Records from 2016 to 2022. Most recent: inspection, 10 February 2022.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 4 November 2020
Resolved
Supply vent to engine room leading from main deck starboard passageway locker down to engine room is wasted and holed. Boundary decks separating the accommodations and machinery spaces, shall be of ‘‘A’’ Class construction. Make permanent and proper repairs.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 December 2020
Resolved 29 December 2020
Resolution: Resolved
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 4 November 2020
Resolved
The exit door leading out of the pilot lounge to open deck on the main deck port side is missing the handle and is not easily opened. There shall be means of escape from all areas accessible to the crew.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 December 2020
Resolved 29 December 2020
Resolution: Resolved
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 4 November 2020
Resolved
Electric installations on vessels must ensure: Protection of passengers, crew, other persons, and the vessel from electrical hazards. Vessel was found with ground on 120V ship service electrical system.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 December 2020
Resolved 29 December 2020
Resolution: Resolved
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 4 November 2020
Resolved
All pressure vessels must be provided with protective devices. The protective devices must be in accordance with the requirements of UG-125 through UG-136 of section VIII of the ASME Boiler and Pressure Vessel Code (incorporated by reference; see 46 CFR 54.01-1) except as modified in this subpart. Vessel start air receivers were found with relief valves that were not designed for intended purpose.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 December 2020
Resolved 29 December 2020
Resolution: Resolved
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 2 October 2020
Resolved
All automatically or remotely controlled or monitored vital systems addressed by part 62 of this sub-chapter must be subjected to tests and inspections to evaluate the operation and reliability of controls, alarms, safety features, and interlocks. Test procedures must be submitted to the Coast Guard for approval. Vessel reverse power relay test for auxiliary engine, diesel generator No. 2 was not conducted. High jacket water alarm/shut down for auxiliary engines was not conducted.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 December 2020
Resolved 28 December 2020
Resolution: Resolved
01 - Certificates & Documentation › 012 - Crew Certificates › Record of employment
Issued 3 December 2018
Resolved
Provide proof that the crew of the vessel are enrolled in a drug/alcohol testing program meeting DOT 49CFR40 and 46CFR16
Action required: 10 - Deficiency Rectified
Resolved 18 December 2018
03 - Water/Weathertight Conditions › N/A - No Subsystem › Windows, sidescuttles and deadlights
Issued 3 December 2018
Resolved
Port and starboard windows are leaking and not weather tight. Conduct a hose test in presence of USCG Inspector
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
Resolution: witnessed hose test
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 3 December 2018
Resolved
All attachments and fittings, if synthetic, a dark color or certified by the manufacturer to be resistant to deterioration from ultraviolet light.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
09 - Working and Living Conditions › 091 - Living Conditions › Electrical devices
Issued 3 December 2018
Resolved
There are stuffing tubes on the outside of the vessel that need to be made weather tight and repacked. Above port bridge door and open deck above bridge port side.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 3 December 2018
Resolved
Some of the navigation lights still have over spray from the dry-dock remove all the over spray
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 3 December 2018
Resolved
Ensure all emergency equipment is labeled as per 46CFR97.37
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 3 December 2018
Resolved
Escape platform out of engine room is blocked, clear items from port side main deck platform.
Action required: 10 - Deficiency Rectified
Resolved 3 December 2018
Resolution: Cleared while onboard
09 - Working and Living Conditions › 091 - Living Conditions › Electrical devices
Issued 3 December 2018
Resolved
The walk in freezer has open electrical boxes and spliced extension cord to heating pad. Ensure all wire connections are safe and don't create a hazardous/electrical shock.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
09 - Working and Living Conditions › 091 - Living Conditions › Electrical devices
Issued 3 December 2018
Resolved
Clean behind freezer chest and provide a outlet for the power versus a exstenion cord
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 3 December 2018
Resolved
Stateroom #14 and #12 are being used as storeroom, remove all the supplies and store them in a proper storeroom.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
Resolution: Was in the process of cleaning out while onboard
09 - Working and Living Conditions › 091 - Living Conditions › Cleanliness
Issued 3 December 2018
Resolved
Clean the galley exhaust vent, grease traps, soup warmers and remove all food particles crumbs and expired foods.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
Resolution: Cleaners missed under hood, crew cleaned while onboard
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 3 December 2018
Resolved
Properly stow the port/starboard rescue boats and demonstrate launching and recovery.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
Resolution: Crew was adding retro to the bottom of boat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 3 December 2018
Resolved
Vessel must show compliance with 46CFR61&62 and have approved periodic safety test procedures (PSTP).
Action required: 705 - Other - as specified
Due 18 March 2019
Resolved 4 November 2020
Resolution: Prove that it has been submitted, then may extend the deficiency. Cleared as directed by Kovery
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 3 December 2018
Resolved
Vessel has a fuel leak at the purifier, must repair this leak and clean all fuel from the bilge.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 3 December 2018
Resolved
Gen set #2 must show it can hold the electrical load and perform required test as discussed.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 3 December 2018
Resolved
Vessel's emergency gen set intake louver is frozen shut and must be repaired to new condition.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 3 December 2018
Resolved
Prove proper operation of bilge pump and emergency suction line.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 3 December 2018
Resolved
Portable fire extinguishers must have monthly checks and logged on inspection cards.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 January 2019
Resolved 18 December 2018
14 - Pollution Prevention › 144 - MARPOL Annex IV (Not Applicable to PSC Exams conducted in the U.S.) › Other (MARPOL Annex IV)
Issued 3 December 2018
Resolved
Prove proper operation of sewage overboard discharge valve and this valve must remain closed and locked with-in 3 miles unless proper operation of MSD type II device works properly.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 December 2018
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 3 December 2018
Resolved
Instruction on how to operate the watertight doors need to be posted in vicinity of the 3 WTDs. Also need steering change over instructions. (Simple instructions)
Due 1 January 2019
Resolved 4 February 2019
Lifesaving › Launching Appliances › Falls
Issued 2 September 2016
Resolved
Vessel has not provided documentation of rescue boat fall renewal being conducted or davit weight testing since 2008. Provide proper documentation attesting to renewal and davit testing or replace falls and conduct weight test for the port and starboard rescue boats. While on station a support vessel must be identified and be in the vicinity to provide rescue boat capabilities at all times.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 12 September 2016
Resolution: New wire was purchased, placed into service, and weight test were conducted.
Engineering › Steam System (auxiliary) › Lagging/Insulation
Issued 31 August 2016
Resolved
Lagging is missing on the boiler exhaust piping. Need to properly insulate the exhuast piping.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 14 September 2016
Resolution: replaced lagging
Engineering › Diesel Engine (propulsion-reduction gear) › Exhaust Manifold
Issued 31 August 2016
Resolved
Lagging is missing on the port main engine exhaust piping. Properly insulate exhaust piping.
Condition: Invalid
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 14 September 2016
Pollution Prevention/Response › Prevention Equipment › Oily Water Separator (15 ppm)
Issued 31 August 2016
Resolved
Oily water Seperator is not operating properly. Make repairs to equipment and prove proper operation.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 2 September 2016
Resolution: Verified and tested operational.
Electrical › Electrical Distribution System (service) › Cable
Issued 31 August 2016
Resolved
Armored cabling on the controller for the sewage system is not properly installed. The cable needs to be properly terminated to the controller.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 14 September 2016
Resolution: cable was terminated correctly
Engineering › Compressed Air System (start air) › Control Gear
Issued 31 August 2016
Resolved
The relief valve on the whistle tank is not working properly. Replace valve and conduct test of the new relief valve.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 14 September 2016
Resolution: new relief valve was installed
Electrical › Electrical Distribution System (service) › Non-conducting Deck Covering
Issued 31 August 2016
Resolved
The electrical matting is missing in front of the main switchboard. Need to install electrical matting in front of the switchboard.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 14 September 2016
Resolution: matting was placed in front of switchboard
Engineering › Fuel Oil Service System › Valve, Control
Issued 31 August 2016
Resolved
The remote fuel shutoff's are siezed for the diesel engine service tank. Need to make repairs and prove proper operation.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 12 September 2016
Resolution: remote fuel vavle is operational.
Accommodation/Occupational Safety › Ventilation › General
Issued 31 August 2016
Resolved
The air dampeners for the emergency generator room do not close. Make repairs and prove proper operation.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 12 September 2016
Resolution: dampners are opening and closing as design.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 31 August 2016
Resolved
The CO2 pressure switch in the Emergency Generator Room is not properly working. Have the pressure switch fixed and prove proper operation.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 14 September 2016
Electrical › Electric Generation Source (service) › Generator
Issued 31 August 2016
Resolved
The overspeed on the aft generator does not work properly. Make repairs and prove proper operation.
Condition: Invalid
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 31 August 2016
Resolution: The overspeed switch assembly for the generator was broken. CAT tech rep installed a new one, test sat.
Pollution Prevention/Response › Prevention Equipment › Sewage System Piping
Issued 31 August 2016
Resolved
Replace the man made sight glass on the sewage drain line with pipe fitting of similiar material and meeting approved piping standard.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 14 September 2016
Resolution: vessel replaced with a blank flange
Lifesaving › Lifejacket/PFD (Type I) › Condition
Issued 31 August 2016
Resolved
Lifejackets and immersion suits must be fitted with retro reflective tape, lights, and whistles. Replace the above mentioned attachments. Maximum persons allowed is reduced to 41 until rectified. 46 CFR 199.70(b)&(c)
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 12 September 2016
Resolution: All lights were replaced on life jackets and immersion suits. Retro tape was placed on the required life jackets.
Operations/Management › Drills/Instruction › Fire
Issued 31 August 2016
Resolved
Fire drills are required to be conducted at least once a month by all crewmembers. Fire drills had not been conducted for over 03 months. Vessel must conduct drills. 46 CFR 97.15-35 and 46 CFR 199.180(c)(2)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 15 September 2016
Resolved 12 September 2016
Resolution: Drills were conducted and logged by the crew, and a fire and abandonned ship drill was conducted during the COI.
Stability › Watertight Integrity › Watertight Subdivision Standard
Issued 31 August 2016
Resolved
Watertight door at frame 65 has inoperable status indication light on the Bridge and cannot close manually locally. Prove proper operation prior to getting underway. 46 CFR 170.270(e) and 46 CFR 170.270(C)(2)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 2 September 2016
Resolution: Tested frame 65 WT door all controls and alarms verified operational.
Stability › Weathertight Integrity › General
Issued 31 August 2016
Resolved
Forward escape hatch to forecastle was found not weathertight. Replace gasket and ensure no gaps present. 46 CFR 42.15-30(a)
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 12 September 2016
Resolution: Weather stip was replaced and verified weather tight.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 31 August 2016
Resolved
Verify location and proper operation and marking of all emergency lighting. 46 CFR 97.15-30
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 2 September 2016
Resolution: Verified all emergency lighting using the electrical diagram as reference, All tested and labeled satisfactory.
Operations/Management › Drills/Instruction › Launching/Recovery of Survival Craft
Issued 31 August 2016
Resolved
Repost liferaft launching instructions at the embarkation station. 46 CFR 199.90
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 September 2016
Resolution: Placard placed in vicinity of emabrkation.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 31 August 2016
Resolved
Replace lenses over sprayed with paint on the port and starboard navigation lights. Lights must meet UL 1104. 46 CFR 111.75-17
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 12 September 2016
Resolution: Lenses were replaced with new approved lenses.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 31 August 2016
Resolved
Stern and anchor light failure alarms inaudible on bridge indicator panel. 46 CFR 111.75-17(b)
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 2 September 2016
Resolution: Tested navigation lights, two lights were replaced. All satisfactory.
Accommodation/Occupational Safety › Sleeping Accommodations › Berth
Issued 31 August 2016
Resolved
Ensure all berthing lights are operating and replace missing covers for light fixtures. 46 CFR 92.20-45
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 14 September 2016
Resolved 12 September 2016
Resolution: suficient light covers were replaced in all sleeping accomodations.