LADY PAMELA III

LADY PAMELA III is a 1979 passenger vessel (inspected). The Coast Guard has recorded 46 inspections since 1985, most recently in July 2026, along with 36 deficiencies and 1 casualty investigation in 2002.

Records from 1985 to 2026. Most recent: inspection, 20 July 2026.

Built
1979
Last inspected
20 July 2026
Documentation
Valid · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

WDF4750
Flag
UNITED STATES
338374000
Maury page id
psix-50120

Inspections, by type

…with no type recorded11
Years with a record 25 calendar years (1985–2026)
The 46 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Registered dimensions (L × B × D)35.9 ft × 13.1 ft × 6.1 ft
Registered tonnagegross 17 / net 12
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderSTAPLTON BOAT CORP · MIAMI, FL, UNITED STATES · built 1979
Hull materialFRP (Fiberglass)
PropulsionDiesel Direct
Hull shapeNot recorded
Hull configurationNot recorded
Hailing portFORT LAUDERDALE, FL
Trade endorsementsCoastwise, unrestricted, Fishery, Recreational, Registry
DocumentationValid · issued 30 March 2026 · expires 31 March 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it17 - Regulatory (Subpart C or D), Gross Ton
12 - Regulatory (Subpart C or D), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

WDF4750MMSI 338374000 · active · compulsorily equipped · granted 22 May 2020, expires 3 June 2030
WBZ3625MMSI not assigned · expired · voluntarily equipped · granted 20 July 1998, cancelled 8 November 2008
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown. A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.

Inspection history · 46

20 July 2026 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8442635
1 September 2025 Type not recorded
No type recorded · Station Fort Lauderdale · USCG Southeast District (CGD-SE) · Activity 8229872
14 July 2025 COI Inspection · Deficiency Check
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8185695
4 October 2024 Deficiency Check · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8014701
20 June 2024 Administrative Inspection · Drydock Exam · Internal Structural Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7938486
3 October 2023 Deficiency Check · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7803068
4 October 2022 Annual Inspection · Administrative Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7588535
16 June 2022 Internal Structural Exam · Administrative Inspection · Drydock Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7480422
5 October 2021 Annual Inspection · Administrative Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7322867
16 July 2020 Administrative Inspection · Deficiency Check · COI Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 7005853
17 June 2020 Administrative Inspection · Drydock Exam · Internal Structural Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6979897
17 April 2020 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6940432
23 September 2019 Annual Inspection · DAPI Audit
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6818510
20 March 2019 Type not recorded
No type recorded · Station Fort Lauderdale · USCG Southeast District (CGD-SE) · Activity 6646893
19 September 2018 Administrative Inspection · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6395613
10 May 2018 Internal Structural Exam · Drydock Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6395610
19 September 2017 Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6269960
22 September 2016 DAPI Audit · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6004894
16 May 2016 Drydock Exam · Internal Structural Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 5878316
3 October 2014 DAPI Audit · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 4997461
28 May 2014 Drydock Exam · Internal Structural Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 4870559
13 June 2012 DAPI Audit · Examination of Repairs · Annual Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 4334891
25 May 2012 Internal Structural Exam · Drydock Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 4321372
13 July 2011 Annual Inspection · DAPI Audit
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 4077799
30 August 2006 Annual Inspection · Deficiency Check
Physical examination · Marine Safety Unit Lewes · USCG East District (CGD-E) · Activity 2782218
13 April 2006 Deficiency Check · Hull Examination
Physical examination · Marine Safety Unit Lewes · USCG East District (CGD-E) · Activity 2623373
18 July 2005 Deficiency Check
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 2431156
21 June 2005 Annual Inspection
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 2397655
7 June 2005 Type not recorded
No type recorded · Station Indian River · USCG East District (CGD-E) · Activity 2386091
11 September 2004 Type not recorded
No type recorded · Station Indian River · USCG East District (CGD-E) · Activity 2193505
26 April 2004 Hull Examination · Annual Inspection
Physical examination · MSO PHILADELPHIA · USCG East District (CGD-E) · Activity 2053207
15 May 2003 Annual Inspection
Physical examination · MSO PHILADELPHIA · USCG East District (CGD-E) · Activity 1860832
30 July 2002 COI Inspection · Simplified Stability Test · Hull Examination
Physical examination · MSO PHILADELPHIA · USCG East District (CGD-E) · Activity 1654350
9 July 2002 Type not recorded
No type recorded · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 1643590
21 September 2000 COI Inspection · Hull Examination
Physical examination · MSO PHILADELPHIA · USCG East District (CGD-E) · Activity 1391642
3 May 1995 Type not recorded
No type recorded · District 5 (B) · USCG East District (CGD-E) · Activity 675922
31 March 1995 Type not recorded
No type recorded · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 153593
31 March 1995 Type not recorded
No type recorded · MSO HAMPTON ROADS · USCG East District (CGD-E) · Activity 160577
3 February 1995 Type not recorded
No type recorded · District 5 (B) · USCG East District (CGD-E) · Activity 709443
9 December 1993 Type not recorded
No type recorded · District 5 (B) · USCG East District (CGD-E) · Activity 675923
10 November 1993 Type not recorded
No type recorded · USCG East District (dp) · USCG East District (CGD-E) · Activity 675924
26 June 1992 Administrative
Administrative · Commandant (CG-INV-3) · Activity 957710
4 April 1986 Deficiency Check
Physical examination · MIO PHILADELPHIA · USCG East District (CGD-E) · Activity 1304955
1 April 1986 Re-Inspection
Physical examination · MIO PHILADELPHIA · USCG East District (CGD-E) · Activity 1304954
23 October 1985 Credit Drydock
Administrative · MIO PHILADELPHIA · USCG East District (CGD-E) · Activity 992391
14 March 1985 COI Inspection
Physical examination · MIO PHILADELPHIA · USCG East District (CGD-E) · Activity 984055

Deficiency record · 36

18 - Maritime Labour Convention (Not Applicable to PSC Exams conducted in the U.S.) › N/A - No Subsystem › Other (Conditions of employment)
Issued 20 July 2026 Resolved
Chemical testing of personnel must be conducted as required by this subpart and in accordance with the procedures detailed in 49 CFR part 40. Vessel has an expired drug and alcohol testing program.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 20 July 2026
Resolved 20 July 2026
Resolution: Company provided confimration of enrollement. Account #26706 with Martime Consortium Inc.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 14 July 2025 Resolved
Monthly inspections required by NFPA 10 may be conducted by the owner, operator, person-in-charge, or a designated member of the crew. Vessel did not have a monthly inspection log of firefighting equipment.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 28 July 2025
Resolved 16 July 2025
Resolution: Implemented monthly inspection log
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 14 July 2025 Resolved
Placards containing instructions for the donning and use of the life jackets aboard the vessel must be posted in conspicuous places that are regularly accessible and visible to the crew and passengers. Life jacket donning placard was not posted for each style of Life Jacket.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 28 July 2025
Resolved 15 July 2025
Resolution: Posted correct donning placards
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 14 July 2025 Resolved
Each ring life buoy with a floating waterlight must have a lanyard of at least 3 feet in length, but not more than 6 feet, securing the waterlight around the body of the ring life buoy. Each floating waterlight installed after March 11, 1997,on a vessel carrying only one ring buoy, must be attached to the lanyard with a corrosion-resistant clip. The waterlight was not attached via the prescribed lanyard and was without a corrosion resistant clip,and secured to the grab line.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 28 July 2025
Resolved 15 July 2025
Resolution: Correctly arranged life ring and float light lanyards
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 14 July 2025 Resolved
Piping, including valves, pipe fittings and flanges, conveying vapor, gas, or liquid, the temperature of which exceeds 65.5 °C (150 °F), must be suitably insulated where necessary to prevent injuries. Insulation was compromised on turbocharger outlet.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 28 July 2025
Resolved 15 July 2025
Resolution: Replaced exhaust lagging
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 14 July 2025 Resolved
Portable fire extinguishers must be located so that they are clearly visible and readily accessible from the space being protected. The installation and location must be to the satisfaction of the Officer in Charge, Marine Inspection. Port side main deck fire extinguisher bracket was broken and unusable.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 28 July 2025
Resolved 15 July 2025
Resolution: Replaced fire extinguisher bracket and appropriately mounted
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 14 July 2025 Resolved
Gauges to indicate engine revolutions per minute (RPM), jacket water discharge temperature, and lubricating oil pressure must be provided for all propulsion engines installed in the vessel. The gauges must be readily visible at the operating station. Port Main engine had non operational RPM and temperature gauge, Stbd Main engine had non operational oil pressure gauge.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 28 July 2025
Resolved 15 July 2025
Resolution: Gauges replaced and tested satisfactory
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 4 October 2024 Resolved
A pre-engineered fixed gas extinguishing system must be installed in accordance with the manufacturer's instructions. 46 CFR 181.420(4) System needs to be serviced and observed by Marine Inspector. Inspector will confirm that upon activation any associated equipment will not start or energize until override button is depressed.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Due 18 October 2024
Resolved 25 October 2024
Resolution: System was serviced and tech verified proper operation.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 3 October 2023 Resolved
Chemical testing of personnel must be conducted as required by this subpart and in accordance with the procedures detailed in 49 CFR part 40. During the inspection, three crew members were found not to be named on the 'covered list' for the marine employer. Require pre-employment testing and add to covered list all employees engaged in safety sensitive positions. 49 CFR 16.201(a)
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 3 October 2023
Resolution: Vessel has spare crew members that could fill vacant roles. The consortium list was updated.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 3 October 2023 Resolved
The master of each vessel subject to this subpart shall ensure that suitable... instructive placards... are provided in a manner which affords all passengers the opportunity to become acquainted with: Proper method of donning and adjusting life preservers of the type(s) carried on the vessel. Post life jacket donning instructions for all types of life jackets carried on board. 46 CFR 185.24(d)(2)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 6 October 2023
Resolution: Placard posted
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 3 October 2023 Resolved
The part of the exhaust system between the point of cooling water injection and the engine manifold must be water-jacketed or effectively insulated and protected. Renew damage lagging on port and starboard engine exhaust piping. 46 CFR 18.15-10(b)(3)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 6 October 2023
Resolution: New lagging installed
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 16 July 2020 Resolved
Each life preserver carried on a vessel must have at least 31 square inches of retro reflective material on each side. Replace retro reflective material on all life preservers. 46 CFR 180.25-25
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 30 July 2020
Resolved 17 July 2020
Resolution: Operator sent in photos of replaced retro-tape.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 19 September 2018 Resolved
FM-200 Audible and Visual alarm inop. at control station.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 October 2018
Resolved 4 October 2018
Resolution: Recieved proof of repair.
Communications › Radio Communications › EPIRB
Issued 3 October 2014 Resolved
Provide up to date hydrostatic release for EPIRB
Action required: 705 - Other - as specified
Due 15 October 2014
Resolved 14 October 2014
Resolution: Hydrostatic release for EPIRB has been renewed.
Navigation › Collision/Grounding Avoidance › Automatic Radar Plotting Aid (ARPA)
Issued 3 October 2014 Resolved
Prove operation of Radar for oceans route. 46 CFR 184.404(a)
Action required: 705 - Other - as specified
Due 15 October 2014
Resolved 14 October 2014
Resolution: Vessel tested operation of radar successfully.
Documentation › Manuals/Policy Documentation › Emergency Instructions
Issued 3 October 2014 Resolved
Post emergency instruction list. 46CFR185.512
Action required: 705 - Other - as specified
Due 15 October 2014
Resolved 14 October 2014
Resolution: Emergency instructions created and placed on vessel.
Communications › Radio Communications › EPIRB
Issued 13 June 2012 Resolved
Provide a functing EPIRB w/NOAA registration and hydro-static release. Vessel route is limited to not more than 3 miles from shore, and no more than 20 from a habor of safe refuge.
Action required: 705 - Other - as specified
Due 20 June 2012
Resolved 15 June 2012
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 13 June 2012 Resolved
Replaced all expired items in first aid kit.
Action required: 705 - Other - as specified
Due 20 June 2012
Resolved 15 June 2012
Electrical › Electrical Distribution System (service) › Circuit Breaker
Issued 13 June 2012 Resolved
Install circuit breaker blanks in fwd head distribution panel, and label all circuits.
Action required: 705 - Other - as specified
Due 20 June 2012
Resolved 15 June 2012
Navigation › Piloting/Steering › Marine Charts
Issued 30 August 2006 Resolved
Correct or renew charts of the Delaware Bay near shore chart.
Action required: 705 - Other - as specified
Due 20 October 2006
Resolved 17 June 2010
Navigation › Piloting/Steering › US Coast Pilot
Issued 30 August 2006 Resolved
Provide current Coast Pilot and Light list, or applicable exeprts.
Action required: 705 - Other - as specified
Due 20 October 2006
Resolved 17 June 2010
Fire Fighting › Portable Dry Chemical Fire Extinguisher › Pressure
Issued 30 August 2006 Resolved
Recharge or renew 2 BII fire extinguishers in well deck.
Action required: 701 - Prior to carriage of passengers/cargo
Due 20 September 2006
Resolved 22 September 2006
Lifesaving › Lifejacket/PFD (Type I) › Quantity
Issued 30 August 2006 Resolved
Provide 1 adult Type I life jacket, for a total of 20 adult Type I jackets onboard.
Action required: 701 - Prior to carriage of passengers/cargo
Due 20 November 2006
Resolved 22 September 2006
Communications › Radio Communications › VHF Radiotelephone
Issued 30 August 2006 Resolved
Provide FCC Radio installation certificate and radio operator permit.
Action required: 705 - Other - as specified
Due 20 October 2006
Resolved 17 June 2010
Stability › Freeing Ports › General
Issued 13 April 2006 Resolved
Make repairs to return the two forward drainage scuppers in the cockpit area back to the original 3 inch inlet and outlet configuration.
Due 30 April 2007
Resolved 20 September 2006
Communications › Radio Communications › EPIRB
Issued 21 June 2005 Resolved
The vessel is restricted to within three miles of shore until a new hydrostatic release unit it provided for the EPIRB.
Due 21 June 2005
Resolved 22 June 2005
Resolution: The operator faxed a copy of reciept for the purchase of a new HRU to the MSD.
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 21 June 2005 Resolved
Provide a 3-6 foot lanyard with a metalic clip for the ring buoy float light.
Due 21 July 2005
Resolved 18 July 2005
Fire Fighting › Portable Dry Chemical Fire Extinguisher › Location
Issued 21 June 2005 Resolved
Relocate one B-I portable fire extinquisher to the operating station.
Due 21 July 2005
Resolved 18 July 2005
Operations/Management › Drills/Instruction › Abandon Ship
Issued 21 June 2005 Resolved
Post emergency instructions and life jacket donning instructions in a passenger area.
Due 21 July 2005
Resolved 18 July 2005
Engineering › Bilge Water Management System › Pump
Issued 21 June 2005 Resolved
Repair or replace the bilge pump indicating lights at the operating station for the engine room and aft compartments.
Due 21 July 2005
Resolved 18 July 2005
Engineering › Diesel Engine (propulsion-reduction gear) › Crankshaft
Issued 21 June 2005 Resolved
Repair or replace the stbd main engine tachometer and demonstrate proper operation.
Due 21 July 2005
Resolved 18 July 2005
Accommodation/Occupational Safety › Medical/First Aid › Medicine Chest
Issued 21 June 2005 Resolved
Provide eyewash and asprins for the first aid kit.
Due 21 July 2005
Resolved 18 July 2005
Lifesaving › Lifejacket/PFD (General) › Lights
Issued 29 July 2003 Resolved
REPLACE 8 PFD LIGHTS WITH CG APPROVED.
Condition: Improper Installation
Due 29 July 2003
Resolved 29 July 2003
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 29 July 2003 Resolved
PROVE PROPER OPERATION OF FIXED EXTINGUISHING SYSTEM M/E SHUT DOWNS.
Condition: Improper/Lack of Maintenance
Due 29 July 2003
Resolved 29 July 2003
Stability › Watertight Integrity
Issued 29 July 2003 Resolved
PROVIDE CABLE FOR STERN COMPT HATCH COVER.
Condition: Improper/Lack of Maintenance
Due 29 July 2003
Resolved 29 July 2003
Engineering › Bilge Water Management System
Issued 29 July 2003 Resolved
PROVE PROPER OPERATION OF STERN COMPT. HIGH BILGE ALARM.
Condition: Improper/Lack of Maintenance
Due 29 July 2003
Resolved 29 July 2003

Casualty record · 1

9 July 2002Significant Marine Casualty · role: Involved in a Marine Casualty · serious marine incident, as classified · 1 dead · activity 1643590
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it, and the bridge, lock or dam the investigation names where it names one. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.

Recorded names · 1

REEL - ISTIC (2002). Names as the Coast Guard recorded them in incident records, with the years they appear; some are renames and some are spelling variants.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.