MAURY USCG vessel records
← All vessels

STARLIGHT

STARLIGHT is a 1978 passenger vessel (inspected). The Coast Guard has recorded 20 inspections since 2016, most recently in May 2026, along with 45 deficiencies and 2 casualty investigations in 2011.

Records from 2011 to 2026. Most recent: inspection, 21 May 2026.

Built
1978
Last inspected
21 May 2026
Documentation
Valid · documentation file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 21 May 2026
Operational controls None recorded without a removal date
Years with a record 11 calendar years (2016–2026)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

WDP5951
Flag
UNITED STATES
Maury page id
psix-49685

Documentation record

Registered dimensions (L × B × D)68.7 ft × 22.1 ft × 6.7 ft
Registered tonnagegross 81 / net 55
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderLYDIA YACHTS INC · STUART, FL, UNITED STATES · built 1978
Hull materialWood
PropulsionDiesel Reduction
Hull shapeUNSPECIFIED
Hull configurationUNSPECIFIED
Hailing portCAPE MAY, NJ
Trade endorsementsCoastwise, unrestricted, Fishery, Registry
DocumentationValid · issued 30 July 2026 · expires 31 July 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it81 - Regulatory (Subpart C or D), Gross Ton
55 - Regulatory (Subpart C or D), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 2016 to 2026 for this class, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 20

21 May 2026 COI Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8367211
3 September 2025 Annual Inspection · Examination of Repairs
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8226219
30 October 2024 Administrative Inspection · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8026929
9 October 2024 Drydock Exam · Internal Structural Exam
Physical examination · Sector Virginia · USCG East District (CGD-E) · Activity 8015543
16 May 2024 In-Service Inspection · Deficiency Check
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 7912484
3 April 2023 Annual Inspection · In-Service Inspection · Administrative Inspection · Deficiency Check
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7661549
16 March 2023 Administrative Inspection
Administrative · Sector New York · USCG Northeast District (CGD-NE) · Activity 7652215
10 February 2023 Internal Structural Exam · Drydock Exam
Physical examination · Marine Safety Unit Coram · USCG Northeast District (CGD-NE) · Activity 7634696
15 April 2022 Annual Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7446122
29 September 2021 Drydock Exam · Internal Structural Exam
Physical examination · Marine Safety Unit Coram · USCG Northeast District (CGD-NE) · Activity 7322355
29 April 2021 COI Inspection · Deficiency Check · Administrative Inspection
Physical examination · Sector New York · USCG Northeast District (CGD-NE) · Activity 7185852
23 March 2021 Administrative Inspection
Administrative · Marine Safety Unit Coram · USCG Northeast District (CGD-NE) · Activity 7161401
18 June 2020 Deficiency Check · COI Inspection
Physical examination · Marine Safety Unit Coram · USCG Northeast District (CGD-NE) · Activity 6924631
16 October 2019 Drydock Exam · Internal Structural Exam
Physical examination · Marine Safety Unit Coram · USCG Northeast District (CGD-NE) · Activity 6820855
4 June 2019 Annual Inspection
Physical examination · Marine Safety Unit Coram · USCG Northeast District (CGD-NE) · Activity 6688792
22 May 2018 Annual Inspection
Physical examination · Marine Safety Unit Coram · USCG Northeast District (CGD-NE) · Activity 6384974
13 October 2017 Internal Structural Exam · Hull Examination
Physical examination · Marine Safety Unit Coram · USCG Northeast District (CGD-NE) · Activity 6282091
9 May 2017 Annual Inspection
Physical examination · Marine Safety Unit Coram · USCG Northeast District (CGD-NE) · Activity 6199715
6 June 2016 Annual Inspection · Deficiency Check
Physical examination · Marine Safety Unit Coram · USCG Northeast District (CGD-NE) · Activity 5899248
20 April 2016 Hull Examination · Internal Structural Exam
Physical examination · Marine Safety Unit Coram · USCG Northeast District (CGD-NE) · Activity 5858321

Deficiency record · 45

07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 3 September 2025 Resolved
The owner, managing operator, or a qualified servicing facility as applicable must conduct the following inspections and tests: For fixed-gas fire extinguishing systems, the inspections and tests required by Table 176.810(b) of this section, in addition to the tests required by 46 CFR 147.60 and 147.65. The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector. If any of the equipment or records have not been properly maintained, a qualified servicing facility may be required to perform the required inspections, maintenance procedures, and hydrostatic pressure tests. Provide service report for Fixed CO2 system and portable extinguishers.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 17 September 2025
Resolved 5 September 2025
Resolution: Summit fire report completed, all sat.
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 3 September 2025 Resolved
Each vessel that operates on the high seas, or that operates beyond three miles from the coastline of the Great Lakes, must have on board a FCC Type Accepted Category 1, 406 MHz EPIRB, installed to automatically float free and activate. The EPIRB hydrostatic release was expired.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 17 September 2025
Resolved 5 September 2025
Resolution: Hydrostatic release installed, all sat.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 3 September 2025 Resolved
A fire hose with a nozzle must be attached to each fire hydrant at all times. For fire hydrants located on open decks or cargo decks, where no protection is provided, hoses may be temporarily removed during heavy weather or cargo handling operations, respectively. Hoses so removed must be stored in nearby accessible locations. Replace fire hose.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 17 September 2025
Resolved 5 September 2025
Resolution: Fire hose replaced, All sat.
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 3 September 2025 Resolved
The means used to attach the float-free link to the vessel must have a breaking strength of at least the breaking strength of the painter. Life floats were found fastened to the uppermost deck by means of the painter housing.
Action required: 60 - Rectify deficiencies prior to movement
Due 17 September 2025
Resolved 5 September 2025
Resolution: Life float line re-rigged, all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 3 September 2025 Resolved
Each lifejacket must be approved under approval series in subparts 160.002, 160.005, 160.055, 160.115, 160.176, or 160.255, or other standard specified by the Commandant. MI found 7 life jackets that were either not approved for small passenger vessel service or damaged to the point of being unserviceable.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 September 2025
Resolved 5 September 2025
Resolution: Lifejackets replaced and retro tape renewed, all sat.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 3 September 2025 Resolved
Each life float must be fitted with a lifeline, pendants, two paddles, a painter, and a light. All life float paddles were cracking and unserviceable.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 September 2025
Resolved 5 September 2025
Resolution: Paddles replaced, all sat.
05 - Radio Communications › N/A - No Subsystem › SART/AIS-SART
Issued 3 September 2025 Resolved
Use of a Coast Guard type-approved AIS Class B device in lieu of an AIS Class A device is permissible on the following vessels if they are not subject to pilotage by other than the vessel Master or crew: Vessels identified in paragraph (b)(1)(i) of this section that are certificated to carry less than 150 passengers. Vessel does not have AIS, Owner/Operator instructed to install Class "B" AIS transponder.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 3 October 2025
Resolved 8 September 2025
Resolution: Vessel provided prrof of funcional AIS onboard.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 3 September 2025 Resolved
The following spaces must be equipped with a fixed gas fire extinguishing system, in compliance with § 181.410, or other fixed fire extinguishing system specifically approved by the Commandant, except as otherwise allowed by paragraph (b) of this section: Discharge hose on CO2 has wasted fitting. Fitting to be replaced.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Due 17 September 2025
Resolved 5 September 2025
Resolution: Fitting replaced, all sat.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 3 September 2025 Resolved
A collision bulkhead must not be fitted with any type of penetration or opening except penetrations may be made if they are located as high and as far inboard as practicable and they have a means to make them watertight. The collision bulkhead had two vent penetrations that were not watertight in way of the most outboard locations of both the port and starboard-most reaches of the bulkhead.46 CFR 179.310(a)(2)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 September 2025
Resolved 5 September 2025
Resolution: Penetrations closed, all sat.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 3 September 2025 Resolved
No person may operate a vessel to which this part applies unless they have on board in hard copy or digital form a valid certificate of number or temporary certificate for that vessel issued by the issuing authority in the State in which the vessel is principally operated. The vessel does not have a valid certificate of number for the state of Florida. 33CFR173.21(a)(1)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 September 2025
Resolved 1 December 2025
Resolution: Certs updated, all sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 3 September 2025 Resolved
Where flexible nonmetallic hose is permitted for use in piping systems by this section, it must meet SAE J-1942. Hydraulic lines serving the anchor windlass were cracked. 46 CFR182.720(e)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 September 2025
Resolved 1 December 2025
Resolution: Hydraulic lines replaced, all sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 3 September 2025 Resolved
Flexible nonmetallic hose must be complete with factory-assembled end fittings requiring no further adjustment of the fittings on the hose and must comply with SAE J-1475. Hose end fittings serving the hydraulic lines for the anchor windlass were unsuitably corroded.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 September 2025
Resolved 1 December 2025
Resolution: Fittings replaced, all sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 3 September 2025 Resolved
The design of all exhaust systems must ensure minimum risk of injury to personnel. Protection must be provided at such locations where persons or equipment might come in contact with an exhaust pipe. The port side main engine exhaust lagging was missing.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 September 2025
Resolved 1 December 2025
Resolution: Lagging replaced, all sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 3 September 2025 Resolved
Water for cooling the exhaust pipe, must be injected into the exhaust system as near to the engine manifold as practicable, and that water must pass through the entire length of the exhaust pipe. Center main engine lagging was leaking raw cooling water between its injection point and the exhaust terminus as evidenced by the accumulation of salt in the engine room below the exhaust pipe.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 September 2025
Resolved 1 December 2025
Resolution: Leak repaired, all sat.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 3 September 2025 Resolved
Each watertight bulkhead must be of sufficient strength to be capable of remaining watertight with a head of water to the top of the bulkhead. Bulkhead in lazarette to engine room has penetrations that need to be watertight.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 September 2025
Resolved 5 September 2025
Resolution: Penetrations sealed, all sat.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 3 September 2025 Resolved
A hatch exposed to the weather must be watertight. Forward hatch for collision bulkhead needs to be fully operational.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 September 2025
Resolved 1 December 2025
Resolution: Hatch replaced, all sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 3 September 2025 Resolved
Where flexible nonmetallic hose is permitted for use in piping systems by this section, it must meet SAE J-1942. Piping on port engine water pump to heat exchanger has a patch. Piping must be approved type or replaced in kind.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 September 2025
Resolved 5 September 2025
Resolution: Pipe replaced, all sat.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 16 May 2024 Resolved
For fixed gas fire extinguishing system, The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector. Vessel had a custom fixed co2 system that had not been serviced since March 2023. Service the fixed C02 system to the satisfaction of the attending marine inspector. 46CFR810(b)2
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 30 May 2024
Resolution: Received report ad invioce attesting to the serviceing of the CO2 Fire Suppression system. Report Uploaded to documents.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 16 May 2024 Resolved
Fire hose shall have a nozzle that has a 1/2 inch solid stream Orifice or a combination nozzle. Vessel did not have a nozzle attached to fire hose. Install nozzle on the fire hose to the satisfaction of the attending marine inspector. 46CFR181.15-10(c)(1) (Old "T")
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 30 May 2024
Resolution: Received video of the installation of fire nozzle onto the fire hose. Video showed adequate pressure and varying spray patterns.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 16 May 2024 Resolved
The minimum capacity of the power fire pump shall be 50 gallons per minute at a pressure not less than 60 pounds per square inch at the pump outlet. The pump outlet shall be fitted with a pressure gauge. Vessel did not have a pressure gauge installed. Install pressure gauge at the pump outlet to the satisfaction of the attending marine inspector. 46CFR182.520
Action required: 701 - Prior to carriage of passengers/cargo
Due 30 May 2024
Resolved 30 May 2024
Resolution: Received photo of pressure guage installed on fire pump.
09 - Working and Living Conditions › 092 - Working Conditions › Anchoring devices
Issued 16 May 2024 Resolved
A vessel must be fitted with ground tackle and mooring lines necessary for the vessel to be safely anchored or moored. Vessel did not have the anchor fitted to the vessel for use. Install anchor. 46CFR184.300
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 30 May 2024
Resolution: Anchor on vessel was installed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 16 May 2024 Resolved
A bilge pipe piercing the collision bulkhead must be fitted with a screw-down valve located on the forward side of the collision bulkhead. Valve was not operable. Replace valve in forward compartment to the satisfaction of the attending marine inspector. 46CFR181.10-1c (Old "T")
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 30 May 2024
Resolution: Received video of the replacement valve on forward compartment. Video showed valve exercised.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 16 May 2024 Resolved
Each item of lifesaving equipment determined by the marine inspector to not be in serviceable condition must be repaired or replaced. Vessel had 17 life jackets that needed retro reflective tape replaced and two life jackets were condemned. Repair the 17 life jackets and replace the two condemned life jackets. 46cfr176.808c
Action required: 705 - Other - as specified
Resolved 25 June 2024
Resolution: Received photographic evidence of new retro-reflective tape on life jackets and two new additional life jackets on board.
05 - Radio Communications › N/A - No Subsystem › VHF radio installation
Issued 16 May 2024 Resolved
Unless normal use of the radiotelephone installation demonstrates that the equipment is in proper operating condition. VHF radio did not have the MSSI number programmed in. Install MSSI number. 47CFR80.931
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 23 May 2024
Resolution: Revieved Photo of MMSI # programed into VHF Radio.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 16 May 2024 Resolved
Each small battery installation must be located in a well ventilated space and protected from falling objects. Install covers on batteries. 46CFR183.354(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 May 2024
Resolution: Received photo of battery with installed covers.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 16 May 2024 Resolved
Receptacle outlets of the type providing a grounded pole or a specific direct current polarity must be of a configuration that will not permit improper connection. Install outlet cover on Fwd Starboard bulkhead. 183.220(c)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 May 2024
Resolution: Received photo of instaled outlet covers.
14 - Pollution Prevention › 144 - MARPOL Annex IV (Not Applicable to PSC Exams conducted in the U.S.) › Sewage discharge connection
Issued 16 May 2024 Resolved
Operator must secure each Type I or Type II device in a manner which prevents discharge of treated or untreated sewage. Blank off overboard discharge. 33CFR1597(b)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 May 2024
Resolution: Received photo of sewage discharge pipe capped off.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 16 May 2024 Resolved
Double hose clamping is required where practicable in systems and application where flexible hoses are permitted to be clamped. Install double hose clamps. 46CFR182.410d(1)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 30 May 2024
Resolution: Received photo of double hose clamps installed.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 3 April 2023 Resolved
Spaces containing propulsion machinery are required to to be equipped with a fire detection system. Heat detection system in engine room was no longer operable. 46 CFR 181.405 (disregard below)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 April 2023
Resolved 19 April 2023
Resolution: Conducted satisfactory test of new heat detection system; activiated detectors, actuated test mode, and operated with both power sources. All sat.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 3 April 2023 Resolved
All equipment including switches shall be of a type designed for the potential involved and so identified. The generator selector switches in the engine room require the knobs designed for properly turning switches. 46 CFR 183.10-20 (OLD T)
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 April 2023
Resolved 26 April 2023
Resolution: New switch was satisfactorily installed. Delay was caused by damaged unit being shipped to vessel initially.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 3 April 2023 Resolved
All machinery must be maintained in such a manner as to afford adequate protection against failure. Spring on the STBD engine shutoff assembly was being held by a zip tie and needs to be replaced with a new part. 46 CFR 182.01-5 (OLD T)
Condition: Damaged By Earlier Event
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 April 2023
Resolved 19 April 2023
Resolution: Spring was replaced. All sat.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 3 April 2023 Resolved
Each item of survival craft equipment must be of good quality and efficient for the purpose of its intended service. Grab lines on several life floats and the basket on one were deteriorated. 46 CFR 180.175
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 April 2023
Resolved 26 April 2023
Resolution: Almost all life lines were replaced.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 3 April 2023 Resolved
A life preserver shall not be appreciably deteriorated. 10 life jackets on the upper deck were found to be significantly deteriorated and must be replaced.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 April 2023
Resolved 19 April 2023
Resolution: Observed new, satisfactory life jackets.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 29 April 2021 Resolved
46 CFR 182.20-25 Sounding gage for independent fuel tanks were not of a heat resistant material and did not have a means to automatically close. Due prior to next credit dry dock.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 10 February 2023
Resolution: Next drydock to be completed by 30SEP2023.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 29 April 2021 Resolved
46 CFR 183.05-20 Batteries do not have covers/ protection from objects falling on terminals.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 May 2021
Resolved 10 May 2021
Resolution: Received photos of battery covers installed
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 29 April 2021 Resolved
46 CFR 177.35-15 Pullies on center and port side main engines do not have guards.
Condition: Improper Installation
Action required: 16 - Rectify deficiencies w/in 14 days
Due 17 May 2021
Resolved 10 May 2021
Resolution: Received photos of engine guards installed.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 18 June 2020 Resolved
Life-floats were left detached from weak link after rep serviced. properly re-connect.
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Due 18 June 2020
Resolved 18 June 2020
Resolution: Re-connected
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 18 June 2020 Resolved
Water light for one of the life floats was not properly secured repair or replace light.
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Due 18 June 2020
Resolved 18 June 2020
Resolution: Repaired water light.
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 4 June 2019 Resolved
Replace battery and hydrostatic release prior to operating more than 3 miles from shore with passengers.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 4 July 2019
Resolved 3 July 2019
Resolution: O/O provided proof of correction.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 4 June 2019 Resolved
replace ring buoy
Condition: Damaged By Earlier Event
Action required: 10 - Deficiency Rectified
Due 20 June 2019
Resolved 20 June 2019
Resolution: O/O provided proof of corrected item.
Engineering › Bilge Water Management System › Pump
Issued 8 June 2016 Resolved
Repair clutch for stbd pump (for bilge piping system)
Action required: 705 - Other - as specified
Due 22 June 2016
Resolved 20 June 2016
Resolution: Replaced Belt, and operated successfully
Communications › Radio Communications › VHF Radiotelephone
Issued 8 June 2016 Resolved
Program MMSI# into VHF/DSC capable radio per MSIB.
Action required: 705 - Other - as specified
Due 22 June 2016
Resolved 20 June 2016
Documentation › Certificates/Documents › Stability Letter
Issued 8 June 2016 Resolved
Post stability letter with COI in operating station.
Action required: 705 - Other - as specified
Due 22 June 2016
Resolved 20 June 2016
Navigation › Piloting/Steering › Marine Charts
Issued 8 June 2016 Resolved
Provide updated chart for area of operation.
Action required: 705 - Other - as specified
Due 22 June 2016
Resolved 20 June 2016
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 8 June 2016 Resolved
Label, and put retro on RLB's on aft and port of operating station.
Action required: 705 - Other - as specified
Due 22 June 2016
Resolved 20 June 2016

Casualty record · 2

19 April 2011Routine · role: Involved in a Marine Casualty · activity 4137656
23 May 2011Routine · role: Involved in a Marine Casualty · 1 injured · activity 4071413
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.

Recorded names · 1

CAPTREE STAR III (2011). Names as the Coast Guard recorded them in incident records, with the years they appear; some are renames and some are spelling variants.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.