MAURY USCG vessel records
← All vessels

DELIVERANCE

DELIVERANCE is a 1977 passenger vessel (inspected). The Coast Guard has recorded 17 inspections since 2016, most recently in March 2023, along with 32 deficiencies — 6 with no resolution recorded — and 3 operational controls.

Records from 2016 to 2023. Most recent: inspection, 1 March 2023.

Built
1977
Last inspected
1 March 2023
Documentation
Not in the documentation file of 10 August 2026
Controls
None recorded without a removal date

This record may be incomplete: the most recent inspection recorded for this vessel was 3 years ago. Maury shows what the Coast Guard recorded, not whether the vessel has been inspected since, is still in service, or what condition it is in. Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 1 March 2023
…with no type recorded3
…past their stated due date6
Operational controls None recorded without a removal date
Years with a record 7 calendar years (2016–2023)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

WDD6974
Flag
UNITED STATES
Maury page id
psix-49472

Documentation record

Tonnage as PSIX records it12 - Regulatory (Subpart C or D), Gross Ton
10 - Regulatory (Subpart C or D), Net Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 2016 to 2026 for this class, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 17

1 March 2023 Drydock Exam · Deficiency Check · Administrative Inspection
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 7642993
28 April 2022 Deficiency Check · COI Inspection
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 7435891
30 September 2021 Deficiency Check
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 7324446
25 August 2021 Deficiency Check · Drydock Exam
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 7281637
21 June 2021 Deficiency Check · Annual Inspection
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 7231621
21 July 2020 DAPI Audit · Administrative Inspection · Annual Inspection
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 7011069
24 October 2019 Drydock Exam
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 6840863
22 October 2019 Administrative Inspection
Administrative · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 6839402
14 August 2019 Examination of Repairs
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 6783146
11 August 2019 Type not recorded
No type recorded · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 6783131
22 April 2019 DAPI Audit · Annual Inspection
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 6662596
12 April 2019 Administrative Inspection · Deficiency Check
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 6661197
25 October 2017 In-Service Inspection
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 6295200
28 April 2017 COI Inspection · DAPI Audit
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 6131207
10 August 2016 Annual Inspection · DAPI Audit
Physical examination · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 5968548
24 May 2016 Type not recorded
No type recorded · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 5885597
11 May 2016 Type not recorded
No type recorded · Resident Inspection Office St. Croix · USCG Southeast District (CGD-SE) · Activity 5874686

Deficiency record · 32

01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 2 March 2023 No resolution recorded
Each vessel must be marked as required by part 67, subpart I, of this chapter. Hull markings have been removed from vessel.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 April 2023 — due date passed with no resolution recorded
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 2 March 2023 No resolution recorded
The discharge ends of vent pipes shall be fitted with removable flame screens or flame arresters. The flame screen shall consist of a single screen of corrosion resistant wire of at least 30 x 30 mesh. Replace missing vent screen.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 April 2023 — due date passed with no resolution recorded
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 2 March 2023 No resolution recorded
Non metallic exhaust hoses may be used, provided it is especially adapted to resist the action of collapsing or panting, and is doubled clamped where practicable. Repair/ replace clamps on Exhaust hose.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 April 2023 — due date passed with no resolution recorded
09 - Working and Living Conditions › 091 - Living Conditions › Water, pipes, tanks
Issued 2 March 2023 No resolution recorded
At each inspection for certification the owner shall have all items available. Potable water tank on STBD side of vessel need to be mounted correctly. Strap has broken and needs to be replaced.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 April 2023 — due date passed with no resolution recorded
03 - Water/Weathertight Conditions › N/A - No Subsystem › Manholes/flush scuttles
Issued 2 March 2023 No resolution recorded
Inspection and operation of all water tight closures in the hull and decks. FWD hatch AFT of engine compartment is missing arm and needs to be repaired/replaced. Also gaskets on all hatches have to be fitted correctly.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 April 2023 — due date passed with no resolution recorded
02 - Structural Conditions › N/A - No Subsystem › Bulkhead strength
Issued 2 March 2023 No resolution recorded
Inspection of all accessible parts of the interior of the hull. Engine room access door under ladder has to be remounted.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 April 2023 — due date passed with no resolution recorded
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 28 April 2022 Resolved
Gages to indicate engine cooling water discharge temp. and lubricating oil pressure shall be provided for all propulsion engines and located so as to be in view of the operator. Engine temperature gauge is not working.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2022
Resolved 26 May 2022
Resolution: New gauges have been installed and tested SAT.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 28 April 2022 Resolved
All life preservers shall be marked with vessel's name. Life jackets on board vessel have another vessel's name labeled on them.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2022
Resolved 29 April 2022
Resolution: Relabeled jackets correctly.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance and inspections
Issued 28 April 2022 Resolved
All vessels shall be fitted with one life ring life buoy of not less than 24 inches in diameter. Vessel life ring buoy is in a dilapidated condition.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2022
Resolved 29 April 2022
Resolution: Purchased new life ring.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 28 April 2022 Resolved
Each portable fire extinguisher on a vessel must be of an approved type. One of the 3 portable extinguishers has not had it's annual inspection.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2022
Resolved 9 May 2022
Resolution: new extinguisher has been purchased.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 30 September 2021 Resolved
Gages to indicate engine cooling water discharge temperature and lubricating oil pressure shall be provided for all propulsion engines and located so to be view of the operator.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 October 2021
Resolved 30 November 2021
Resolution: Received photo documentation of the part for repair has been ordered and paid for.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 21 June 2021 Resolved
AN ADULT LIFE JACKET MUST BE PROVIDED FOR EACH PERSON CARRIED ONBOARD A VESSEL. 17 ADULT LIFE JACKETS WERE FOUND TO BE DILABIDATED.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 July 2021
Resolved 21 July 2021
Resolution: Life jackets have been purchased and on board.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 21 June 2021 Resolved
STATE NUMBERS MUST BE PAINTED ON OR PERMANENTLY ATTACHED TO EACH SIDE OF THE FORWARD HALF OF THE VESSEL. THE STATE NUMBERS NEED TO BE MARKED.
Condition: Invalid
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 July 2021
Resolved 21 July 2021
Resolution: State numbers have been painted on the vessel.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 21 June 2021 Resolved
LIFE BUOYS MUST HAVE SUFFICIENT REFLECTIVE TAPE AT FOUR EVENLY-SPACED POINTS ON THE LIFE BUOY. THE REFLECTIVE TAPE ON THE LIFBUOY DOES NOT SUFFICIENTLY REFLECT LIGHT AND WAS PLACED AT 3 EVENLY SPACED POINTS.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 July 2021
Resolved 21 July 2021
Resolution: Retro tape has been applied to the life buoy.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 24 July 2020 Resolved
Pre engineered fixed gas fire extinguishing system and portable fire extinguishers were not within servicing date.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 24 July 2020
Resolved 21 June 2021
Resolution: ALL FIRE EXTINGUISHING SYSTEMS HAD BEEN RE-INSPECTED.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 24 July 2020 Resolved
Port side emergency fuel shut off valve was broken and not connected properly.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 24 July 2020
Resolved 21 June 2021
Resolution: TESTED FUEL SHUT OFF VALVE. FOUND SAT.
05 - Radio Communications › N/A - No Subsystem › Operation/maintenance
Issued 24 July 2020 Resolved
FCC station license and radio safety certificate were expired.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 August 2020
Resolved 21 June 2021
Resolution: LICENSE AND CERTIFICATES FOUND VAILD.
08 - Alarms › N/A - No Subsystem › Emergency signal
Issued 24 July 2020 Resolved
Pyrotechnics were expired.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 24 July 2020
Resolved 21 June 2021
Resolution: ALL REQUIRED PYROTECHNICS FOUND VALID.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 24 July 2020 Resolved
Aft bilge alarm not working.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 24 July 2020
Resolved 21 June 2021
Resolution: CONDUCTED SATISFACTORY TEST OF AFT BILGE ALARM.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 22 October 2019 Resolved
Owner or managing operator shall make a vessel available for drydock examinations. vessel that is exposed to salt water more than 3 months in any 12 month period must undergo a drydock examination once every 2 years. Vessel was due for drydock on 31AUG2019, and was not completed. Vessel must undergo drydock prior to movement. 46 CFR 176.600(c)(1); 60c
Condition: Invalid
Action required: 60 - Rectify deficiencies prior to movement
Resolved 4 November 2019
Resolution: Drydock completed.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 22 April 2019 Resolved
(03) PFD's were beyond their useful service life.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 22 April 2019
Resolved 22 April 2019
Resolution: (03) new PFD's were brought to the vessel during the inspection.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 22 April 2019 Resolved
The front naviagtional light lens is wasted and corroded.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 May 2019
Resolved 21 May 2019
Resolution: A new navigational light was installed.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-corrosion
Issued 22 April 2019 Resolved
The aft engine space has a rotten transverse frame. This deficiency has been deferred until drydock, NLT 31 AUG 2019.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 31 August 2019
Resolved 24 October 2019
Resolution: Repair completed at drydock
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 22 April 2019 Resolved
The port side railing was missing screws in several areas.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 May 2019
Resolved 21 May 2019
Resolution: Screws were replaced, securing the port side railing.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 22 April 2019 Resolved
Several areas of wiring on the vessel had dead end wires/wires that were not attached to anything.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 22 May 2019
Resolved 21 May 2019
Resolution: Old wiring was removed, connections have been heat sealed and shrunk, no dead end wiring was observed.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 12 April 2019 Resolved
The vessel missed its annual inspection.
Condition: Placed in Improper Service
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 April 2019
Resolved 22 April 2019
Resolution: Scheduled and completed annual inspection.
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 8 November 2017 Resolved
Lettering needed to be refreshed. Corrected on spot.
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 8 November 2017
Resolved 8 November 2017
Resolution: Corrected by deckhand with Sharpie marker.
Electrical › Electrical Distribution System (service) › Wiring
Issued 8 November 2017 Resolved
Properly secure electrical wiring throughout engine room.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 22 November 2017
Resolved 22 April 2019
Resolution: Resolved
Construction/Loadline › Structures › Superstructure
Issued 8 November 2017 Resolved
Install port side railing (removed for painting)
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 22 April 2019
Resolution: port side railing is installed
Construction/Loadline › Markings › Vessel Name/Home Port
Issued 8 November 2017 Resolved
Affix vessel name and hailing port to stern (removed for painting)
Condition: Improper Installation
Action required: 60 - Rectify deficiencies prior to movement
Resolved 22 April 2019
Resolution: Vessels name and hailing port is painted on stern.
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 28 April 2017 Resolved
Was unable to conduct operational test of the fireboy.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 November 2017
Resolution: Satisfactory test.
Operations/Management › Drills/Instruction › Man Overboard Recovery
Issued 28 April 2017 Resolved
Vessel unable to get U/W due to transmission overhaul and unable to conduct drills.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 8 November 2017
Resolution: Got u/w for engine trials and drills.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.