inspector.
Condition: Unknown
Action required: 701 - Prior to carriage of passengers/cargo
Due 9 July 2008
Resolved 25 July 2008
Resolution: NDT complete. Visual inspection conducted of all drains. New CG 835 issued for repairs.
Engineering › Steam Boiler (propulsion) › Blowdown System
Issued 9 July 2008 Resolved
Make permanent repair proposla to USCG Sector SENE which addresses permanent correcive actions to be taken to rectify the corroded conditions found on stbd boiler superheater inlet drain adn fwd watewall header drain and port boiler fwd sidewall header drain. This repair proposal and rpairs must be accomplished to the USCG satisfaction prior to lighting fires in these boilers.
Action required: 705 - Other - as specified
Resolved 16 August 2008
Resolution: Repair proposal submitted and approved. Repairs made and tested satisfactory.
Fire Fighting › Structural - A Class Divisions › Machinery Spaces
Issued 15 March 2007 Resolved
The remote controlled motor operated ventilation supply damper for the Oil Handling Room does not work. As such, there shall be no fuel oil or lube oil processing and/or handling operations in this space until permanent repairs have been made to this damper assembly to the satisfaction of an attending USCG Marine Inspector.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 15 March 2007
Resolved 25 September 2007
Resolution: Corrected this date.
Deck/Cargo › Cargo Transfer (solid) › General
Issued 15 March 2007 Resolved
The vessel's cargo gear shall be placed in an out of commission status and shall not be operated until such time as a Cargo Gear Certificate has been issued to the ship upon completion of satisfactory permanent repairs to same.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 March 2007
Resolved 8 December 2007
Resolution: ABS has isued a cargo gear certificate this date.
Fire Fighting › Ventilation Systems › Operating Controls
Issued 12 January 2007 Resolved
Remote motor operated ventilation supply damper for Oil Handling Room does not work. Manual damper to be employed at upper boat deck until repairs have been made but no later than March 15, 2007.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 15 March 2007
Resolved 15 March 2007
Resolution: The remote controlled motor operated ventilation supply damper for the Oil Handling Room does not work. As such, there shall be no fuel oil or lube oil processing and/or handling operations in this space until permanent repairs have been made to this dam
Deck/Cargo › Cargo Transfer (solid) › General
Issued 12 January 2007 Resolved
Cargo gear certificate is not issued due to no weight test being performed after major overhaul during dockside availblity of 2006. Cargo gear not to be operated until such certificate is produced.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 12 January 2007
Resolved 15 March 2007
Resolution: The vessel''s cargo gear shall be placed in an out of commission status and shall not be operated until such time as a Cargo Gear Certificate has been issued to the ship upon completion of satisfactory permanent repairs to same.
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 12 October 2006 Resolved
Greater than 20 main vertical zone fire screen doors were found to be tied open, blocked open with wooden wedges, and otherwise physically obstructed during COI exam. Ship's master to address situation with ship wide policy note NLT Friday October 13, 2006.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 13 October 2006
Resolved 8 November 2006
Resolution: Corected this date
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 12 October 2006 Resolved
18 Fire screen doors noted to be inoperative as discussed in Activity # 2734626. Permanent repairs to these doors shall be accomplished prior to embarking passengers to satisfaction of USCG.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 12 October 2006
Resolved 11 January 2007
Resolution: Completed this date
Communications › Alarms/Indicators › Engineers' Assistance-needed Alarm
Issued 12 October 2006 Resolved
General Alarm contactor is being used as Engineer [name withheld] contactor in lower level of engine room. replace improper contactor with correct unit prior to being placed in service to satisfaction of USCG.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 12 October 2006
Resolved 8 November 2006
Resolution: Corrected this date
Engineering › Steam Turbine (propulsion) › Casing
Issued 12 October 2006 Resolved
Numerous coffee cans were noted hung under bearing journal caps on main reduction gear fwd casing on lower level in engine room. Remove fire hazards created by these cans, fix the leaks and demonstrate to USCG satisfactory conditions upon completion of this job and prior to starting turbine on steam.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 12 October 2006
Resolved 8 November 2006
Resolution: Corrected this date
Electrical › Electric Generation Source (emergency) › Generator
Issued 12 October 2006 Resolved
Emergency Generator found with an intermittent "failure to start" problem. This shall be trouble shot by qualified personnel and rectified prior to departing to sea to the satisfaction of an attending USCG inspector.
Condition: Unknown
Action required: 705 - Other - as specified
Due 12 October 2006
Resolved 7 December 2006
Resolution: Resolved this date
Fire Fighting › Automatic Sprinkler System › Connection to Fire Main
Issued 29 September 2006 Resolved
The vessel's "Nav Lab" sprinkler system Marine Safety Center approval remains outstanding this date. This space shall remain unoccupied AND this sprinkler system is NOT to be tied into the remainder of the ship's system until such time as this approval is received from the USCG Marine Safety Center.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 29 September 2006
Resolved 13 October 2006
Fire Fighting › Fire Main › Condition
Issued 18 September 2006 Resolved
Ship's crew shall rig and prove a satisfactory secondary means of fire main supply from the ship's pier. The ship currently does not have 2 operational fire pumps as required by 46 CFR 167.45-5(c)(1). This secondary source of fire main shall be independent of any potable water supply and solely dedicated to the fire main of the vessel.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 29 September 2006
Resolved 7 December 2006
Resolution: Resolved this date
Fire Fighting › Automatic Sprinkler System › Sprinklers
Issued 18 September 2006 Resolved
The vessel's "Nav Lab" sprinkler system Marine Safety Center approval remains outstanding this date. This space shall remain unoccupied AND this sprinkler system is NOT to be tied into the remainder of the ship's system until such time as this approval is received from the USCG Marine Safety Center.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 28 September 2006
Resolved 7 December 2006
Resolution: Resolved this date
Fire Fighting › Fire Pumps › Power Source
Issued 18 September 2006 Resolved
Ship's crew shall rig and prove a satisfactory secondary means of fire main supply from the ship's pier that will serve as the vessel's second required fire pump as the ship currently does not have 2 operational fire pumps as required by 46 CFR 167.45-5(c)(1).
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Resolved 29 September 2006
Fire Fighting › Miscellaneous Items › Paint/Flammable Liquid Lockers
Issued 18 September 2006 Resolved
4 Light fixtures found to be not explosion-proof as required in the aft paint locker. This to be corected prior touse to satisfaction of USCG.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 31 December 2006
Resolved 8 December 2006
Resolution: Completed this date
Engineering › Steam Turbine (propulsion) › Valve, Regulating
Issued 18 September 2006 Resolved
Chief Engineer to provide a written affadavit attesting to the satisfactory operational testing of the vessels main unit overspeed limiting device within the first 72 hours of underway operations.
Action required: 705 - Other - as specified
Due 12 January 2007
Resolved 14 January 2007
Resolution: Completed this date
Fire Fighting › Fixed Fire Detection System › Control Panel
Issued 18 September 2006 Resolved
New sprinkler system zone does not accurately reflect ont he fire control panel on the bridge when tested. This system to be reprogrammed prior to the vessel sailing on it's upcoming cadet cruise.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 11 January 2007
Resolved 12 January 2007
Resolution: Completed this date
Lifesaving › Lifeboat › Carriage Requirement
Issued 13 December 2005 Resolved
For sea-trial purposes only, vessel may reduce lifeboat capacity provided that crew & persons in addition to crew do not exceed aggregate life boat capacity. Reduced life boat carriage requirement is allowed to expedite the completion of item #24 of 21OCT05.
Due 31 December 2005
Resolved 28 December 2005
Resolution: Sea Trails completed. All life saving appliances installed as per COI.
Fire Fighting › Fire Main › Material
Issued 13 December 2005 Resolved
Prior to sailing with cadets, replace pipe elbow (in way of temporary repair) on discharge side of newly installed fire pump.
Due 31 December 2005
Resolved 11 January 2006
Electrical › Electric Generation Source (service) › Panelboard
Issued 13 December 2005 Resolved
Prior to sailing with cadets repair frequency (cycle) meter on main board.
Due 31 December 2005
Resolved 11 January 2006
Engineering › Pressure Vessel › Piping
Issued 13 December 2005 Resolved
Prior to sailing with cadets, provide proof of hydrostatic testing of all new ship service air piping to 1.5 times MAWP.
Due 31 December 2005
Resolved 11 January 2006
Engineering › Pressure Vessel › Marking and Stamping
Issued 13 December 2005 Resolved
Submit for approval, the design and installation plans for the newly installed ship service air compressor and associated piping to USCG marine safety center.
Condition: Unknown
Due 1 February 2006
Resolved 28 September 2006
Resolution: MSC letter comments satisfactorily addressed this date.
Fire Fighting › Fire Pumps › Arrangement
Issued 13 December 2005 Resolved
Submit for approval, change specifications and installation details of newly installed electric fire pump that replaced steam driven pump.
Condition: Unknown
Due 1 February 2006
Resolved 28 September 2006
Resolution: MSC letter comments satisfactorily addressed this date.
Lifesaving › Launching Appliances › Release Mechanism
Issued 21 October 2005 Resolved
Lifeboat #1 and #5 found with damaged or inoperative releasing gear. Both boats are to be repaired and demonstrated to be fully operational prior to the vessel sailing with cadets.
Condition: Unknown
Due 31 December 2005
Resolved 28 December 2005
Resolution: Life Boat testing completed sat on #1 and #5 life boats. All operational testing completed sat.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 16 September 2005 Resolved
AMR CO2 system emergency shutdown pressure switches (2) did not work when testing system. Switches as follows; Ventilation, FSD closures, WTD controllers. 46CFR/76.15
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 18 October 2005
Resolution: Verified as corrected this date.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 16 September 2005 Resolved
60 second time delay for AMR did not work when tested. Renew and retest. 46CFR/76.15-30
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 2 November 2005
Resolution: Firex servicing report received this date showing replacement of subject time delay with new unit.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 16 September 2005 Resolved
Audible alarms for AMR space and control room did not work when tested. Renew and retest. 46CFR/167.45
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 18 October 2005
Resolution: Verified as corrected this date.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 16 September 2005 Resolved
Tine delay for fwd bosn' stores is unreasonably short @ 30 seconds, replace with a 60 second delay to account for personnel working in bow thruster space. 46CFR/76.15-30
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 13 December 2005
Electrical › Electrical Distribution System (emergency) › Panelboard
Issued 16 September 2005 Resolved
Provide documentation proving plan review and subsequent approval has been completed on main emergency shutdown circuit junction box and panel board trunk lines located in AMR control room in the form of an ABS approved wiring diagram or other acceptable method. 46CFR/111.01-1(3).
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 18 October 2005
Resolution: Verified as corrected this date.
Construction/Loadline › Structures › Machinery Space Opening
Issued 16 September 2005 Resolved
Shaft alley WTD is inoperative both on activation of CO2 system and/or activation of local operating control. Repair same and retest. 46CFR/76.15
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 18 October 2005
Resolution: Verified as corrected this date.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 16 September 2005 Resolved
Data logger room automatic ventilation shutdown on CO2 activation is inoperative. Prove proper operation of this system. 46CFR/76.15-35.
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 18 October 2005
Resolution: Verified as corrected this date.
Electrical › Electrical Distribution System (service) › Metallic Enclosure/Frame
Issued 16 September 2005 Resolved
Data logger room has open and unprotected high voltage circuits, improperly dead-ended cicuits, open panel boards, missing panel covers, spare parts / boxes / file cabinets / misc junk all located in same room. Correct these listed items to comply with 46CFR111.01-1(1)(2)(3) and (4).
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 12 December 2005
Fire Fighting › Fixed Fire Detection System › Smoke Detectors
Issued 16 September 2005 Resolved
Smoke detection system for cargo holds and data logger room found to be inoperative. This system is to be fully overhauled and demonstrated fully operational. 46CFR76.33-20
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 13 December 2005
Fire Fighting › Fixed CO2 Fire Extinguishing System › Piping
Issued 16 September 2005 Resolved
Flexible loops for CO2 system have not been hydro tested to 1000 PSIG as required. Vessel is to test 12 loops and properly label the tested loops and provide servicing report to OCMI at conclusion of these tests. 46CFR147.65(d)
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 13 December 2005
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Instructions
Issued 16 September 2005 Resolved
Labels for the various local actuating bottle stations in the CO2 room are missing or illegible. Permanently mark these operating stations to satisfaction of USCG inspector. 46CFR78.47-17
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 13 December 2005
Fire Fighting › Fixed CO2 Fire Extinguishing System › Quantity of CO2
Issued 16 September 2005 Resolved
Provide a servicing report for the missing 9 bottles of CO2 from CO2 room. 46CFR76.15-5(a)
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 13 December 2005
Fire Fighting › Automatic Sprinkler System › Testing Switches (Alarm/Sprinklers)
Issued 16 September 2005 Resolved
Found sprinkler zone for main deck aft in mess deck zone valve tamper switch and zone flow switch to both be inoperative. This zone to be overhauled and retested to satisfaction of USCG inspector. 46CFR/76.25-35
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 12 December 2005
Fire Fighting › Automatic Sprinkler System › Testing Switches (Alarm/Sprinklers)
Issued 16 September 2005 Resolved
Found sprinkler zone for upper deck aft house ladder well fan room zone valve tamper switch and zone flow switch to both be inoperative. This zone to be overhauled and retested to satisfaction of USCG inspector. 46CFR/76.25-35
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 12 December 2005
Fire Fighting › Automatic Sprinkler System › Testing Switches (Alarm/Sprinklers)
Issued 16 September 2005 Resolved
Found sprinkler zone upper tween deck #6 hold zone valve tamper switch and zone flow switch to both be inoperative. This zone to be overhauled and retested to satisfaction of USCG inspector. 46CFR/76.25-35
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 12 December 2005
Fire Fighting › Combustible Materials › Facings/Mouldings/Decorations/Veneers
Issued 16 September 2005 Resolved
Found hold #3 lower level being used as a store room for life saving gear, engine spare parts, gaskets, boxes paper goods etc. No fire detection or fire supression system in place or operational in this area. Remove flammables or reclassify space to allow stowage of this gear and fix the FF system, 46CFR72.05
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 12 December 2005
Lifesaving › Lifeboat Equipment › Food Ration
Issued 16 September 2005 Resolved
Provide a receipt for missing pyrotechincs and food rations for all life boats to [name withheld]. 46CFR199.175.
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 18 October 2005
Resolution: Verified as corrected this date.
Lifesaving › Lifejacket/PFD (General) › Storage
Issued 16 September 2005 Resolved
Proprly label ALL staterooms and berthing areas with IMO Res A760(18) style labeling the location of each lifejacket (AND immersion suit if so equipped) to comply with 46CFR199.178.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 13 December 2005
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 16 September 2005 Resolved
Galley automatic fire damper and ventilation shutdowns for fixed gas fire fighting system found to be inoperative upon testing. Overhaul and restes the is system to satisfaction of USCG inspector. 46CFR/76.15-35
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 12 December 2005
Operations/Management › Vessel Safety Management › Documentation Maintenance/Control
Issued 16 September 2005 Resolved
Provide labels outside of all doors giving access to interior of hospital spaces that indicate that stowage of oxygen tanks is in the hospital area and that the stowage of greater than 85 M3 of oxygen is prohibited by law. 46CFR147.85.
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 13 December 2005
Operations/Management › Vessel Safety Management › Reports and Analysis
Issued 16 September 2005 Resolved
Complete COI exam all items of section 3 exam booklet CG840HI and as noted in joint COI exam booklets. 46CFR/71.25-10
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 13 December 2005
Fire Fighting › Structural Fire Protection - General › Accommodation Space Protection
Issued 16 September 2005 Resolved
Found oxygen bottles in storage in hospital space and an operating room designation in place without the space being rated as a hazardous location and equipped with Class I Division I expolsion proof fittings and fixtures. Retrofit this space to meet Class I Div I ratings or reclassify the space and use to meet non-Haz classification. 46CFR/111.105
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 13 December 2005
Resolution: Oxygen bottles removed from vessel. To be stored in approved container on weather deck.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 15 September 2005 Resolved
Engine room CO2 system emergecny shutdown pressure switches (6) did not work when testing system. Switches as follows; WTD, Motor driven F/O pup, Turbine driven F/O pump, Ventilation, P&S Forced draft blowers. Repair all and retest same. 46CFR/76.15
Condition: Unknown
Action required: 705 - Other - as specified
Due 30 September 2005
Resolved 18 October 2005
Resolution: Verified as corrected this date.
Accommodation/Occupational Safety › Occupational Safety › Guards for Exposed Hazards
Issued 15 January 2005 Resolved
Due to CO2 smothering system, holds #1 and #2 are to be designated as "unmanned spaces" and shall not be utilized as workshops, classrooms, or training spaces. This requirement does not prohibit occasional and limited entry associated with a hold or storage space. Requirement maintains in effect until vessel compliant with 46 CFR 167.45-1(c)(4)
Due 31 December 2006
Resolved 11 January 2006
Resolution: Converted item to inspection note.
Fire Fighting › Automatic Sprinkler System › Pump
Issued 15 January 2005 Resolved
Complete plan approval for sprinkler installation to navigation laboratory per MSC letter dated 30 SEPT 04. (Serial # E1-0402606).
Due 1 February 2006
Resolved 11 January 2007
Resolution: Completed this date
Fire Fighting › Ventilation Systems › Operating Controls
Issued 15 January 2005 Resolved
Label physical locations of fire control dampers and ensure they are identified on the fire control plan (FCP). 46 CFR 78.45-1 During inspection noted that ventilation damper controls were marked on FCP, but that actual damper locations within system were not identified.
Due 1 February 2006
Resolved 11 January 2006
Resolution: Verified fire damper location table. Table to be used as a supplement to FCP. Inspection noted added.
Engineering › Diesel Engine (auxiliary)
Issued 2 April 2003 Resolved
Prove proper operation of auxiliary generator after installing new speed control module. LEGACY COMPONENT DESC: Overspeed Device
Condition: Unknown
Due 2 May 2003
Resolved 15 April 2003
Resolution: GENERATOR OPERATING PROPERLY.
Lifesaving › Embarkation Appliances/Stations › Designated Location
Issued 2 April 2003 Resolved
Prior to sailing with cadets onboard, conduct fire and boat drills, davit launched liferaft deployment and abandon ship drill to the satisifaction of the attending marine inspector. Per aggreement with MSO Providence.
Condition: Unknown
Action required: 701 - Prior to carriage of passengers/cargo
Due 31 December 2003
Resolved 7 January 2005
Lifesaving
Issued 3 December 1999 Resolved
PRIOR TO DEPARTURE FROM NEXT PORT, BOTH LIFEBOAT FALLS ARE TO BE RENEWED.
Condition: Unknown
Due 3 December 1999
Resolved 3 December 1999
Engineering
Issued 3 December 1999 Resolved
SUBMIT NEXT 3 (THREE) SHAFT OIL ANALYSIS REPORTS TO THIS OFFICE (MOBMS), ONE EVERY 6 MONTHS.
Condition: Unknown
Due 3 December 1999
Resolved 3 December 1999
Engineering
Issued 1 October 1997 Resolved
Demonstrate a proper test of the relief valve for DC Heater.
Condition: Unknown
Due 23 October 1997
Resolved 23 October 1997
Construction/Loadline
Issued 1 October 1997 Resolved
Demonstrate proper operation of starboard deep bilge well pump.
Condition: Unknown
Due 1 October 1997
Resolved 1 October 1997
Construction/Loadline
Issued 2 April 1996 Resolved
Conduct water hose test of hatch covers that were repaired, in presence of marine inspector.
Condition: Unknown
Due 19 December 1996
Resolved 19 December 1996
Electrical
Issued 2 April 1996 Resolved
Replace electrical outlets in crew laundry on main deck with water tight type._x001C_
Condition: Unknown
Due 25 April 1996
Resolved 25 April 1996
Fire Fighting
Issued 2 April 1996 Resolved
Replace firemain pressure gage on bridge._x001C_
Condition: Unknown
Due 2 April 1996
Resolved 2 April 1996
Navigation
Issued 2 April 1996 Resolved
Provide means for conducting alcohol testing._x001C_
Condition: Unknown
Due 2 April 1996
Resolved 2 April 1996
Engineering
Issued 2 April 1996 Resolved
Provide accurate boiler feedwater level indicators per 46CFR62.35-20(b)_x001C_
Condition: Unknown
Due 2 April 1996
Resolved 2 April 1996
Engineering
Issued 2 April 1996 Resolved
Provide approved automation test procedures per 46CFR61.40._x001C_
Condition: Unknown
Due 2 April 1996
Resolved 2 April 1996
Fire Fighting
Issued 2 April 1996 Resolved
Make fire damper closure operable in fan room aft main deck, just behind door._x001C_
Condition: Unknown
Due 25 April 1996
Resolved 25 April 1996
Navigation
Issued 2 April 1996 Resolved
Provide training certification for operator of alcohol testing device._x001C_
Condition: Unknown
Due 2 April 1996
Resolved 2 April 1996
Construction/Loadline
Issued 2 April 1996 Resolved
Provide documentation to prove nonmetallic expansion joints, in systems which penetrate the hull and both the penetration and expansion joint are below deepest load waterline, have been manufactured within 10 years or replace at deactivation per 46 CFR 61.15-12.
Condition: Unknown
Due 25 April 1996
Resolved 25 April 1996
Electrical
Issued 1 June 1994 Resolved
RELAMP SHAFT ALLEY EMERGENCY ESCAPE.
Condition: Unknown
Due 1 June 1994
Resolved 1 June 1994
Documentation
Issued 1 June 1994 Resolved
PROVIDE OIL TRANSFER PROCEDURES IAW 33CFR155.728
Condition: Unknown
Due 1 June 1994
Resolved 1 June 1994
Navigation
Issued 1 June 1994 Resolved
INSTALL STATION DIRECTORY FOR FWD LOOKOUT PHONE.
Condition: Unknown
Due 1 June 1994
Resolved 1 June 1994
Lifesaving
Issued 1 June 1994 Resolved
PROVIDE PROOF THAT LIFEBOAT FALLS WERE END FOR ENDED AND WEIGHT TESTED IN PRESENSE OF COAST GUARD.
Condition: Unknown
Due 1 June 1994
Resolved 1 June 1994
Documentation
Issued 1 June 1994 Resolved
PROVIDE UP TO DATE RADIO TELEGRAPHY CERTIFICATE.
Condition: Unknown
Due 1 June 1994
Resolved 1 June 1994
Electrical
Issued 1 June 1994 Resolved
REPAIR/REPLACE BURNT OUT EMERGENCY LIGHTS.
Condition: Unknown
Due 1 June 1994
Resolved 1 June 1994
Unknown
Issued 26 February 1993 Resolved
REPLENISH MEDICAL SUPPLIES UPON VESSEL'S ACTIVATION OR AT THE NEXT INSPECTION FOR CERTIFICATION BUT NOT LATER THAN 17 DECEMBER 1994.
Condition: Unknown
Due 26 February 1993
Resolved 26 February 1993
Electrical
Issued 22 January 1993 Resolved
UPDATE VESSEL'S ELECTRICAL ONE LINE DIAGRAM TO INCLUDE THE NEW HOT WATER HEATER AND LUBRICATING OIL HEATER. SUBMIT PLANS FOR APPROVAL. (46 CFR 110.25-1)._x001C_ _x001C_
Condition: Unknown
Due 22 January 1993
Resolved 22 January 1993
Construction/Loadline
Issued 17 December 1992 Resolved
REPAIR HOLE IN AFT BULKHEAD OF NO. 1 CARGO HOLD AT THE UPPER TWEEN'DECK NEAR THE BOTTOM OF THE VERTICAL LADDER FROM THE MAINDECK HATCH._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Navigation
Issued 17 December 1992 Resolved
RENEW STEERING GEAR PORT UNIT LEFT RUDDER PRESSURE GUAGE._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Unknown
Issued 17 December 1992 Resolved
RENEW OUTDATED MEDICAL SUPPLIES._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Lifesaving
Issued 17 December 1992 Resolved
PROVIDE SOLAS APPROVED LIGHTS FOR ALL PFDS AND EXPOSURE SUITS._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
PROVIDE NEW CONDENSED MILK SUPPLIES FOR BOTH LIFEBOATS._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
PROVIDE 1 GALLON OF STORM OIL FOR EACH LIFEBOAT._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
PROVIDE ONE 8" ADJUSTABLE WRENCH FOR STARBOARD LIFEBOAT TOOL KIT._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
PROVIDE NEW WATER RATIONS TO REPLACE THOSE RATIONS OLDER THAN 5 YEARS._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
PROVIDE NEW BATTERIES FOR ALL RINGBUOYS WITH LIGHTS ATTACHED (9) TOTAL._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
ENSURE ALL PFDS AND EXPOSURE SUITS HAVE VESSEL NAME STENCILED ON THEM, APPROXIMATELY 10 WERE MISSING PROPER NAME._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
PROVIDE/RENEW RETROREFLECTIVE TAPE ON FOUR PFDS._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Engineering
Issued 17 December 1992 Resolved
RENEW SUCTION AND DISCHARGE SIDE PIPING TO FUEL OIL SERVICE PUMP._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Documentation
Issued 17 December 1992 Resolved
RENEW RADIOTELEGRAPH CERTIFICATE WITH FCC._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Documentation
Issued 17 December 1992 Resolved
RENEW RADIOTELEPHONE CERTIFICATE WITH FCC_x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
RENEW BATTERIES IN EMERGENCY GEAR LOCKER HAND LATERNS._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Engineering
Issued 17 December 1992 Resolved
CALIBRATE DC HEATER HIGH LEVEL ALARM._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Engineering
Issued 17 December 1992 Resolved
CALIBRATE STARBOARD BOILER SUPERHEATER OUT TEMPERATURE GUAGE._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Unknown
Issued 17 December 1992 Resolved
PROVIDE AFFIDAVIT ON PROPER OPERATION OF THE A/C SYSTEM, EVAPORATOR, AND OWS WHILE ON SEA TRIALS._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
PROVIDE RECERTIFICATION PLACARD FOR NO. 2 LIFEBOAT._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Construction/Loadline
Issued 17 December 1992 Resolved
REPAIR HOLE ON BACK SIDE OF FOREPEAK GOOSENECK VENT ON STARBOARD SIDE OF THE FOC'SLE._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Documentation
Issued 17 December 1992 Resolved
PROVIDE UNDERWATER SURVEY PLAN (REFERENCE MARKS PLAN, VIDEO, COATING SYSTEMDATA) TO MSO PORTLAND FOR REVIEW AND FORWARDING TO CG HEADQUARTERS (G-MVI)_x001C__x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Electrical
Issued 17 December 1992 Resolved
PROVE PROPER OPERATION OF EMERGENCY GENERATOR HIGH JACKET WATER TEMPERATUREALARM ON REMOTE ALARM PANEL IN ENGINEROOM._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Fire Fighting
Issued 17 December 1992 Resolved
PROVIDE OPEN DOOR LATCHES AND LABEL DOORS "LATCH DOOR OPEN WHEN OCCUPIED" FOR THOSE COMPARTMENTS WITH CO2 BOTTLES STORED IN THEM AND THE DOORS OPEN INTO THE COMPARTMENT._x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Electrical
Issued 17 December 1992 Resolved
REPAIR/RENEW FAN MOTOR FOR FORWARD BOS'N LOCKER VENTILATION SYSTEM._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Fire Fighting
Issued 17 December 1992 Resolved
Demonstrate proper operation of power actuated sea valve for emergency firepump._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Engineering
Issued 17 December 1992 Resolved
REPAIR MAIN CONDENSER DISCHARGE VALVE BODY AND HYDROTEST._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
MAKE PROPER FRP REPAIRS ON LIFEBOAT HULLS IN ACCORDANCE WITH FILE WORKLIST_x001C__x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Engineering
Issued 17 December 1992 Resolved
RENEW SUPERHEATER TUBES IN BOTH BOILERS WHICH HAVE EXCESSIVE WASTAGE AS DETERMINED BY U.T., SEE FILE ,FOR EXACT NUMBER OF TUBES RENEWED._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Engineering
Issued 17 December 1992 Resolved
RENEW COLLAPSED CONDENSER TUBE INLET INSERTS._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Construction/Loadline
Issued 17 December 1992 Resolved
REPAIR HOLES IN BULKHEAD BETWEEN CARGO HOLDS NO. 5 AND 6 AT FIRST DECK LEVEL BELOW THE MAINDECK_x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Engineering
Issued 17 December 1992 Resolved
REPAIR BROKEN REFRACTORY IN BOTH BOILER FIREBOXES._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Fire Fighting
Issued 17 December 1992 Resolved
REPAIR TWO FIRE DAMPERS AND SHOW PROPER OPERATION OF THE SAME._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
PROVIDE NEW BATTERIES FOR LIFEBOAT FLASHLIGHTS AND SPARES._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Lifesaving
Issued 17 December 1992 Resolved
PROVIDE THREE ADDITIONAL PARACHUTE FLARES FOR THE STARBOARD LIFEBOAT_x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 23 December 1992
Resolved 23 December 1992
Engineering
Issued 17 December 1992 Resolved
RENEW THE STARBOARD AFT SUPPLY FAN MOTOR FOR THE ENGINEROOM SUPPLY VENTILATION._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Engineering
Issued 17 December 1992 Resolved
PROVIDE CG APPROVED PIPING AND ELECTRICAL PLANS ON THE LUBE OIL PURIFIER HEATER._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Accommodation/Occupational Safety
Issued 17 December 1992 Resolved
PROVIDE CG APPROVED PIPING AND ELECTRICAL PLANS FOR THE SEWAGE SYSTEM MODIFICATIONS._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Lifesaving
Issued 17 December 1992 Resolved
END FOR END BOTH SETS OF FALLS ON LIFEBOAT DAVITS._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Accommodation/Occupational Safety
Issued 17 December 1992 Resolved
PROVIDE CG APPROVED PIPING AND ELECTRICAL PLANS ON THE INSTALLATION OF THE POTABLE WATER SYSTEM HEATER._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Electrical
Issued 17 December 1992 Resolved
PROVIDE CG APPROVED ELECTRICAL PLANS ON THE 230 VOLT REEFER CONTAINER DECK WIRING INSTALLATIONS._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 17 December 1992
Resolved 17 December 1992
Engineering
Issued 22 October 1991 Resolved
SUBMIT TAILSHAFT LUBE OIL ANALYSIS TO [name withheld] OIL ANALYSIS MUSTSTATE IF LUBE OIL IS SATISFACTORY OR NOT FOR SERVICE INTENDED AND INCLUDE METALS CONTENT AND WATER CONTENT._x001C_ _x001C_
Condition: Unknown
Due 22 October 1991
Resolved 22 October 1991
Construction/Loadline
Issued 16 September 1991 Resolved
MAKE PERMANENT REPAIRS TO THE WASTED ROSE BOXES IN HOLD #2 PORT AND STBE, AND HOLD #6 STBD.
Condition: Unknown
Due 16 September 1991
Resolved 16 September 1991
Engineering
Issued 16 September 1991 Resolved
MAKE OPERABLE OR REMOVE ENTIRELY THE BRIDGE THROTTLE CONTROL SYSTEM. THE SYSTEM IS NOT TO BE USED FOR ANY REASON UNTIL COMPLETED.
Condition: Unknown
Due 16 September 1991
Resolved 16 September 1991
Engineering
Issued 16 September 1991 Resolved
PROVIDE A SUITABLE HIGH TEMPERATURE ALARM FOR THE #1 MAIN FEED PUMP LUBE OIL.
Condition: Unknown
Due 16 September 1991
Resolved 16 September 1991
Engineering
Issued 16 September 1991 Resolved
MAKE OPERABLE THE HIGH LEVEL ALARMS FOR BOTH FUEL OIL SETTLER TANKS._x001C_ _x001C_ _x001C_ _x001C_
Condition: Unknown
Due 16 September 1991
Resolved 16 September 1991
Engineering
Issued 16 September 1991 Resolved
SUBMIT FOR APPROVAL THE MODIFICATIONS DONE ON THE ENGINE ROOM ALARM PANEL.
Condition: Unknown
Due 16 September 1991
Resolved 16 September 1991
Navigation
Issued 6 December 1990 Resolved
PROVE PROPER OPERATION OF STEERING MOTOR POWER FAILURE AUDIBLE ALARM ON BRIDGE.
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Engineering
Issued 6 December 1990 Resolved
PROVE OPERATION OF MACHINERY SPACE AND SHAFT ALLEY BILGE ALARMS.
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Electrical
Issued 6 December 1990 Resolved
PROVE PROPER OPERATION OF #2 SSTG REVERSE POWER TRIP INDICATOR.
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Fire Fighting
Issued 6 December 1990 Resolved
REPAIR LEAK IN FIRE MAIN BLANKS AFT OF 6"X4" REDUCER.
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Engineering
Issued 6 December 1990 Resolved
RE-CALIBIRATE THE FOLLOWING GAUGES: 1) #1 FEED PUMP DISCH PRES 2) P&S SUPHTR OUTLET PRES 3) STBD DESUPHTR OUTLET TEMP 4) PORT SUPHTR OUTLET TEMP 5) MAIN STEAM TEMP
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Navigation
Issued 6 December 1990 Resolved
MAKE REPAIRS AND PROVE THE OPERATION OF THE RUDDER ANGLE INDICATOR ON THE BRIDGE COLUMN.
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Lifesaving
Issued 6 December 1990 Resolved
GENERAL ALARM BELLS IN ENGINE ROOM WEAK. VERY DIFFICULT TO HEAR. ALL DEFICIENT BELLS TO BE REPAIRED BEFORE LEAVING SAN FRANCISCO BAY.
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Lifesaving
Issued 6 December 1990 Resolved
MAKE REPAIRS TO FIBERGLASS IN PORT LIFEBOAT.
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Lifesaving
Issued 6 December 1990 Resolved
MAKE REPAIRS TO LEAKING EXHAUST ON STARBOARD LIFEBOAT.
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Electrical
Issued 6 December 1990 Resolved
PROVE PROPER OPERATION OF LOW LUBE OIL ALARM AND TRIP ON #2 SSTG. ENSURE THAT LOW LUBE OIL ALARM SOUNDS BEFORE THE GENERATOR TRIPS.
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Engineering
Issued 6 December 1990 Resolved
LIFT RELIEF VALVES ON THE FOLLOWING PRESSURE VESSELS: 1) DC HEATER 50 PSIG MAWP 2) CONTROL AIR RECEIVER 110 PSIG MAWP
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Engineering
Issued 6 December 1990 Resolved
RE-PACK PORT PISTON ON STEAM RECIPROCATING FEED PUMP.
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Engineering
Issued 6 December 1990 Resolved
LIFT RELIEF VALVE ON CONTAMINATED EVAP.
Condition: Unknown
Due 6 December 1990
Resolved 6 December 1990
Lifesaving
Issued 9 August 1990 Resolved
SERVICE INFLATABLE LIFERAFT IAW 46 CFR 91.25-15(A)(6).
Condition: Unknown
Due 9 August 1990
Resolved 9 August 1990
Fire Fighting
Issued 9 August 1990 Resolved
REPAIR OR RENEW THE CO2 TIME DELAY FOR SHAFT ALLEY.
Condition: Unknown
Due 9 August 1990
Resolved 9 August 1990
Fire Fighting
Issued 9 August 1990 Resolved
PROVIDE ONE ADDITIONAL FIREMAN'S OUTFIT IAW 46 CFR 96.35-10(B).
Condition: Unknown
Due 9 August 1990
Resolved 9 August 1990
Fire Fighting
Issued 9 August 1990 Resolved
LABEL DOOR TO EMERGENCY GENERATOR ROOM TO READ "LASH DOOR OPEN WHEN ROOM ISOCCUPIED."
Condition: Unknown
Due 9 August 1990
Resolved 9 August 1990
Fire Fighting
Issued 9 August 1990 Resolved
LABEL CO2 PULLS OUTSIDE OF SHAFT ALLEY IAW 46 CFR 95.15-10(H).
Condition: Unknown
Due 9 August 1990
Resolved 9 August 1990
Engineering
Issued 5 February 1987 Resolved
PROVIDE USCG APPROVED PLANS ON OILY WATER SEPARATOR & BILGE MONITOR INSTALLATION (INCLUDING PIPING & ELECTRICAL MODIFICATIONS)
Condition: Unknown
Due 5 February 1987
Resolved 5 February 1987
Construction/Loadline
Issued 5 February 1987 Resolved
PROVIDE APPROVED PLANS ON SIDESHELL MOORING BIT INSTALLATION.
Condition: Unknown
Due 5 February 1987
Resolved 5 February 1987
Engineering
Issued 5 February 1987 Resolved
PROVIDE INFORMATION ON WHEN & WHERE THE OILY WATER SEPARATOR & BILGE MONITOR WERE INSTALLED AND WHICH COAST GUARD OFFICE WITNESSED THE INSTALLATION.
Condition: Unknown
Due 5 February 1987
Resolved 5 February 1987
Engineering
Issued 23 January 1985 Resolved
SHOW SATISFACTORY OPERATION OF BRIDGE THROTTLE CONTROL.
Condition: Unknown
Due 23 January 1985
Resolved 23 January 1985
Engineering
Issued 23 January 1985 Resolved
PROVIDE A RELIEF VALVE OF THE PROPER SIZE AND CAPACITY FOR THE SHIP'S SERVICE AIR RECEIVER.
Condition: Unknown
Due 23 January 1985
Resolved 23 January 1985
Unknown
Issued 23 January 1985 Resolved
MAKE OPERABLE WATER LEVEL INDICATOR FOR STARBOARD BOILER AT THE CONTROL PANEL.
Condition: Unknown
Due 23 January 1985
Resolved 23 January 1985
Electrical
Issued 23 January 1985 Resolved
MAKE NECESSARY REPAIRS TO THE #2 MAIN CONDENSATE PUMP MOTOR CONTROLLER.
Condition: Unknown
Due 23 January 1985
Resolved 23 January 1985
Engineering
Issued 23 January 1985 Resolved
SHOW SATISFACTORY OPERATION OF THE OILY WATER SEPARATOR.
Condition: Unknown
Due 23 January 1985
Resolved 23 January 1985
Fire Fighting
Issued 23 January 1985 Resolved
PROVIDE PROPER PROTECTIVE CLOTHING FOR THE FIREMAN'S OUTFIT IN THE MACHINERY SPACE.
Condition: Unknown
Due 23 January 1985
Resolved 23 January 1985
Documentation
Issued 23 January 1985 Resolved
POST THE REQUIRED OIL POLLUTION PLACARDS.Y 33 CFR 155.440.
Condition: Unknown
Due 23 January 1985
Resolved 23 January 1985
Lifesaving
Issued 23 January 1985 Resolved
CONDUCT A SUSPENSION/WEIGHT TEST OF THE PORT LIFEBOAT IN THE PRESENSE OF A U. S. COAST GUARD MARINE INSPECTOR.
Condition: Unknown
Due 23 January 1985
Resolved 23 January 1985
Engineering
Issued 23 January 1985 Resolved
SHOW PROPER OPERATION OF THE THROTTLE WRONG DIRECTION ALARM.
Condition: Unknown
Due 23 January 1985
Resolved 23 January 1985
Construction/Loadline
Issued 14 October 1982 Resolved
MAKE PERMANENT REPAIRS TO THE RIVETED SEA OR AT THE J-11 AND K-11 PLATES INTHE #4 CARGO HOLD PORT SIDE TO THE SATISFACTION OF A COAST GUARD MIO INSPEC
Condition: Unknown
Due 14 October 1982
Resolved 14 October 1982

Casualty record · 5

23 March 2008Routine · role: Involved in a Marine Casualty · activity 3184699
12 February 2013Routine · role: Involved in a Marine Casualty · activity 4539736
12 February 2013Routine · role: Involved in a Marine Casualty · activity 4597439
23 June 2025Routine · role: Involved in a Marine Casualty · serious marine incident, as classified · 1 injured · activity 8168625
16 July 2025Routine · role: Involved in a Marine Casualty · serious marine incident, as classified · 1 injured · activity 8200100
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it, and the bridge, lock or dam the investigation names where it names one. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.

Recorded names · 2

ENTERPRISE (2008), T S KENNEDY (2013). Names as the Coast Guard recorded them in incident records, with the years they appear; some are renames and some are spelling variants.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.