Records in 2002. Most recent: inspection, 3 April 2002.
A report is not offered for this hull: Its Coast Guard record spans fewer than two calendar years. That is a statement about the record, not about the vessel. Reports.
Fire Fighting › Structural - A Class Divisions
Issued 20 March 2002
Resolved
Fire door between engine room and steering gear room does not properly latch, creating a fire hazard and preventing proper functioning of the CO2 fixed firefighting system. LEGACY COMPONENT DESC: Openings - Fire Doors
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 20 April 2002
Resolved 3 April 2002
Resolution: Corrected
Fire Fighting › Fire Pumps
Issued 20 March 2002
Resolved
Vessel is only fitted with 1 power fire pump, while SOLAS 74 II-2/52(b) requires two power pumps on cargo ships of 1000 gross tonnage and upwards. LEGACY COMPONENT DESC: Arrangement
Action required: 17 - Rectify deficiencies prior to departure
Resolved 21 March 2002
Resolution: Obtained letter from KRSclass citing error in tonnage given on Safety Construction Certificate. Class has opted to applying register tonnage of 829 GT vice ITC tonnage of 1978 GT for purpose of applying SOLAS requirements per IMO resolution A758(18).
Fire Fighting › Fire Main
Issued 20 March 2002
Resolved
Fire main piping on the starboard main deck in the vicinity of cargo hatch #2 has a temporary patch that is leaking. LEGACY COMPONENT DESC: Condition
Condition: Unknown
Action required: 705 - Other - as specified
Due 20 April 2002
Resolved 3 April 2002
Resolution: Corrected
Lifesaving › Launching Appliances
Issued 20 March 2002
Resolved
The port lifeboat davit does not properly lower the port lifeboat by gravity and brake alone. The davit system is not maintained in working order and available for immediate use per SOLAS 74 III/4(c). LEGACY COMPONENT DESC: Davit
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 March 2002
Resolution: KRS representative and MSD Sitka personnel witnessed sat test of davit; COTP order rescinded.
Accommodation/Occupational Safety › Occupational Safety
Issued 20 March 2002
Resolved
No face or eye protection was provided in vicinity of battery room to protect crew from acid splash injuries.
Condition: Unknown
Due 20 March 2002
Resolved 20 March 2002
Resolution: Safety glasses were provided as an interim measure; strongly recommended that chemical splash goggles and/or faceshields be provided.
Fire Fighting › Nozzles › Condition
Issued 20 March 2002
Resolved
Several fire nozzles were siezed such that the spray pattern could not be adjusted.
Condition: Improper/Lack of Maintenance
Due 20 March 2002
Resolved 20 March 2002
Resolution: Corrected on site.
Electrical › Electrical Distribution System (service) › Wiring
Issued 20 March 2002
Resolved
A detached junction box with loose and intermittently shorting electrical wiring was found serving a lighting fixture over near a ladder serving the upper level engine room.
Condition: Damaged By Earlier Event
Due 20 March 2002
Resolved 20 March 2002
Resolution: Corrected on site.
Engineering › Steering Gear System › Rudder Angle Indicator
Issued 20 March 2002
Resolved
The fixed rudder angle indicator in the steering gear room had become loose and no longer gave a correct indication for emergency steering.
Condition: Improper/Lack of Maintenance
Due 20 March 2002
Resolved 20 March 2002
Resolution: Corrected on sight.