PRIDE is a 1968 passenger vessel (inspected). The Coast Guard has recorded 94 inspections since 1984, most recently in March 2026, along with 247 deficiencies, 2 operational controls and 4 casualty investigations between 2011 and 2024.

Records from 1984 to 2026. Most recent: inspection, 27 March 2026.

Built
1968
Last inspected
27 March 2026
Documentation
Valid · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

WDK8867
Flag
UNITED STATES
368098230
Maury page id
psix-45756

Inspections, by type

…with no type recorded14
Years with a record 37 calendar years (1984–2026)
The 94 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Registered dimensions (L × B × D)43.7 ft × 16.1 ft × 5.1 ft
Registered tonnagegross 34 / net 23
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderCUSTOM BOAT CO · VENTURA, CA, UNITED STATES · built 1968
Hull materialWood
PropulsionDiesel Reduction
Hull shapeNot recorded
Hull configurationNot recorded
Hailing portSAN PEDRO, CA
Trade endorsementsCoastwise, unrestricted, Registry
DocumentationValid · issued 29 April 2026 · expires 31 March 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it34 - Regulatory (Subpart C or D), Gross Ton
23 - Regulatory (Subpart C or D), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

WDK8867MMSI 368098230 · active · compulsorily equipped · granted 7 June 2019, expires 7 June 2029
WDI9275MMSI 367747060 · expired · compulsorily equipped · granted 20 July 2016, cancelled 22 August 2026
WDD2706MMSI 367118770 · expired · compulsorily equipped · granted 2 June 2006, cancelled 6 August 2016 · licensed under a name not among this hull’s recorded names (not shown)
WCZ8893MMSI 366784350 · expired · compulsorily equipped · granted 20 June 2000, cancelled 21 August 2010 · licensed under a name not among this hull’s recorded names (not shown)
WCZ2325MMSI 366765450 · expired · compulsorily equipped · granted 30 April 1999, cancelled 4 July 2009 · licensed under a name not among this hull’s recorded names (not shown)
WUS4854MMSI not assigned · expired · compulsorily equipped · granted 23 March 1994, cancelled 23 May 2004 · licensed under a name not among this hull’s recorded names (not shown)
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown. A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.

Inspection history · 94

27 March 2026 Hull Examination
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 8327575
17 September 2024 Deficiency Check · Annual Inspection
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7956301
16 July 2024 Deficiency Check · In-Service Inspection
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7959586
16 July 2024 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 8044423
1 June 2024 Administrative Inspection · Deficiency Check
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7924884
12 April 2024 Vessel Attendance · Administrative Inspection · Special Consideration
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7896528
2 April 2024 Deficiency Check · Administrative Inspection · Damage Survey
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7888971
29 March 2024 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7889974
9 February 2024 Internal Structural Exam · Administrative Inspection · Drydock Exam
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7863565
4 January 2024 Drydock Extension · Internal Structural Exam
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7845232
28 September 2023 Annual Inspection · Deficiency Check
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7740786
7 April 2023 In-Service Inspection
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7655842
9 March 2023 Plan Review "T" Boat
Administrative · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7648316
7 March 2023 Plan Review "T" Boat
Administrative · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7647215
1 July 2022 Deficiency Check · COI Inspection
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7489864
3 March 2022 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7560458
2 December 2021 Internal Structural Exam · Drydock Exam
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7360954
20 October 2021 In-Service Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7336632
17 May 2021 Annual Inspection · Deficiency Check
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7199032
28 May 2020 Deficiency Check · Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6962559
27 January 2020 Deficiency Check · Drydock Exam
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6896900
24 September 2019 In-Service Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6820030
20 May 2019 Deficiency Check · Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6688559
2 August 2018 Type not recorded
No type recorded · Station San Diego · USCG Southwest District (CGD-SW) · Activity 6499794
14 June 2018 Deficiency Check · DAPI Audit · COI Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6444513
19 April 2018 Internal Structural Exam · Drydock Exam
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6395099
5 September 2017 Administrative Inspection · Annual Inspection · Examination of Repairs · Deficiency Check
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6220560
11 August 2017 Damage Survey · Deficiency Check · Administrative Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6237467
23 June 2016 Internal Structural Exam · Deficiency Check · Hull Examination · Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 5916349
16 June 2016 Administrative Inspection
Administrative · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 5909576
16 June 2014 Annual Inspection · Deficiency Check · DAPI Audit
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 4890143
7 May 2012 DAPI Audit · Annual Inspection · Deficiency Check
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 4304765
5 December 2011 Administrative Inspection
Administrative · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 4201759
7 September 2011 Damage Survey
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 4139400
6 September 2011 Type not recorded
No type recorded · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 4140205
11 June 2008 Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 3234159
24 October 2007 Hull Examination · Deficiency Check
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 3081921
23 May 2007 Annual Inspection · Deficiency Check
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 2931677
31 May 2006 Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 2655881
15 November 2005 Hull Examination
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 2509106
2 June 2005 COI Inspection · Deficiency Check
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 2350043
13 May 2004 Annual Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 2047951
7 October 2003 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1923125
19 May 2003 Annual Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1796579
17 June 2002 Type not recorded
No type recorded · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1648298
29 May 2002 Re-Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1623114
20 November 2001 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1395843
24 May 2001 Re-Inspection · Deficiency Check
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1468218
1 February 2001 Type not recorded
No type recorded · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1058983
1 February 2001 Type not recorded
No type recorded · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1422010
16 June 2000 COI Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1389117
27 January 2000 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1381924
2 November 1999 COI Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1131955
4 August 1999 Type not recorded
No type recorded · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1448016
28 May 1999 Re-Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1372648
14 April 1999 Type not recorded
No type recorded · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1388779
5 March 1999 Plan Review "T" Boat
Administrative · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 802938
12 May 1998 Hull Examination
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1400782
8 April 1998 Administrative
Administrative · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1123343
3 March 1998 COI Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1456578
20 January 1998 Type not recorded
No type recorded · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1396865
11 July 1997 Administrative
Administrative · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1114891
6 May 1997 Deficiency Check
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1100724
5 March 1997 Re-Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1380781
11 September 1996 Type not recorded
No type recorded · Marine Safety Detachment Santa Barbara · USCG Southwest District (CGD-SW) · Activity 162412
30 May 1996 Hull Examination
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1465257
16 January 1996 Re-Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1434356
17 January 1995 COI Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1459159
5 December 1994 Hull Examination · Deficiency Check
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1407410
19 January 1994 Re-Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1356574
28 May 1993 Hull Examination
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1148088
1 March 1993 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 840468
4 January 1993 Re-Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1138280
19 May 1992 Hull Examination
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 948975
13 January 1992 COI Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1315785
16 September 1991 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1244545
5 February 1991 Hull Examination · Re-Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 906998
7 February 1990 Administrative
Administrative · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 904035
8 January 1990 Re-Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 919523
28 September 1989 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1308986
25 September 1989 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 898749
29 August 1989 Hull Examination
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 894905
26 January 1989 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1338167
10 January 1989 COI Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 888905
8 March 1988 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1337301
3 February 1988 Hull Examination
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1018686
10 January 1988 Re-Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1322207
21 April 1987 Type not recorded
No type recorded · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1007562
25 February 1987 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1008255
23 January 1987 Re-Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1316640
15 July 1986 Credit Drydock
Administrative · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1297364
11 March 1986 Deficiency Check
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1299840
9 January 1986 COI Inspection
Physical examination · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 995972
4 December 1984 Type not recorded
No type recorded · MSO SAN FRANCISCO BAY · USCG Southwest District (CGD-SW) · Activity 1284712

Deficiency record · 247

01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 27 March 2026 Resolved
A vessel that is exposed to salt water more than three months in any 12 month period since the last examination must undergo a drydock examination at least once every two years. Vessel is overdue for credit hull exam (28FEB26). Vessel must be made available for exam and receive credit dry dock prior to carrying passengers for hire. 46CFR176.600 (c)(1)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 1 April 2026
Resolution: Vessel has been issued dry dock credit.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 17 September 2024 Resolved
A vessel must be operated in accordance with applicable laws and regulations in such a manner as to afford adequate precaution against hazards that might endanger the vessel and the persons to be transported. Deficiencies 3, 5-13, 15, 20-25 & 29-31 provide objective evidence that the vessel is substandard and not proactively managing technical and operational requirements. Vessel must complete a satisfactory COI re-inspection prior to any movement. 46 CFR 185.100
Action required: 30 - Ship detained
Resolved 23 September 2024
Resolution: All Code 30, 60 and 17 deficiencies have been corrected. Flag State detention cleared.
07 - Fire Safety › N/A - No Subsystem › Fire-dampers
Issued 17 September 2024 Resolved
Provisions shall be made by means of plugs, covers, etc., to prevent the admission of air into the space protected. There were no provisions for securing the ventilation openings to the engine room, rendering the fixed firefighting system ineffective. 46 CFR 181.20-35(a) (OLD CFRs)
Action required: 30 - Ship detained
Resolved 23 September 2024
Resolution: Vessel crew installed metal vent covers and demonstrated sucessfully full closure of vent louvers.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 17 September 2024 Resolved
Shutoff valves, installed so as to close against the fuel flow, shall be fitted in the fuel supply lines. The shutoff valve at the tank shall be operable from outside the tank compartment. The emergency fuel shutoff valves are covered by PVC caps. The PVC caps were seized due to excessive deck paint, rendering the shutoff valves inaccessible. 46 CFR 182.20-40(b)(3) (OLD CFRs)
Action required: 30 - Ship detained
Resolved 17 September 2024
Resolution: Vessel crew used hand tools to remove fuel shutoff caps.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 17 September 2024 Resolved
A pre-engineered fixed gas fire extinguishing system must…be installed in accordance with manufacturer's instructions. The installed Fireboy system was not securely mounted on its brackets, causing the bottle to shift and nearly slip out. Continued movement likely would have engaged the activation cable, triggering the system to activate. 46 CFR 181.420(a)(4)
Action required: 30 - Ship detained
Resolved 23 September 2024
Resolution: Service Technical from Marine Fire Protection attended the vessel and adjusted and properly secured Fireboy extinguisher bottle.
07 - Fire Safety › N/A - No Subsystem › Ready availability of fire fighting equipment
Issued 17 September 2024 Resolved
A vessel not required to have a power-driven fire pump by 181.300 must have at least three 2.5 gallon buckets with an attached lanyard, placed so as to be easily available during an emergency. The words “FIRE BUCKET” must be stenciled in a contrasting color on each bucket. The onboard fire buckets were wasted, cracked, missing required markings, and were under capacity at only 2 gallons. 46 CFR 181.610
Action required: 30 - Ship detained
Resolved 23 September 2024
Resolution: Vessel placed on board 3 Fire Buckets with the proper markings and lanyards attached.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 17 September 2024 Resolved
Firefighting, abandon ship, and man overboard drills and training shall be logged or otherwise documented for review by the coast guard upon request. The drill entry shall include the following information: date of the drill and training and a general description of the drill scenario and training topics. Vessel did not have a logbook and was not recording any required drills and training. 46 CFR 185.520(f) & 185.524(d)
Action required: 30 - Ship detained
Resolved 23 September 2024
Resolution: Vessel provided a logbook of conducted drills and training to the attending Marine Inspector.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 17 September 2024 Resolved
Passenger egress drills must be logged or otherwise documented for review by the Coast Guard upon request. The drill entry must include the following information: (1) Date and time of the drill; and (2) Number of drill participants. Vessel did not have a logbook and was not recording any required passenger egress drills. 46 CFR 185.507
Action required: 30 - Ship detained
Resolved 23 September 2024
Resolution: Educated vessel owners/ operators on requirement for passenger egress drill at the beginning of each excursion and the requirements for logging the drills. Vessel o/o will conduct and document passenger egress drills upon resuming operations.
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 17 September 2024 Resolved
Each buoyant apparatus must have a life line securely attached around the outside, festooned in bights no longer than 3 ft., with a seine float in each bight, unless the line is of an inherently buoyant material and absorbs little or no water. The life line must be at least 10 mm (3/8 in.) diameter and have a breaking strength of at least 1215 lb. Pendants must be fitted approximately 18 in. apart around the outside of each buoyant apparatus. Each pendant must be at least 1/4 in. diameter, at least 12 ft. long, secured in the middle, and have a breaking strength of at least 540 lb. Each pendant must be made up in a hank, and the hank secured by not more than two turns of light twine. The Life Floats pendants were installed with incorrect cords and dimensions, were improperly spaced, and several were missing. 46 CFR 160.010-4
Action required: 30 - Ship detained
Resolved 23 September 2024
Resolution: Vessel installed an IBA.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 17 September 2024 Resolved
Each battery used in an item of lifesaving equipment, except inflatable survival craft equipment, must be replaced during the annual inspection if the expiration date of the battery has passed. The water light batteries on the lifefloats were expired in 2022 and of the incorrect type. 46 CFR 185.726(d)
Action required: 30 - Ship detained
Resolved 23 September 2024
Resolution: Vessel installed an IBA.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 17 September 2024 Resolved
The grab lines shall encircle the buoy and shall be held in place by beckets. The ring life buoy's grab lines were severed in multiple locations and did not encircle the buoy. 46 CFR 160.050-4(c)
Action required: 30 - Ship detained
Resolved 23 September 2024
Resolution: Vessel crew repaired Ring Lifebuoy grab line.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 17 September 2024 Resolved
Each life jacket carried on a vessel on oceans, coastwise, or Great Lakes route, must have a life jacket light approved in accordance with §161.012 in subchapter Q of this chapter. 18 life jacket lights were expired. Some lights were expired by one year, while the majority had surpassed their expiration date by two years. 46 CFR 180.75(a)
Action required: 30 - Ship detained
Resolved 23 September 2024
Resolution: Crew replaced all expired life jacket lights with new ones.
09 - Working and Living Conditions › 091 - Living Conditions › Pipes, wires (insulation)
Issued 17 September 2024 Resolved
Electrical equipment on a vessel must be installed and maintained to protect passengers, crew, and the vessel from electrical hazards, including fire and electrical shock. The vessel had numerous wiring issues which posed a major hazard to passengers and crew. The hazards identified include: various exposed and dead end wiring throughout vessel and inappropriate wire connections to include wire nuts. 46 CFR 183.200(b)
Action required: 30 - Ship detained
Resolved 23 September 2024
Resolution: Exposed and dead-end wiring was removed or properly terminated.
02 - Structural Conditions › N/A - No Subsystem › Hull damage impairing seaworthiness
Issued 17 September 2024 Resolved
Repairs or alterations to the hull, machinery, or equipment that affect the safety of the vessel must not be made without the approval of the cognizant OCMI, except during an emergency. The vessel made unapproved repairs to the starboard bow after an allision with a dock, preventing the attending marine inspector from evaluate the extent of the damage. 46 CFR 176.700(a)
Action required: 60 - Rectify deficiencies prior to movement
Resolved 23 September 2024
Resolution: Crew sanded down repair compound and attending Marine Inspector was able to evaluate the extent of the damage. Damage was deemed minor and not penetrating the hull.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 17 September 2024 Resolved
Accessories, such as switches , fuses, and sockets, shall be standard National Electrical Code types for the loads to be carried. Power strips were found throughout the vessel allowing loads to extend beyond the outlets' designed capabilities. Several extension cords were found throughout vessel as a means of permanent installation. 46 CFR 183.05-35 (OLD CFRs)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 September 2024
Resolution: Crew removed extention cords.
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 17 September 2024 Resolved
The equipment required for life floats must meet the following specifications: Each paddle must be of at least 4 feet in length, lashed to the life float to which it belongs, and buoyant. Vessel’s paddles were not secured to their respective life floats and one was broken and requires replacement. 46 CFR 180.175(f)(2)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 September 2024
Resolution: Vessel installed an IBA.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 17 September 2024 Resolved
A vessel at anchor shall exhibit where it can best be seen: In the fore part, an all-round white light. The installed anchor light was obstructed by the radar dome and the approximate arc of visibility was 180 degrees. Vessel is restricted to daylight operations only. 33 CFR 83.30(a)(i)
Action required: 705 - Other - as specified
Resolved 23 September 2024
Resolution: Anchor light was mounted above radar dome providing 360 degree arc of visibility.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 17 September 2024 Resolved
Where a flexible fill pipe section is necessary…Such hose shall overlap metallic pipe ends at least 1.5 times the pipe diameter and shall be secured at each end by two clamps of corrosion resistant metal…When the flexible section is a nonconductor of electricity, the metallic sections of the filling pipe separated thereby shall be joined by a conductor for protection against static spark when filling. The flexible fuel fill pipes on the port and starboard sides were missing two clamps and bonding wire to prevent static spark.46 CFR 182.15-30(d) (OLD CFRs)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 22 October 2024
Resolution: Piping properly bonded with bonding wire and two hose clamps.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 17 September 2024 Resolved
At each inspection for certification and at every other vessel inspection all observed unsafe practices, fire hazards, and other hazardous situations must be corrected and all required guards and protective devices must be in satisfactory condition. The onboard freezer located in the passenger accommodation area was improperly stowed on an overhead shelf and left unsecured, posing a potential hazard to both crew and passengers. 46 CFR 176.830
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 23 September 2024
Resolution: Freezer was bolted with metal brackets and secured in place.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 17 September 2024 Resolved
Bilge suction shall be fitted with suitable strainers. The installed bilge foots were missing required strainers. 46 CFR 182.25-5(b) (OLD CFRs)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 22 October 2024
Resolution: New bilge foot screens installed.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 17 September 2024 Resolved
Each child size life jacket must be stowed in a location that is appropriately marked and separated from adult life jackets so the child size life jackets are not mistaken for adult life jackets. The child size life jackets were not separated from the adult lifejackets. 46 CFR 180.78(a)(5)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 23 September 2024
Resolution: Crew separated and labeled child-sized life jackets where they would not be mistaken for adult-sized lifejackets.
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 17 September 2024 Resolved
Life floats must not be stowed in tiers more than 4 feet high. When stowed in tiers, the separate units must be kept apart by spacers. Spacers between lifefloats were missing. 46 CFR 180.137(f)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 23 September 2024
Resolution: Vessel installed an IBA.
18 - Maritime Labour Convention (Not Applicable to PSC Exams conducted in the U.S.) › N/A - No Subsystem › Other (Conditions of employment)
Issued 17 September 2024 Resolved
An individual may not be engaged or employed, including self-employment, on a vessel in a position as master, operator, or person in charge for which a credential is required by law or regulation unless all crewmembers covered by this section are subject to the random testing requirements of this section. Vessel was unable to prove compliance with any DAPI requirements, including master and crew enrollment in the vessel's DAPI program and a lack of company DAPI policy. 46 CFR 16.230(k)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 23 September 2024
Resolution: Owner/ Operator provided DAPI enrollment certificate and documentation to attending Marine Inspector.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 17 September 2024 Resolved
Each EPIRB, other than an EPIRB in an inflatable liferaft , must be tested monthly, using the integrated test circuit and output indicator, to determine that it is operative. The EPIRB test required by paragraph (a) shall be logged or otherwise documented, as applicable. Vessel was unable to provide an EPIRB testing log. 46 CFR 185.728
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 23 September 2024
Resolution: Vessel crew provided EPIRB testing log to the attending Marine Inspector.
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 17 September 2024 Resolved
As appropriate for the intended voyage, a vessel must carry adequate and up-to-date: U.S. Coast Pilot [name withheld] List, and Tide Tables. The publications onboard were outdated by 6 years and inland navigation rules was missing. 46 CFR 184.420(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 22 October 2024
Resolution: Appropriate nav pubs provided.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 17 September 2024 Resolved
The name of a vessel must be marked or painted in clearly legible letters and numbers: (2) On each life float and buoyant apparatus. Required markings were worn and illegible. 46 CFR 185.604(a)(2)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 22 October 2024
Resolution: IBA installed.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 17 September 2024 Resolved
Spaces containing machinery shall be fitted with at least 2 ducts to furnish natural or mechanical supply and exhaust ventilation. One duct shall extend to a point at the bottom of the compartment. Engine room only has one general ventilation duct located at the top entrance of the compartment. 46 CFR 182.20-45(c) (OLD CFRs)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 5 November 2024
Resolution: Deficiency cleared after reconsideration with regard to new T requirements.
01 - Certificates & Documentation › 011 - Ships Certificates › Cargo Ship Safety Radio (including exemption)
Issued 17 September 2024 Resolved
Each ship transporting more than six passengers for hire equipped with a radiotelephone station in accordance with Part III of Title III of the Communications Act must carry a radio operator. Operator did not have an FCC radio operator permit. 47 CFR 80.159(e)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 22 October 2024
Resolution: Owner has FCC marine radio operator permit.
01 - Certificates & Documentation › 011 - Ships Certificates › Cargo Ship Safety Radio (including exemption)
Issued 17 September 2024 Resolved
Every vessel subject to Part III of Title III of the Communications Act must have a detailed inspection of the radio installation by an FCC-licensed technician in accordance with § 80.59 once every five years. Vessel did not have a valid safety radiotelephony certificate. 47 CFR 80.903
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 22 October 2024
Resolution: Certificate onboard.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 17 September 2024 Resolved
For a vessel described by 46 CFR 175.110(c), the training program in paragraph (a) of this section must address firefighting proficiency and must include, but need not be limited to...Emergency egress training for each member of the crew, to occur for all members of the crew— (i) At least monthly while such members are employed on board the vessels; and (ii) Each time a crew member joins the crew of such vessel. The vessel had no record of a training program or emergency egress training for crewmembers. 46 CFR 185.420(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 23 September 2024
Resolution: Vessel Owner/ Operator provided documentation for conducted and logged emergency egress training for crewmembers.
11 - Life Saving Appliances › N/A - No Subsystem › On board training and instructions
Issued 17 September 2024 Resolved
The master and crew of a vessel will be familiar with the content of and have mounted at the operating station, emergency instructions containing the actions to be taken in the event of fire, heavy weather, or man overboard conditions. The vessel was missing emergency instructions as listed in 46 CFR 185.512. 46 CFR 185.510(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 23 September 2024
Resolution: Owner/ Operator posted emergency instructions at the operating station.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 17 September 2024 Resolved
Lighting fixtures shall be contrasted in accordance with the requirements of UL Inc. Standard for Marine Type Electric Lighting Fixtures. An overhead light in the E/R was missing its light bulb, globe, and protective cover. 46 CFR 183.10-20(l) (OLD CFRs)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 1 October 2024
Resolved 23 September 2024
Resolution: Crew replaced missing lightbulb, globe and cover on Engine Room overhead light.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 16 July 2024 Resolved
Propulsion machinery must be suitable in type and design for propulsion requirements of the hull in which it is installed and capable of operating at constant marine load under such requirements without exceeding its designed limitations. Vessel lost propulsion while underway with passengers on board. Prior to movement, proper operation of propulsion machinery must be verified by an attending USCG Marine Inspector.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 22 July 2024
Resolution: Witnessed satisfactory operation of MDE.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 1 June 2024 Resolved
Each vessel that relies on electricity to power the following loads must be arranged so that the loads can be energized from two sources of electricity. Generator is inoperable due to a seized alternator.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 1 June 2024
Resolved 3 June 2024
Resolution: Alternator has been replaced and functionality has been tested to the satisfaction of the attending MI.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 2 April 2024 Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with the terms of its Certificate of Inspection giving consideration to provisions for a seaworthy hull, protection against fire, means of escape in case of a sudden unexpected casualty, guards and rails in hazardous places, ventilation of enclosed spaces, and necessary facilities for passengers and crew. Vessel's propeller is damaged. Repair/replace propeller and conduct a satisfactory sea trial prior to movement to the satisfaction of an attending USCG Marine Inspector. 46 CFR 177.100
Condition: Damaged By Earlier Event
Action required: 60 - Rectify deficiencies prior to movement
Resolved 8 April 2024
Resolution: New propeller has been installed and vessel completed satisfactory sea trial.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 2 April 2024 Resolved
In systems and applications where flexible hoses are permitted to be clamped: Double hose clamping is required where practicable. Inspector found raw water intake system with single hose clamping in engine room. 46CFR182.410(d)(1)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 18 April 2024
Resolved 8 April 2024
Resolution: Double hose clamps were installed on the raw water intake system flexible hose.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 2 April 2024 Resolved
At each inspection for certification and at every other vessel inspection the bilges and other spaces may be examined to see that there is no excessive accumulation of oil, trash, debris, or other matter that might create a fire hazard, clog bilge pumping systems, or block emergency escapes. Inspector observed bilges with excessive accumulation of oil in engine room. 46 CFR 176.830(b)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 18 April 2024
Resolved 8 April 2024
Resolution: The oil in the bilge has been cleaned up.
14 - Pollution Prevention › 141 - MARPOL Annex I › Oil fuel tank protection
Issued 28 September 2023 Resolved
WHERE FLEXIBLE FILL PIPE SECTION IS NECESARRY, SUITABLE FLEXIBLE TUBING OR HOSE HAVING HIGH RESISTANCE TO SALT WATER, PETROLEUM OILS, HEAT AND VIBRATION, MAY BE USED. SUCH HOSE MUST OVERLAP METALIIC PIPE ENDS AT THE LEAST 1 1/2" TIMES THE PIPE DIAMTER AND MUST BE SECURTED AT EACH END BY CLAMPS. MI OBSERVED FUEL FILL PIPE MISSING HOSE CLAMPS. 46 CFR 182.445(g)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 12 October 2023
Resolved 8 April 2024
Resolution: Pipe secured by hose clamps.
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 28 September 2023 Resolved
EACH VESSEL THAT OPERATES ON THE HIGH SEAS MUST HAVE ONBOARD A FCC TYPE ACCEPTED CATEGORY 1, 406 MHz EPIRB, INSTALLED TO AUTOMATICALLY FLOAT FREE AND ACTIVATE. MI OBSERVED EPIRB REGISTRATION STICKER MISSING. 46 CFR 150.64
Action required: 50 - Rectify deficiencies w/in 30 days
Due 28 October 2023
Resolved 8 April 2024
Resolution: Registration is up to date.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 28 September 2023 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Action required: 50 - Rectify deficiencies w/in 30 days
Due 28 October 2023
Resolved 8 April 2024
Resolution: Alcohol strips have been procured.
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 1 July 2022 Resolved
Each vessel that operates on the high seas, or that operates beyond three miles from the coastline of the great lakes, must have an onboard a FCC type accepted category I, 406 Mhz EPIRB, installed to automatically float free & activate. EPIRB hydrostatic release is expired.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 2 July 2022
Resolution: Vessel operator purchased new EPIRB hydrostatic release unit. Unite was installed in EPIRB housing unit.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 1 July 2022 Resolved
Painter. The painter must be of at lease 30.5 meters (100) feet in length, but not less than 3 times the distance between the deck where the life float of buoyant apparatus it serves is stowed. Life float painter lines is not of required length.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 2 July 2022
Resolution: Operator installed new painter line on onboard life floats, of adequate length (60').
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 1 July 2022 Resolved
All fiber reinforced plastic (FRP) vessels constructed with general purpose resin must be fitted with a smoke activation fire detection system in isolated spaces that contain an ignition source. No fire detection system in galley.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 2 July 2022
Resolution: New smoke detector was installed ivo the galley space.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 1 July 2022 Resolved
Each life jacket carried on a vessel on oceans route or coastwise route must have a lifejacket light.01 lifejacket missing light.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 2 July 2022
Resolution: Operator privided approriate light for 01 life jacket.
14 - Pollution Prevention › 145 - MARPOL Annex V › Placards
Issued 1 July 2022 Resolved
Master shall ensure that one or more placards meeting the requirements of this section are displayed in prominent locations. No garbage placard located on the vessel.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 July 2022
Resolved 21 July 2022
Resolution: New placard was purshased and placed ivo galley.
14 - Pollution Prevention › 144 - MARPOL Annex IV (Not Applicable to PSC Exams conducted in the U.S.) › Sewage treatment plant
Issued 1 July 2022 Resolved
When operational a vessel on a body of water where the discharge of untreated sewage is prohibited by the EPA, the operator must secure each type II device in a manner which prevents discharge of sewage. Vessel does not have means to secure the discharge of sewage.
Condition: Invalid
Action required: 16 - Rectify deficiencies w/in 14 days
Due 15 July 2022
Resolved 15 July 2022
Resolution: Handle was removed from the sewage overboard discharge valve.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 1 July 2022 Resolved
Each watertight bulkhead must be of sufficient strenght to be capable of remaining watertight with a head of water. To the top of the bulkhead, water ingress from laz to E/R.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 July 2022
Resolved 21 July 2022
Resolution: 3M marine adhesive sealant used to secure water ingress.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machines/parts
Issued 1 July 2022 Resolved
An exposed hazard, such as gears or rotating machinery, must be properly protected by a cover guard or rail. No guard around generator belt.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 July 2022
Resolved 9 October 2022
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 1 July 2022 Resolved
All equipment, including switches, fuses, lamp holders etc. must be suitable for the voltage and current utilized. Vsl battery system is plugged into the power strip.
Action required: 10 - Deficiency Rectified
Resolved 1 July 2022
Resolution: Operator unplugged the battery system from the power strip.
05 - Radio Communications › N/A - No Subsystem › MF/HF Radio installation
Issued 1 July 2022 Resolved
All cables and wire must be: protected from the weather. HF antenna cable is cracked.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 15 July 2022
Resolved 15 July 2022
Resolution: Completely removed wire. Antenna and radio unit was not bein utilized.
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 1 July 2022 Resolved
A vessel must carry either a first-aid kit approved under approval series 160.041 or a kit with equivalent contents & instructions. Aspirin in kit is expired.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 July 2022
Resolved 27 July 2022
Resolution: New fist aid kit was purchased.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 17 May 2021 Resolved
02 permanently installed extension cords were found on the vessel, provide dedicated receptacles and properly sized boat cable for electrical loads.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 May 2021
Resolved 19 May 2021
Resolution: Vessel rep emailed photos of removed extension cords and installed boat cable.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 17 May 2021 Resolved
Remove electrical outlet installed in the stbd head/shower, outlet is an electrical safety hazard.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 May 2021
Resolved 19 May 2021
Resolution: Vessel rep emailed photos of outlet removed and blanked off.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 17 May 2021 Resolved
Main engine sea strainers acrylic cylinder was found cracked but not leaking, replace in-kind.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 May 2021
Resolved 19 May 2021
Resolution: Vessel rep emailed photos of new sea strainer installed.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 17 May 2021 Resolved
Permanently secure hose that was interfering with the closure of the port fuel shutoff valve.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 May 2021
Resolved 19 May 2021
Resolution: Vessel rep emailed photos of secured hose.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 17 May 2021 Resolved
Remove dead ended wires for 02 junction boxes in lazarette.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 May 2021
Resolved 19 May 2021
Resolution: Vessel rep emailed photos of removed wires and covers placed on j-boxes.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 17 May 2021 Resolved
Provide chafe gear where fuel hose is in contact with metal structure, engine compartment, port side.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 May 2021
Resolved 19 May 2021
Resolution: Vessel rep emailed photos of chafe gear installed.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Machinery space openings
Issued 17 May 2021 Resolved
Several open piping and wiring bulkhead penetrations were found in engine compartment. Make both forward and aft engine room bulkhead water / vapor tight.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 May 2021
Resolved 19 May 2021
Resolution: Vessel rep emailed photos of bulkhead sealed with fire stop sealant.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 28 May 2020 Resolved
Child lifejacket marking showed 06 but actual lifejackets are 04. Change marking to show actual proper amount of stowage.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 June 2020
Resolved 10 June 2020
Resolution: Markings provided.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 28 May 2020 Resolved
Provide retro-reflective tape for all lifejackets where tape is worn out.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 June 2020
Resolved 29 May 2020
Resolution: Verified by [name withheld]
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 28 May 2020 Resolved
Provide weak link that has label that is legible for life floats.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 June 2020
Resolved 29 May 2020
Resolution: verified by [name withheld]
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboat inventory
Issued 28 May 2020 Resolved
Remove unused life float weak link and 100 ft of line.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 June 2020
Resolved 29 May 2020
Resolution: Verified by [name withheld]
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboat inventory
Issued 28 May 2020 Resolved
Provide operational waters light for three life floats.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 June 2020
Resolved 29 May 2020
Resolution: Verified by [name withheld]
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboat inventory
Issued 28 May 2020 Resolved
Provide 100ft of new line for life float. Old line showing UV deterioration.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 11 June 2020
Resolved 29 May 2020
Resolution: Verified by [name withheld]
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 28 May 2020 Resolved
Primary steering system is in-op. Must rectify prior to carrying passengers.
Action required: 705 - Other - as specified
Due 11 June 2020
Resolved 10 June 2020
Resolution: Steering operational.
02 - Structural Conditions › N/A - No Subsystem › Decks - cracking
Issued 27 January 2020 Resolved
Deck support in forepeak overhead cracked. Make repairs to support to ensure deck does not sag.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 20 February 2020
Resolution: Deck forepeak repaired.
02 - Structural Conditions › N/A - No Subsystem › Decks - cracking
Issued 27 January 2020 Resolved
In lazerrete deck clamp both port and starboard where aft cleat is located is holed. Make repairs to deck clamp to bring back to original condition.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 20 February 2020
Resolution: Repairs made to aft cleat.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 24 September 2019 Resolved
Vessel has been identified as having various A/C electrical modifications since initial certification. Sector San Diego does not have vessels electrical plans on file or current installations do not match what we have on file. Provide a one-line electrical drawing for all A/C switchboards and distribution panels. Include all circuit loads, conductor sizes, and over current protection.
Condition: Invalid
Action required: 705 - Other - as specified
Due 24 December 2019
Resolved 1 June 2021
Resolution: Drawing approved and filed in vessel electronic files...[name withheld]
01 - Certificates & Documentation › 012 - Crew Certificates › Manning specified by the minimum safe manning doc
Issued 24 September 2019 Resolved
While underway or drifting at sea, every vessel shall at all times maintain a proper look-out by sight and hearing. The designated watchmen required by 46 CFR 185.410 cannot preform both roving patrolling and look-out watch simultaneously.
Condition: Invalid
Action required: 10 - Deficiency Rectified
Due 24 September 2019
Resolved 24 September 2019
18 - Maritime Labour Convention (Not Applicable to PSC Exams conducted in the U.S.) › N/A - No Subsystem › Electrical
Issued 24 September 2019 Resolved
Vessel electrical panel shall be provided with a shore tie interlock to prevent simultaneous electrical loads from going to the panel.
Condition: Design Flaw
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 11 October 2019
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 24 September 2019 Resolved
All emergency lighting installed shall operate in accordance with regulations. Emergency lighting install in close vicinity to the emergency exit was not working.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 October 2019
Resolved 11 October 2019
09 - Working and Living Conditions › 092 - Working Conditions › Fitness for duty - intoxication
Issued 20 May 2019 Resolved
Update crewlist for new hire employee
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 June 2019
Resolved 12 June 2019
01 - Certificates & Documentation › 011 - Ships Certificates › Cargo Ship Safety Radio (including exemption)
Issued 20 May 2019 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 June 2019
Resolved 12 June 2019
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 20 May 2019 Resolved
Demonstate proper operation of the emergency tiller and make fast all steering components.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 June 2019
Resolved 12 June 2019
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 20 May 2019 Resolved
Renew wasted retrotape on ring buoy.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 June 2019
Resolved 12 June 2019
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 20 May 2019 Resolved
Provide flame bowls for MDE F/O filters.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 20 June 2019
Resolved 12 June 2019
Documentation › Certificates/Documents › Certificate of Documentation (CG-1270)
Issued 14 June 2018 Resolved
No valid COD.
Action required: 60 - Rectify deficiencies prior to movement
Due 19 June 2018
Resolved 20 June 2018
Resolution: New COD obtained.
Lifesaving › Lifejacket/PFD (General) › Marking
Issued 14 June 2018 Resolved
Update marking for lifejackets storage.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 June 2018
Resolved 28 June 2018
Resolution: Marking updated.
Navigation › Piloting/Steering › Magnetic Compass
Issued 14 June 2018 Resolved
Provide light for magnetic compass.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 June 2018
Resolved 28 June 2018
Resolution: Flashlight installed for use at compass.
Stability › Watertight Integrity › General
Issued 14 June 2018 Resolved
Provide gasket for forward hatch.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 June 2018
Resolved 28 June 2018
Resolution: Gasket provided.
Fire Fighting › Means of Escape › Blocked
Issued 14 June 2018 Resolved
Clear emergency exit hatch in operating station.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 June 2018
Resolved 28 June 2018
Resolution: Hatch cleared. New carpet installed.
Engineering › Bilge Water Management System › Pump
Issued 14 June 2018 Resolved
Make rule bilge system operational or remove from vessel.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 19 June 2018
Resolved 28 June 2018
Resolution: Rule pump in accommodation space removed. Rule pumps in engineering spaces now operational.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 6 September 2017 Resolved
Prove proper operation of engine shutdown.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 6 September 2017
Resolved 6 September 2017
Resolution: System serviced and tested by 3rd party.
Engineering › Fuel Oil Service System › Hose
Issued 6 September 2017 Resolved
Install double hose clamps on fuel lines of diesel generator
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 6 October 2017
Resolved 8 March 2018
Engineering › Fuel Oil Service System › Filter
Issued 6 September 2017 Resolved
Install flame impingement bowl on MDE fuel filter
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 6 October 2017
Resolved 8 March 2018
Fire Fighting › Portable CO2 Fire Extinguisher › Service
Issued 6 September 2017 Resolved
Remove expired fire extinguisher from vessel
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 6 September 2017
Resolved 6 September 2017
Resolution: Extinguisher removed from vessel.
Fire Fighting › Remote Fuel Shutoff › General
Issued 6 September 2017 Resolved
Properly label fuel shutoff valves.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 6 October 2017
Resolved 8 March 2018
Electrical › Electrical Distribution System (service) › Switch
Issued 6 September 2017 Resolved
Properly mount bilge pump switch on bulkhead.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 6 October 2017
Resolved 8 March 2018
Lifesaving › Lifejacket/PFD (Type I) › Lights
Issued 6 September 2017 Resolved
Install operational lifejacket lights on life jackets X 2.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 6 September 2017
Resolved 6 September 2017
Resolution: Lights installed.
Lifesaving › Hand Flares › Storage
Issued 6 September 2017 Resolved
Make distress signal container watertight.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 6 October 2017
Resolved 8 March 2018
Documentation › Certificates/Documents › Certificate of Inspection
Issued 5 September 2017 Resolved
Complete successful annual inspection.
Action required: 701 - Prior to carriage of passengers/cargo
Due 6 September 2017
Resolved 6 September 2017
Resolution: Completed annual inspection.
Engineering › Steering Gear System › Yoke
Issued 11 August 2017 Resolved
Repair/Replace sheered steering ram adapter.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 11 August 2017
Operations/Management › Drug and Alcohol Testing › Proof of Enrollment
Issued 23 June 2016 Resolved
Provide consortium letter for 2016
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 July 2016
Resolution: Enrollment letter provided
Documentation › Certificates/Documents › FCC Safety Radiotelephony Certificate
Issued 23 June 2016 Resolved
Provide current FCC station lic. and safety cert.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 28 June 2017
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 23 June 2016 Resolved
Prove proper operation of all nav lights
Action required: 705 - Other - as specified
Resolved 8 July 2016
Resolution: Extinguished Nav Light have been corrected
Navigation › Piloting/Steering › Marine Charts
Issued 23 June 2016 Resolved
Provide updates to Coast Pilot [name withheld], Tide Tables, Nav Rules and Charts.
Action required: 705 - Other - as specified
Resolved 28 June 2017
Communications › Radio Communications › Radiotelephone Transceiver (2-4 MHz)
Issued 23 June 2016 Resolved
Provide MF radio for voyages beyond 20NM
Action required: 705 - Other - as specified
Resolved 28 June 2017
Communications › Visual Communication › Red Warning Signal
Issued 23 June 2016 Resolved
Provide 12 red flares
Action required: 705 - Other - as specified
Resolved 8 July 2016
Resolution: 12 red flare are onboard
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 23 June 2016 Resolved
Provide current first aid kit items
Action required: 705 - Other - as specified
Resolved 8 July 2016
Resolution: All items current
Fire Fighting › Fixed Gas Fire Extinguishing System › Operating Controls
Issued 23 June 2016 Resolved
Provide snorkel or shutdown for generator
Action required: 705 - Other - as specified
Resolved 8 July 2016
Resolution: Engine snorkle was installed
Electrical › Electrical Distribution System (service) › Fuse
Issued 23 June 2016 Resolved
Remove all wire nuts and blade fuses
Action required: 705 - Other - as specified
Resolved 8 July 2016
Resolution: All blade fuses replaced by cartridge type
Engineering › Fuel Oil Storage/Transfer System › Vent Pipe
Issued 23 June 2016 Resolved
Provide fuel tank vent screens.
Action required: 705 - Other - as specified
Resolved 8 July 2016
Resolution: 30x30 mesh installed
Communications › Alarms/Indicators › Bilge Alarm
Issued 23 June 2016 Resolved
Prove proper operation of bilge alarms
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 July 2016
Resolution: All bilge alarms operable.
Personnel › Certificates/Documents/Licenses › License, Master
Issued 23 June 2016 Resolved
Provide MMC for CAPT
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 July 2016
Resolution: Current license provided by the Master
Electrical › Lighting (emergency) › Lighting Fixture
Issued 23 June 2016 Resolved
Prove proper operation of E-lighting
Action required: 705 - Other - as specified
Resolved 8 July 2016
Resolution: E-lighting operates as requiered
Communications › Radio Communications › EPIRB
Issued 23 June 2016 Resolved
Provide current registration for EPIRB
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 July 2016
Resolution: NOAA registration provided as required
Unknown
Issued 23 June 2016 Resolved
Resolve all outstanding CG 835's prior to departing the dock.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 June 2017
Documentation › Certificates/Documents › Certificate of Inspection
Issued 16 June 2016 Resolved
Vessel exceeded its Hull Inspection dates
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 28 June 2017
Fire Fighting › Remote Fuel Shutoff › General
Issued 16 June 2014 Resolved
Renew fuel shutoff valve. Vessel restricted to pier.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 June 2014
Resolved 17 June 2014
Electrical › Lighting (emergency) › Lighting Fixture
Issued 16 June 2014 Resolved
Prove proper operation of emergency lighting and mark properly. Vessel restricted to no overnight passengers.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 June 2014
Resolved 18 June 2014
Electrical › Electrical Distribution System (service) › Wiring
Issued 16 June 2014 Resolved
Remove dead end wiring from bridge and engine room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 June 2014
Resolved 17 June 2014
Fire Fighting › Portable CO2 Fire Extinguisher › Marking
Issued 16 June 2014 Resolved
[name withheld] Extinguisher location.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 June 2014
Resolved 18 June 2014
Personnel › Certificates/Documents/Licenses › License, Operator
Issued 7 May 2012 Resolved
Provide copy of FCC operators permit.
Action required: 705 - Other - as specified
Due 31 May 2012
Resolved 22 May 2012
Resolution: FCC operators permit received.
Documentation › Manifests/Lists › Muster List/Emergency Instructions
Issued 7 May 2012 Resolved
Post copy of emergency instruction list.
Action required: 705 - Other - as specified
Due 31 May 2012
Resolved 23 May 2012
Resolution: Emergency instruction list posted.
Lifesaving › Lifefloat › Paddle
Issued 7 May 2012 Resolved
Provide one additional oar for lifefloat.
Action required: 705 - Other - as specified
Due 31 May 2012
Resolved 22 May 2012
Resolution: Oar provided.
Lifesaving › Hand Flares › Quantity
Issued 7 May 2012 Resolved
Provide 12 red hand flares or 6 orange smoke.
Action required: 705 - Other - as specified
Due 31 May 2012
Resolved 22 May 2012
Resolution: 12 red hand flares provided on board.
Fire Fighting › Means of Escape › Escape Route Signs
Issued 7 May 2012 Resolved
Mark emergency exit in fwd berthing.
Action required: 705 - Other - as specified
Due 31 May 2012
Resolved 24 July 2012
Resolution: Properly marked
Fire Fighting › Fire Bucket › Quantity
Issued 7 May 2012 Resolved
Provide three fire buckets.
Action required: 705 - Other - as specified
Due 31 May 2012
Resolved 22 May 2012
Resolution: 3 fire buckets on board.
Accommodation/Occupational Safety › Occupational Safety › Guards for Exposed Hazards
Issued 7 May 2012 Resolved
Provide guard for rotating parts on genset.
Action required: 705 - Other - as specified
Due 31 May 2012
Resolved 24 July 2012
Resolution: Metal guard installed.
Engineering › Fuel Oil Service System › Piping
Issued 7 May 2012 Resolved
Repair minor fuel leak on MDE fuel line at fuel pump.
Action required: 705 - Other - as specified
Due 31 May 2012
Resolved 22 May 2012
Resolution: Fuel leak repaired.
Stability › Watertight Integrity › General
Issued 7 May 2012 Resolved
Seal watertight bulkhead penetration aft of genset.
Action required: 705 - Other - as specified
Due 31 May 2012
Resolved 22 May 2012
Resolution: Penetration sealed.
Construction/Loadline › Hull › Bracket
Issued 24 October 2007 Resolved
Replace all corroded bolts and seal holes.
Condition: Placed in Improper Service
Due 26 October 2007
Resolved 26 October 2007
Construction/Loadline › Hull › Keel
Issued 24 October 2007 Resolved
Caulk and seal gap along keel and hull.
Condition: Improper/Lack of Maintenance
Due 26 October 2007
Resolved 26 October 2007
Construction/Loadline › Hull › Hull Plating
Issued 24 October 2007 Resolved
Laminate as needed all open wood surface along hull bottom.
Condition: Improper/Lack of Maintenance
Due 26 October 2007
Resolved 26 October 2007
Construction/Loadline › Hull › Bracket
Issued 24 October 2007 Resolved
Replace zinc.
Condition: Unknown
Due 26 October 2007
Resolved 26 October 2007
Deck/Cargo › Holds/Tanks › Bulkhead
Issued 24 October 2007 Resolved
Seal holes in bow locker.
Condition: Improper Installation
Due 26 October 2007
Resolved 26 October 2007
Lifesaving › Lifefloat › Netting
Issued 23 May 2007 Resolved
Replace grabline and netting for all 3 lifefloats.
Condition: Improper/Lack of Maintenance
Due 10 June 2007
Resolved 5 June 2007
Operations/Management › Bilge/Bilge System Management › Control of Excess Water
Issued 23 May 2007 Resolved
Make forepeak auto pump discharge to be manually activated.
Condition: Design Flaw
Due 10 June 2007
Resolved 5 June 2007
Navigation › Piloting/Steering › Marine Charts
Issued 2 June 2005 Resolved
Current navigational charts are outdated.
Due 2 July 2005
Resolved 8 June 2005
Resolution: Replaced with new charts.
Navigation › Piloting/Steering › Tide/Tidal Current Tables
Issued 2 June 2005 Resolved
No tidal current table publication o/b.
Due 2 July 2005
Resolved 8 June 2005
Resolution: Purchased new tidal current publication.
Lifesaving › Visual Distress Signals (General) › Marking
Issued 2 June 2005 Resolved
Pyrotechnic container not labeled.
Due 2 July 2005
Resolved 8 June 2005
Resolution: Pyrotechnic container was properly labeled.
Fire Fighting › Remote Fuel Shutoff › General
Issued 2 June 2005 Resolved
Red letter labeling for the portside emergency fuel shutoff needs to be relabeled.
Due 2 July 2005
Resolved 8 June 2005
Resolution: New lettering posted for fuel shtuoff.
Communications › Radio Communications › EPIRB
Issued 13 May 2004 Resolved
Provide proof of current hydrostatic release for EPIRB or renew.
Action required: 701 - Prior to carriage of passengers/cargo
Due 13 June 2004
Resolved 14 May 2004
Lifesaving › Lifejacket/PFD (General) › Quantity
Issued 13 May 2004 Resolved
Provide 2 additional lifejackets for a total of 28 adult lifejackets. Limited to 26 passangers until completed.
Due 13 June 2004
Resolved 14 May 2004
Operations/Management › Drills/Instruction
Issued 29 May 2002 Resolved
Log fire, man overboard drills and log epirb testing as required by 46 CFR 185.514 and 185.728 (c).
Action required: 705 - Other - as specified
Due 15 June 2002
Resolved 17 June 2002
Lifesaving
Issued 29 May 2002 Resolved
Replace expired hydrostatic release for epirb IAW 46 CFR 185.740. LEGACY COMPONENT DESC: Epirb
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 June 2002
Resolved 17 June 2002
Accommodation/Occupational Safety › Medical/First Aid
Issued 29 May 2002 Resolved
Replace expired items in first aid kit.
Action required: 705 - Other - as specified
Due 15 June 2002
Resolved 17 June 2002
Construction/Loadline
Issued 1 February 2001 Resolved
Provide metallic valves and penetrations for PVC piping traversing watertight bulkheads.
Condition: Unknown
Due 1 February 2001
Resolved 1 February 2001
Construction/Loadline
Issued 1 February 2001 Resolved
Provide damage control kit consisting of a mallet, various sized cone plugsand oakum in a labeled container/bag. Kit is to be stored in an accessible area above the bulkhead deck.
Condition: Unknown
Due 8 February 2001
Resolved 8 February 2001
Electrical
Issued 16 June 2000 Resolved
Provide plans & specifications for rewire of vessel. Include load analysis,wire types & connections, sizes, circuit protection, per 46 CFR subchapter "T". Include all existing and new components (pumps, lights, galley equipment, etc.)
Condition: Unknown
Due 16 June 2000
Resolved 16 June 2000
Construction/Loadline
Issued 28 May 1999 Resolved
Make after bulkhead of engine room water tight in way of exhaust and hole on port side of bulkhead.
Condition: Unknown
Due 28 May 1999
Resolved 28 May 1999
Fire Fighting
Issued 28 May 1999 Resolved
Install and make available for inspection an approved engine room fixed fire extinguishing system.
Condition: Unknown
Due 28 May 1999
Resolved 28 May 1999
Documentation
Issued 28 May 1999 Resolved
Provide current chart #18740 prior to carrying passengers.
Condition: Unknown
Due 7 June 1999
Resolved 7 June 1999
Construction/Loadline
Issued 28 May 1999 Resolved
Install metalic piping between sewage tank and overboard discharge in engine room in way of watertight at forward end of engine room.
Condition: Unknown
Due 28 May 1999
Resolved 28 May 1999
Navigation
Issued 28 May 1999 Resolved
Provide complete emergency radio placard.
Condition: Unknown
Due 7 June 1999
Resolved 7 June 1999
Documentation
Issued 28 May 1999 Resolved
Provide MARPOL garbage placard.
Condition: Unknown
Due 7 June 1999
Resolved 7 June 1999
Lifesaving
Issued 14 April 1999 Resolved
Vessel not prepared for inspection. Vessel's owner and operator are to prepare the vessel for inspection.
Condition: Unknown
Due 14 April 1999
Resolved 14 April 1999
Unknown
Issued 3 March 1998 Resolved
Make the fwd hatch watertight prior to carringh passengers.
Condition: Unknown
Due 26 March 1998
Resolved 26 March 1998
Unknown
Issued 20 January 1998 Resolved
Install pollution placard.
Condition: Unknown
Due 20 January 1998
Resolved 20 January 1998
Unknown
Issued 20 January 1998 Resolved
Check exhaust system for main engine.
Condition: Unknown
Due 20 January 1998
Resolved 20 January 1998
Unknown
Issued 20 January 1998 Resolved
Replace the water supply valve for the MSD, ensure the system works.
Condition: Unknown
Due 20 January 1998
Resolved 20 January 1998
Unknown
Issued 20 January 1998 Resolved
Get the manufacture or a certified rep to O.K. repairs done by the crew, orreplace all four life floats. (ensure that they meet 46CFR160.010)
Condition: Unknown
Due 20 January 1998
Resolved 20 January 1998
Unknown
Issued 20 January 1998 Resolved
Fix or repair the generator.
Condition: Unknown
Due 20 January 1998
Resolved 20 January 1998
Unknown
Issued 20 January 1998 Resolved
Run the main engine durning the revisit.
Condition: Unknown
Due 20 January 1998
Resolved 20 January 1998
Unknown
Issued 20 January 1998 Resolved
Do emergency drills.
Condition: Unknown
Due 20 January 1998
Resolved 20 January 1998
Unknown
Issued 20 January 1998 Resolved
Update drug testing with the vessel current crew.
Condition: Unknown
Due 20 January 1998
Resolved 20 January 1998
Unknown
Issued 20 January 1998 Resolved
Provide current documentation for the vessel.
Condition: Unknown
Due 20 January 1998
Resolved 20 January 1998
Unknown
Issued 20 January 1998 Resolved
Get an E.P.I.R.B.
Condition: Unknown
Due 20 January 1998
Resolved 20 January 1998
Unknown
Issued 20 January 1998 Resolved
Install an anchor light.
Condition: Unknown
Due 20 January 1998
Resolved 20 January 1998
Lifesaving
Issued 5 March 1997 Resolved
Replace lifering with an approved lifering, vessel may not carry passenger until completed.
Condition: Unknown
Due 5 March 1997
Resolved 5 March 1997
Lifesaving
Issued 5 March 1997 Resolved
Provide 4 more water lights for lifejackets prior to carring more than 37 passengers OCEANS route.
Condition: Unknown
Due 5 March 1997
Resolved 5 March 1997
Construction/Loadline
Issued 5 March 1997 Resolved
Install and test bilge pump prior to carring passengers.
Condition: Unknown
Due 5 March 1997
Resolved 5 March 1997
Lifesaving
Issued 5 March 1997 Resolved
Replace life floats with approved life floats. Vessel may not carry passengers until completed.
Condition: Unknown
Due 5 March 1997
Resolved 5 March 1997
Engineering
Issued 5 March 1997 Resolved
Repair the exhaust tube at the water injection.
Condition: Unknown
Due 5 March 1997
Resolved 5 March 1997
Lifesaving
Issued 19 January 1994 Resolved
PROVIDE 3 ADDITIONAL CG APPROVED TYPE I ADULT LIFEJACKETS PRIOR TO CARRYINGMORE THAN 41 ADULTS.
Condition: Unknown
Due 8 February 1994
Resolved 1 April 1994
Electrical
Issued 19 January 1994 Resolved
PROPERLY SECURE ALL ELECTRICAL CABLE AS NOTED DURING EXAM AS PER 46 CFR 183.05-.10
Condition: Unknown
Due 8 February 1994
Resolved 1 April 1994
Lifesaving
Issued 19 January 1994 Resolved
PROPERLY MARK LIFE FLOAT PADDLES.
Condition: Unknown
Due 8 February 1994
Resolved 1 April 1994
Fire Fighting
Issued 19 January 1994 Resolved
PROVIDE & INSTALL PROPER BRACKETS FOR ALL PORTABLE FIRE EXTINGUISHERS ON BOARD VESSEL.
Condition: Unknown
Due 8 February 1994
Resolved 1 April 1994
Engineering
Issued 19 January 1994 Resolved
PROVIDE & INSTALL PROPER FUEL PIPING FROM FUEL TANKS TO FUEL FILTERS & INSURE PROPER BONDING OF FUEL TANK & FILL PIPE AT NEXT VESSEL HAUL OUT PERIOD.
Condition: Unknown
Due 19 January 1994
Resolved 19 January 1994
Fire Fighting
Issued 4 January 1993 Resolved
PROVE PROPER OPERATION OF HAND FIRE BILGE PUMP.
Condition: Unknown
Due 4 January 1993
Resolved 4 January 1993
Lifesaving
Issued 4 January 1993 Resolved
REPAIR AND STENCIL LIFE FLOATS.
Condition: Unknown
Due 4 January 1993
Resolved 4 January 1993
Lifesaving
Issued 4 January 1993 Resolved
PROVIDE PADDLES 4 FT. OR LONGER FOR LIFE FLOATS.
Condition: Unknown
Due 4 January 1993
Resolved 4 January 1993
Electrical
Issued 4 January 1993 Resolved
PROVIDE MISSING SCREW TO SOLENOID ON PORT SIDE OF ENGINE.
Condition: Unknown
Due 4 January 1993
Resolved 4 January 1993
Lifesaving
Issued 4 January 1993 Resolved
PROVIDE PROPER LINE AND CONTAINER FOR LINE TO LIFE FLOATS ON THE STBD SIDE.
Condition: Unknown
Due 30 January 1993
Resolved 9 January 1993
Fire Fighting
Issued 4 January 1993 Resolved
REPAIR STBD EMERGENCY FUEL SHUT OFF VALVE.
Condition: Unknown
Due 30 January 1993
Resolved 9 January 1993
Electrical
Issued 4 January 1993 Resolved
PROVIDE MISSING BLANK FOR THE ENGIN ROOM ELECTRICAL BOX.
Condition: Unknown
Due 30 January 1993
Resolved 9 January 1993
Fire Fighting
Issued 4 January 1993 Resolved
REMOVE WIRING TO OLD ENGINE ROOM HALON SYSTEM.
Condition: Unknown
Due 30 January 1993
Resolved 9 January 1993
Engineering
Issued 4 January 1993 Resolved
BLANK OFF FUEL LINE OR VALVE TO OLD COMPRESSOR WHICH WAS INT HE LAZARETTE.
Condition: Unknown
Due 30 January 1993
Resolved 9 January 1993
Electrical
Issued 4 January 1993 Resolved
SECURE LOOS WIRING TO BATTERIES AND PROVIDE PROPER WIRE CONNECTONS.
Condition: Unknown
Due 4 January 1993
Resolved 4 January 1993
Lifesaving
Issued 4 January 1993 Resolved
REPAIR OR REPLACE WATERLIGHT WITH BROKEN PLASTIC COLLAR.
Condition: Unknown
Due 9 January 1993
Resolved 9 January 1993
Navigation
Issued 4 January 1993 Resolved
PROVIDE LENSE COVER FOR STERN LIGHT.
Condition: Unknown
Due 4 January 1993
Resolved 4 January 1993
Engineering
Issued 4 January 1993 Resolved
PROVIDE BELT GUARDS FOR ALL ENGINE BELTS ON THE MDE AND GENERATOR.
Condition: Unknown
Due 4 January 1993
Resolved 4 January 1993
Documentation
Issued 5 February 1991 Resolved
PROVIDE WASTE MANAGEMENT PLAN.
Condition: Unknown
Due 5 February 1991
Resolved 5 February 1991
Fire Fighting
Issued 5 February 1991 Resolved
FIT INSTALLED HALON SYSTEM WITH REMOTE MANUAL ACTUATION AND AUTOMATIC ENGINE SHUTDOWN.
Condition: Unknown
Due 5 February 1991
Resolved 5 February 1991
Documentation
Issued 5 February 1991 Resolved
PROVIDE DRUG FREE TESTING CERTIFICATE.
Condition: Unknown
Due 5 February 1991
Resolved 5 February 1991
Navigation
Issued 5 February 1991 Resolved
PROVIDE COMPASS DEVIATION CARD.
Condition: Unknown
Due 5 February 1991
Resolved 5 February 1991
Lifesaving
Issued 8 January 1990 Resolved
HAVE EPIRB SERVICED. BATTERY EXPIRED 6/89.
Condition: Unknown
Due 8 January 1990
Resolved 8 January 1990
Lifesaving
Issued 8 January 1990 Resolved
PROVIDE 8 ADULT LIFEJACKETS WITH WORKING LIGHTS. VESSEL IS RESTRICTED TO 37 ADULTS UNTIL THESE ARE PROVIDED.
Condition: Unknown
Due 8 January 1990
Resolved 8 January 1990
Electrical
Issued 8 January 1990 Resolved
PROVIDE ONE ADDITIONAL EMERGENCY FLASHLIGHT.
Condition: Unknown
Due 8 January 1990
Resolved 8 January 1990
Construction/Loadline
Issued 29 August 1989 Resolved
ATTACH KEEPER CHAIN TO SCUTTLE TO FORE PEAK COMPARTMENT.
Condition: Unknown
Due 29 August 1989
Resolved 29 August 1989
Construction/Loadline
Issued 29 August 1989 Resolved
SEAL MAIN DECK AROUND BOTH AIR INTAKES FOR THE ENGINEROOM TO PREVENT SEA WATER FROM ENTERING.
Condition: Unknown
Due 29 August 1989
Resolved 29 August 1989
Engineering
Issued 29 August 1989 Resolved
CLEAN RUST AND SCALE FROM FUEL TANKS AND REPAINT.
Condition: Unknown
Due 29 August 1989
Resolved 29 August 1989
Construction/Loadline
Issued 29 August 1989 Resolved
CLEAN AND TREAT OVERHEAD IN THE ENGINEROOM AROUND VENT INTAKES.
Condition: Unknown
Due 29 August 1989
Resolved 29 August 1989
Documentation
Issued 10 January 1989 Resolved
PROVIDE FCC RADIOTELEPHONY SAFETY CERTIFICATE.
Condition: Unknown
Due 10 January 1989
Resolved 10 January 1989
Engineering
Issued 10 January 1989 Resolved
REPAIR PORTABLE BILGE PUMP.
Condition: Unknown
Due 10 January 1989
Resolved 10 January 1989
Engineering
Issued 10 January 1989 Resolved
PROVIDE FLASH BASINS FOR RACOR FUEL FILTER ON MDE.
Condition: Unknown
Due 10 January 1989
Resolved 10 January 1989
Construction/Loadline
Issued 10 January 1989 Resolved
PROVIDE LASH-DOWN DEVICES FOR E/R HATCH COVER.
Condition: Unknown
Due 10 January 1989
Resolved 10 January 1989
Lifesaving
Issued 10 January 1989 Resolved
REPLAACE MAN LINES ON ALL LIFE FLOATS.
Condition: Unknown
Due 10 January 1989
Resolved 10 January 1989
Lifesaving
Issued 10 January 1989 Resolved
ATTACH WEAK LINK OF PROPER SIZE TO LIFE FLOATS.
Condition: Unknown
Due 10 January 1989
Resolved 10 January 1989
Lifesaving
Issued 10 January 1989 Resolved
MARRY TOGETHER LIFE FLOATS.
Condition: Unknown
Due 10 January 1989
Resolved 10 January 1989
Navigation
Issued 10 January 1989 Resolved
PAINT VESSEL'S NAME ON EPIRB.
Condition: Unknown
Due 10 January 1989
Resolved 10 January 1989
Engineering
Issued 10 January 1989 Resolved
INSTALL FLAME SCREENS ON BOTH FUEL TANK VENTS.
Condition: Unknown
Due 10 January 1989
Resolved 10 January 1989
Navigation
Issued 10 January 1989 Resolved
INSTALL SSB RADIO FOR OCEANS ROUTE.
Condition: Unknown
Due 10 January 1989
Resolved 10 January 1989
Construction/Loadline
Issued 3 February 1988 Resolved
MAKE HATCH COVER TO CHAIN LOCKER EITHER WATERTIGHT WITH APPROVED WATERTIGHTCLOSURE OR WATERTIGHT BY RAISING OPENING 12" OFF DECK AND PROVIDING MEANS TO CLOSE HATCH AS PER 46 CFR 171.124.
Condition: Unknown
Due 3 February 1988
Resolved 3 February 1988
Construction/Loadline
Issued 3 February 1988 Resolved
PLUG TWO HOLES IN AFT ENGINEROOM BULKHEAD.
Condition: Unknown
Due 3 February 1988
Resolved 3 February 1988
Electrical
Issued 10 January 1988 Resolved
PROVIDE TWO (2) WORKING FLASHLIGHTS.
Condition: Unknown
Due 10 January 1988
Resolved 10 January 1988
Engineering
Issued 10 January 1988 Resolved
REPAIR OIL LEAKS ON MAIN ENGINE AFT CAM COVERS.
Condition: Unknown
Due 10 January 1988
Resolved 10 January 1988
Fire Fighting
Issued 10 January 1988 Resolved
PROVIDE GUARD OVER PULLEY FOR FIRE PUMP.
Condition: Unknown
Due 10 January 1988
Resolved 10 January 1988
Electrical
Issued 10 January 1988 Resolved
REPAIR BATTERY CHARGER.
Condition: Unknown
Due 10 January 1988
Resolved 10 January 1988
Engineering
Issued 10 January 1988 Resolved
CLEAN OIL FROM ENGINEROOM BILGES.
Condition: Unknown
Due 10 January 1988
Resolved 10 January 1988
Accommodation/Occupational Safety
Issued 10 January 1988 Resolved
PROVIDE POLLUTION PREVENTION SIGN OR LOCK VLAVES FOR MSD CLOSED.
Condition: Unknown
Due 10 January 1988
Resolved 10 January 1988
Navigation
Issued 10 January 1988 Resolved
REPAIR HAND MIKE FOR VHF RADIO.
Condition: Unknown
Due 10 January 1988
Resolved 10 January 1988
Electrical
Issued 10 January 1988 Resolved
REPAIR ALL OIL LEAKS ON AUX GENERATOR.
Condition: Unknown
Due 10 January 1988
Resolved 10 January 1988
Deck/Cargo
Issued 10 January 1988 Resolved
REMOUNT CHAIN GUIDE FOR ANCHOR LINE TO ANCHOR LOCKER.
Condition: Unknown
Due 10 January 1988
Resolved 10 January 1988
Electrical
Issued 10 January 1988 Resolved
INSTALL JUNCTION BOX ON PALMER GENERATOR.
Condition: Unknown
Due 10 January 1988
Resolved 10 January 1988
Navigation
Issued 23 January 1987 Resolved
REPLACE EPIRB BATTERY AND PROVE SATISFACTORY OPERATION.
Condition: Unknown
Due 23 January 1987
Resolved 23 January 1987
Engineering
Issued 23 January 1987 Resolved
PROPERLY MARK EMERGENCY FUEL SHUTOFF VALVE LOCATION.
Condition: Unknown
Due 23 January 1987
Resolved 23 January 1987
Navigation
Issued 23 January 1987 Resolved
INSTALL PROPER STERN LIGHT AS PER RULE 23 INTERNATIONAL RULES OF THE ROAD
Condition: Unknown
Due 23 January 1987
Resolved 23 January 1987
Fire Fighting
Issued 23 January 1987 Resolved
PROVIDE NOZZLE (BRASS) TO FIREHOSE.
Condition: Unknown
Due 23 January 1987
Resolved 23 January 1987
Lifesaving
Issued 23 January 1987 Resolved
REPLACE LIFELINES ON LIFEFLOATS AS NEEDED.
Condition: Unknown
Due 23 January 1987
Resolved 23 January 1987
Navigation
Issued 23 January 1987 Resolved
INSTALL AND PROVE OPERATION OF SINGLE SIDE BAND RADIO AND PROVE OPERATION OF 2182 DISTRESS FREQUENCY.
Condition: Unknown
Due 23 January 1987
Resolved 23 January 1987
Engineering
Issued 23 January 1987 Resolved
REPAIR PORT EMERGENCY FUEL SHUTOFF REACH ROD.
Condition: Unknown
Due 23 January 1987
Resolved 23 January 1987
Navigation
Issued 23 January 1987 Resolved
REPLACE SIDE LIGHTS LENS PORT & STBD
Condition: Unknown
Due 23 January 1987
Resolved 23 January 1987
Engineering
Issued 23 January 1987 Resolved
MAKE PERMANENT REPAIRS TO EMERGENCY FUEL SHUTOFFS WITH ENCLOSED UNITS.
Condition: Unknown
Due 23 January 1987
Resolved 23 January 1987
Lifesaving
Issued 23 January 1987 Resolved
VESSEL IS RESTRICTED TO 26 ADULT PASSENGERS UNTIL 17 ADDITIONAL PFDS ARE PROVIDED.
Condition: Unknown
Due 23 January 1987
Resolved 23 January 1987
Engineering
Issued 23 January 1987 Resolved
REPLACE/REPAIR TACHOMETER & AUX GENERATOR OIL PRESSURE GUAGE.
Condition: Unknown
Due 23 January 1987
Resolved 23 January 1987
Lifesaving
Issued 9 January 1986 Resolved
REPLACE OR REPAIR ONE WATERLIGHT FOR 1 OF THE 4 LIFEFLOATS AND PROVE SAT OPERATION.
Condition: Unknown
Due 9 January 1986
Resolved 9 January 1986
Lifesaving
Issued 9 January 1986 Resolved
PROVIDE 14 ADDITIONAL ADULT PFD'S AND 1 ADDITIONAL CHILD PFD WITH APPROVED LIGHTS, STENCIL, AND REFLECTIVE TAPE
Condition: Unknown
Due 9 January 1986
Resolved 9 January 1986
Engineering
Issued 9 January 1986 Resolved
PERMENENTLY REPAIR EXHAUST LEAKS IN PORT AND STBD EXHAUST LINES AND PROVE SAT OPERATION.
Condition: Unknown
Due 9 January 1986
Resolved 9 January 1986
Engineering
Issued 4 December 1984 Resolved
SUBMIT PROPOSAL FOR REPAIRS TO EXPANTION TANK ON MAIN ENGINE.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Engineering
Issued 4 December 1984 Resolved
CONDUCT OPERATIONAL TEST 29 JAN 85.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Deck/Cargo
Issued 4 December 1984 Resolved
UNPLUG FUEL OIL VENT STBD SIDE.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Construction/Loadline
Issued 4 December 1984 Resolved
REPLACE THREE THREW HULL VALVES. A. EXHAUST PORT SIDE MAIN ENGINE,B. MAIN ENGINE SEA WATER COOLING,C. BILGE PUMP OVERBOARD DISCHARGE.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Engineering
Issued 4 December 1984 Resolved
NON-DESTRUCTIVE TEST PROPELLER SHAFT IN AREA OF KEYWAY.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Construction/Loadline
Issued 4 December 1984 Resolved
REPLACE WITH A INSERT OF BOTTOM PLYWOOD ALONG KEEL PORT SIDE APPROX 4 FOOT FWD OF END OF KEEL WITH A 4 INCH BY 12 INCH PLYWOOD.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Navigation
Issued 4 December 1984 Resolved
REPAIR ANCHOR LIGHT
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Lifesaving
Issued 4 December 1984 Resolved
REPAIR RING BOUY AND WATERLIGHT STBD SIDE.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Lifesaving
Issued 4 December 1984 Resolved
PROPERLY INSTALL SEA PAINTER TO LIFEFLOATS.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Engineering
Issued 4 December 1984 Resolved
INSTALL NEW AFT CUTLESS BEARING.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Lifesaving
Issued 4 December 1984 Resolved
POCURE 6 RED FLARES.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Construction/Loadline
Issued 4 December 1984 Resolved
REPAIR BROKEN WINDOW STBD WHEELHOUSE.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Lifesaving
Issued 4 December 1984 Resolved
INSTALL REFLECTIVE TAPE AND STENCIL NAME ON LIFEFLOATS.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Construction/Loadline
Issued 4 December 1984 Resolved
INSTALL CHAIN TO FWD HATCH COVER.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Electrical
Issued 4 December 1984 Resolved
REMOVE OR PEPAIR WIRES TO SPOTLIGHT.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Electrical
Issued 4 December 1984 Resolved
REMOVE ALL ELECTRICAL WIRES LESS THAN 14AWG AND INSTALL WITH 14AWG OR LARGER ON BILGE PUMPS.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Navigation
Issued 4 December 1984 Resolved
INSTALL SNAP RING TO AFT STEERING PIN.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984
Construction/Loadline
Issued 4 December 1984 Resolved
REPLACE 2 HOSE CLAMP DECK DRAIN FWD OVERBOARD.
Condition: Unknown
Due 4 December 1984
Resolved 4 December 1984

Casualty record · 4

6 September 2011Routine · role: Involved in a Marine Casualty · activity 4140205
3 March 2022Routine · role: Involved in a Marine Casualty · activity 7560458
29 March 2024Routine · role: Involved in a Marine Casualty · activity 7889974
16 July 2024Routine · role: Involved in a Marine Casualty · activity 8044423
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it, and the bridge, lock or dam the investigation names where it names one. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.