01 - Certificates & Documentation › 011 - Ships Certificates › USCG Certificate of Documentation (COD)
Issued 4 June 2025
Resolved
The person in command of a documented vessel must have on board that vessel the original certificate of documentation currently in effect for that vessel. Certificate of documentation on board is a copy. Provide original before operating.
46 CFR 67.313
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 June 2025
Resolution: Vessel provided original COD onboard and placed in documents folder, all sat.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 12 March 2024
Resolved
Annual inspection. Your vessel must undergo an annual inspection within the 3 months before or after each anniversary date.
46 cfr 176.500
Action required: 10 - Deficiency Rectified
Due 12 March 2024
Resolved 12 March 2024
Resolution: Conducted annual inspection.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 24 August 2021
Resolved
To maintain a valid Certificate of Inspection, you must complete your annual inspection within the periods specified in §176.500(b)(1) and your Certificate of Inspection must be endorsed. The annual inspection was to be conducted by no later than August 2, 2021 to remain valid but the inspection not completed until August 24, 2021.
46 CFR 176.502
Action required: 10 - Deficiency Rectified
Resolved 24 August 2021
Resolution: An Annual Inspection was completed on August 24, 2021.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 24 August 2021
Resolved
Auxiliary machinery shall be suitable in type and design for the purpose intended. A weeping fuel connection was observed on the #4 cylinder injector for the generator, additionally the lagging on the exhaust was deteriorated. Correct to the satisfaction of the attending Marine Inspector.
46 CFR 182.10-1
Action required: 60 - Rectify deficiencies prior to movement
Resolved 25 August 2021
Resolution: The fuel line was replaced.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance and inspections
Issued 24 August 2021
Resolved
Inspection and maintenance of the equipment listed in paragraph (a) of this section shall be logged or otherwise documented for review by the Coast Guard upon request. Inspection records of the vessel's life-saving appliances were not onboard.
46 CFR 185.702(d)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 28 September 2021
Resolution: Vessel rep proivided proof of lifesaving equipment checks.
01 - Certificates & Documentation › 012 - Crew Certificates › Certificates for radio personnel
Issued 24 August 2021
Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 September 2021
Resolution: Vessel rep provided copy of Captain's FCC Radio Operators Permit.
09 - Working and Living Conditions › 091 - Living Conditions › Water, pipes, tanks
Issued 24 August 2021
Resolved
Auxiliary machinery shall be suitable in type and design for the purpose intended. The hot water heater tank is severely wasted, remove from service.
46 CFR 182.10-1
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 28 September 2021
Resolution: The hot water heater tank was replaced.
14 - Pollution Prevention › 145 - MARPOL Annex V › Placards
Issued 24 August 2021
Resolved
Placards meeting the requirements of this section are displayed in prominent locations and in sufficient numbers so that they can be read by the crew and passengers. Garbage placards posted depicted obsolete garbage discharge standards.
33 CFR 159.59(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 28 September 2021
Resolution: New garbage placard posted with current garbage discharge standards.
09 - Working and Living Conditions › 091 - Living Conditions › Pipes, wires (insulation)
Issued 24 August 2021
Resolved
All electrical installations shall be to the satisfaction of the [name withheld] end wires were observed coming out of the "stove disconnect" box in the crew accommodations.
46 CFR 183.01-15
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 28 September 2021
Resolution: "stove disconnect" was removed and wire was mounted within a junction box.
09 - Working and Living Conditions › 091 - Living Conditions › Pipes, wires (insulation)
Issued 24 August 2021
Resolved
All electrical installations shall be to the satisfaction of the OCMI. The 240 V distribution panel on the bridge has a 50 amp breaker installed for the A/C unit but not labeled and the panel cover is unable to close.
46 CFR 183.01-15
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 28 September 2021
Resolution: Breaker panel was relabeled to include the 50 amp beaker for the A/C unit and panel door functions properly.
14 - Pollution Prevention › 144 - MARPOL Annex IV (Not Applicable to PSC Exams conducted in the U.S.) › Sewage treatment plant
Issued 24 August 2021
Resolved
No person may operate any vessel equipped with installed
toilet facilities unless it is equipped with an operable marine sanitation device (MSD). No chemical treatment products were available for the MSD to operate properly.
33 CFR 159.7
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 28 September 2021
Resolution: Chemical treatment tabs were placed onboard.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 24 August 2021
Resolved
Fuel shutoff valves shall be installed the tank connection. The aft fuel tank is no longer in-service, remove signage for the aft fuel tank emergency fuel shutoff on the main deck.
46 CFR 182.40(b)(3)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 25 August 2021
Resolution: Remote fuel shutoff reach-rod and signage removed.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 24 August 2021
Resolved
The Master of the vessel must ensure that all of the provisions of the Certificate of Inspection are strictly adhered to. The flooring in the aft starboard corner of the passenger seating area is rotting and weakening the flooring.
46 CFR 185.20-15
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 28 September 2021
Resolution: 02 sections of flooring were replaced.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 27 October 2020
Resolved
All pressure vessels must be provided with protective devices. The vessel's hot water heater's pressure/temperature relief valve was inoperable. Rectify prior to use of the hot water heater.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 16 November 2020
Resolution: Received, reviewed, and accepted video of properly functioning relief valve.
09 - Working and Living Conditions › 092 - Working Conditions › Pipes, wires (insulation)
Issued 27 October 2020
Resolved
Piping including valves, pipe fittings, and flanges
conveying vapor, gas, or liquid, the temperature of
which exceeds 150 degree F must be suitably insulated
where necessary to prevent injury. The insulation on
both MDEs and Generator were wasted.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 16 November 2020
Resolution: Received, reviewed, and accepted documentation of adequate insulation.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 27 October 2020
Resolved
If electrical equipment is utilized in a space in which
the equipment's rated ambient temperature is below the
assumed ambient temperature of the space (50 degrees C), its load must be derated. Vessel's generator data plate had an ambient temperature rating of 40 degrees C. Provide new data plate for an ambient temperature of 50 degrees C or derate the generator to adhere to the above regulation prior to use of the generator.
Condition: Design Flaw
Action required: 705 - Other - as specified
Resolved 8 December 2020
Resolution: Receieved, reviwed, and accepted generator data plate notating an ambient operating temperature of 50 degrees celsius.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 27 October 2020
Resolved
Each generator must meet the applicable construction and test requirements of Section 35 of the American Bureau of Shipping's "Rules for Building and Classing Steel Vessels". Vessel's generator windings were dirty with oil soaked dust. Rectify before use of generator.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 16 November 2020
Resolution: Received, reviewed, and accepted documentation of cleaned generator windings.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 27 October 2020
Resolved
Flexible hose may be used provided it is fitted with suitable connection fittings and has high resistance to
salt water, petroleum oils and vibration. Vessel's fuel
line on the generator was wasted. Replace fuel line prior to use of the generator.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 16 November 2020
Resolution: Received, reviewed, and accepted documentation of new installation of fuel line.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 27 October 2020
Resolved
Batteries shall be effectively screened by a cage or similar structure to minimize the danger of accidental spark through dropping metal objects across the terminal. Vessel's starboard engine batteries were not suitably covered.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 16 November 2020
Resolution: Received, reviewed, and accepted documentation of adequate battery covers.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 27 October 2020
Resolved
The discharge ends of vent pipes shall be fitted with removable flame screens or flame arrestors. 02 ends of of 02 vent pipes were torn and ineffective for intended use.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 16 November 2020
Resolution: Received, reviewed, and accepted documentation of adequate flame screens.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 27 October 2020
Resolved
The exhaust piping shall be so arranged as to prevent backflow of water from reaching engine exhaust ports under normal conditions. The vessel's starboard engine exhaust had no backflow protection rectify prior to use of starboard engine
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Resolved 16 November 2020
Resolution: Received, reviewed, and accepted documentation of adequate exhaust backflow protection.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 27 October 2020
Resolved
Penetrations and openings in watertight bulkheads must have means to make them watertight. Vessel had multiple openings in watertight bulkheads that were not water tight.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 16 November 2020
Resolution: Received, reviewed, and accepted documentation that all watertight bulkheads were made water tight.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 27 October 2020
Resolved
All electrical installations shall be to the satisfaction of the Officer in Charge, Marine Inspection. Vessel's light in the lazarette space was inoperable.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 16 November 2020
Resolution: Received, reviewed, and accepted documentation of functioning light.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 27 October 2020
Resolved
All electrical installations shall be to the satisfaction of the Officer in Charge, Marine Inspections. Veesel's generator control box was not adequately mounted.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 16 November 2020
Resolution: Received, reviewed, and accepted documentation that generator control box was properly secured.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Machinery space openings
Issued 27 October 2020
Resolved
A hatch exposed to the weather must be watertight. Vessels starboard engine room access had a wasted gasket.
Condition: Improper/Lack of Maintenance
Action required: 60 - Rectify deficiencies prior to movement
Resolved 16 November 2020
Resolution: Received, reviewed, and accepted documentation that engine room door gasket was satisfactorily replaced.
Lifesaving › Lifefloat › Painter
Issued 20 April 2017
Resolved
Replace electrical tape on lines for life floats and lights with more suitable ties to satisfaction of attending marine inspector.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 27 April 2017
Resolved 20 April 2017
Resolution: Received pictures showing electrical tape has been removed and lines are secured with quick release ties.
Fire Fighting › Portable Dry Chemical Fire Extinguisher › Number
Issued 26 May 2016
Resolved
Missing x2 type BII Fire Extinguishers. Corrected on the spot.
Action required: 701 - Prior to carriage of passengers/cargo
Due 26 May 2016
Resolved 26 May 2016
Resolution: Added missing fire extinguishers.
Lifesaving › Lifefloat › Float-free Link
Issued 26 May 2016
Resolved
Life Float not connected to weak link/spool. Corrected on the spot.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Due 26 May 2016
Resolved 26 May 2016
Resolution: Properly attached lifefloat to weak link and spool.
Engineering › Diesel Engine (auxiliary) › Piping (exhaust)
Issued 26 May 2016
Resolved
Exhaust insulation on generator shows signes of exhaust leak. Repair effected area to satisfaction of attending MI.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 25 June 2016
Resolved 31 May 2016
Resolution: Exhaust lagging on generator was replaced. No evidence of continuing leak.
Documentation › Certificates/Documents › Certificate of Documentation (CG-1270)
Issued 26 May 2016
Resolved
Certificate of Documentation expired.
Action required: 701 - Prior to carriage of passengers/cargo
Due 2 June 2016
Resolved 27 May 2016
Resolution: Placed current COD on board that was issued in Feb 2016.
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 26 May 2016
Resolved
Mast Light missing nonreflective flat black back.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 9 June 2016
Resolved 31 May 2016
Resolution: Background for mast light was painted nonreflective flat black.