07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 23 January 2025
Resolved
A space containing propulsion machinery must be equipped with a fixed gas fire extinguishing system specifically approved by the Commandant. Vessel did not have USCG approved paperwork attesting to engineering requirements of installed high pressure CO2 system.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 November 2025
Resolution: Verified by attending MI
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 23 January 2025
Resolved
Complete but simple instructions for the operation of a fixed gas fire extinguishing system must be located in a conspicuous place. Fixed gas fire extinguishing system instructions did not provide a clear order of operation.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 November 2025
Resolution: Verified by attending MI
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 23 January 2025
Resolved
The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector. Vessel did not have fixed fire fighting system servicing records available for inspection.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 November 2025
Resolution: Verified by attending MI
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 23 January 2025
Resolved
At each inspection for certification and at every other vessel inspection all observed unsafe practices, fire hazards, and other hazardous situations must be corrected. MI Identified open venting gaskets on the engine room access hatches creating an improper seal to contain fixed fire extinguishing system gases.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 November 2025
Resolution: Verified by attending MI
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 23 January 2025
Resolved
Where subject to moisture, a storage cylinder must be installed to provide a space of at least 51 millimeters (2 inches) between the deck and the bottom of the storage cylinder. CO2 cylinder found stored on the deck.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 November 2025
Resolution: Verified by attending MI
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 23 January 2025
Resolved
Each life jacket must be marked with Type I retroreflective material. Found life jackets not fit for service with degraded missing retroreflective material.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 November 2025
Resolution: Verified by attending MI
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 23 January 2025
Resolved
Each ring life buoy must be marked with Type II retroreflective material. Found ring life buoy with degraded vessel name and retrorelective material.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 November 2025
Resolution: Verified by attending MI
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 23 January 2025
Resolved
Each floating waterlight on a vessel carrying only one ring buoy, must be attached to the lanyard with a corrosion-resistant clip. Found corroded lanyard clip.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 November 2025
Resolution: Verified by attending MI
10 - Safety of Navigation › N/A - No Subsystem › Voyage or passage plan
Issued 23 January 2025
Resolved
Before getting underway on a voyage or as soon as practicable thereafter, the master of a vessel shall ensure that suitable public announcements are made. MI observed the Master demonstrate a lack of competency in regards to providing a passenger safety brief.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 18 November 2025
Resolution: Verified by attending MI
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 23 January 2025
Resolved
All cable and wire must: Not be installed with sharp bends. MI identified battery cables installed with sharp bends and twists.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 November 2025
Resolution: Verified by attending MI
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 23 January 2025
Resolved
Minimize accidental personnel contact with energized parts. MI identified exposed wiring on port battery cable.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 November 2025
Resolution: Verified by attending MI
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 23 January 2025
Resolved
Each battery must be located as high above the bilge as practicable, secured to protect against shifting with the roll and pitch of the vessel, and free from exposure to water splash or spray. MI identified water inside the battery box.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 November 2025
Resolution: Verified by attending MI
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 23 January 2025
Resolved
The design of all exhaust systems must ensure minimum risk of injury to personnel. Protection must be provided at such locations where persons or equipment might come in contact with an exhaust pipe. MI identified exhaust piping with degraded lagging.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 November 2025
Resolution: Verified by attending MI
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 23 January 2025
Resolved
At each inspection for certification and at every other vessel inspection all observed unsafe practices, fire hazards, and other hazardous situations must be corrected and all required guards and protective devices must be in satisfactory condition. MI identified missing guards for rotating pulleys on both MDE's and both of the propulsion shafts.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 18 November 2025
Resolution: Verified by attending MI
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 23 January 2025
Resolved
Propulsion machinery must be suitable in type and design for propulsion requirements of the hull in which it is installed and capable of operating at constant marine load under such requirements without exceeding its designed limitations. Mi identified missing grease fittings on the shaft seal packing glands.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 18 November 2025
Resolution: Verified by attending MI
09 - Working and Living Conditions › 092 - Working Conditions › Lighting (Working spaces)
Issued 23 January 2025
Resolved
Each vessel must be equipped with at least two operable portable battery lights. One of these lights must be located at the operating station and the other at the access to the propulsion machinery space. MI Observed the machinery space portable light inoperable.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 18 November 2025
Resolution: Verified by attending MI
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 23 January 2025
Resolved
A vessel must carry a first-aid kit that meets the requirements in 46 CFR 199.175(b)(10) or a kit with equivalent content. First Aid kit not present on vessel.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 18 November 2025
Resolution: Verified by attending MI
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 22 January 2024
Resolved
Every vessel subject to Part III of Title III of the Communications Act must have a detailed inspection of the radio installation by an FCC-licensed technician in accordance with 46CFR80.59 once every five years. If the ship passes the inspection, the technician will issue a Communications Act Safety Radio-Telephony Certificate.
Each vessel must also carry a Bridge-to-Bridge Certificate with a valid endorsement while subject to the Bridge-to-Bridge Act. Inspector unable to verify certificate status because the vessel's Radio-Telephony and Bridge-to-Bridge Act certificates were faded and unreadable. Verify radio installation and post new certificates on the vessel.
46CFR80.903
46CFR80.1005
Action required: 16 - Rectify deficiencies w/in 14 days
Due 5 February 2024
Resolved 30 January 2024
Resolution: Provided photographic evidence of corrected deficiency.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 8 February 2023
Resolved
Propulsion machinery shall be suitable in type and design for propulsion requirements of the hull in which it is installed and capable of operating at constant marine load under such requirements without exceeding its designed limitations. Throttle controller was not working.
46 CFR 182.05-1(a)
(Old T)
Action required: 60 - Rectify deficiencies prior to movement
Due 8 February 2023
Resolved 24 February 2023
Resolution: Vessel conducted engineering tests proving full function.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 8 February 2023
Resolved
Installation of diesel engine exhaust pipe shall be in accordance with 46 CFR 182.182.15-20.
Exhaust piping shall be led to the point of escape with a minimum number of bends or elbows. It shall be gasket tight throughout its length and shall be properly supported by non-combustible hangers or blocks. MI observed exhaust leaking out of the exhaust manifold on both sides of the STBD MDE.
46 CFR 182.20-20(a)
(Old T)
46 CFR 182.15-20(a)
(Old T)
Action required: 60 - Rectify deficiencies prior to movement
Due 8 February 2023
Resolved 24 February 2023
Resolution: Vessel completed repairs satisfying the requirement.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 17 October 2022
Resolved
Vessels 26 ft up to 65 ft shall be provided with 1 fixed
power pump (10 GPM) and 1 portable hand pump (10 GPM).
Fixed power bilge pump was inoperable and portable hand
pump was not available for inspection.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 19 October 2022
Resolved 1 December 2022
Resolution: Bilge system was found operational.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 17 October 2022
Resolved
Employers must ensure that they and their crewmembers
meet the requirements of 46 CFR 16 – Chemical testing.
Vessel was unable to show proof of pre-employment
testing or enrollment in random drug testing program.
Action required: 701 - Prior to carriage of passengers/cargo
Due 19 October 2022
Resolved 12 December 2022
Resolution: Company provided chemical testing program evidence.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 17 October 2022
Resolved
Propulsion machinery must be suitable in type and design
for propulsion requirements of the hull in which it’s
installed and capable of operating at constant marine
load under such requirements without exceeding its
designed limitations. Marine inspector identified a lube
oil leak on the starboard main engine.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2022
Resolved 1 December 2022
Resolution: Repairs were conducted on the stbd ME.
02 - Structural Conditions › N/A - No Subsystem › Hull - cracking
Issued 17 October 2022
Resolved
At each initial and subsequent inspection for
certification of a vessel, the owner shall be prepared
to conduct tests and have the vessel ready for
inspections of the hull structure and its appurtenances,
inspection of all accessible parts of the exterior and
interior of the hull, the weathertight bulkheads, and
weather decks. Main deck had a crack in between engine
room hatches.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2022
Resolved 1 December 2022
Resolution: Cropped and renew the deck plated. All Sat.
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 17 October 2022
Resolved
Remove fuel shutoff station shall be marked in at least
1-inch indicating purpose of the valve and direction of
operation. Marine inspector identified the fuel shutoff
valve wasn’t properly labeled.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2022
Resolved 1 December 2022
Resolution: Fuel shut off labeled.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 17 October 2022
Resolved
Man over board and firefighting drills and training
shall be logged or otherwise documented for review by
the Coast Guard upon request. Vessel was unable to
provide log of any drills or training conducted.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2022
Resolved 1 December 2022
Resolution: Vessel provided logs of drill, kept in main office.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 17 October 2022
Resolved
Rails or equivalent protection shall be installed near
the periphery of all weather decks accessible to
passengers and crew. Aft safety chain is no longer
operable due to D ring broken off.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2022
Resolved 1 December 2022
Resolution: Repairs were conducted. All sat.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 17 October 2022
Resolved
Rails or equivalent protection shall be installed near
the periphery of all weather decks accessible to
passengers and crew. The aft railing had numerous
cracked welds throughout the courses.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 31 October 2022
Resolved 1 December 2022
Resolution: Repairs were conucted. All sat.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 23 September 2022
Resolved
The electrical equipment on a vessel must be installed and maintained to provide services necessary for safety under normal and emergency conditions. The vessel’s electrical system was found inoperable. The following systems were unable to be tested at the time of inspection: bilge pumps, high water alarms, radar, and navigation lights. Provide proper operation of the system.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 1 December 2022
Resolution: Vessel demonstrated proper operation of the systems.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 23 September 2022
Resolved
Unable to get underway to conduct drills due to inoperable electrical equipment throughout the vessel. Conduct satisfactory man overboard and fire drill in the presence of a marine inspector.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 12 December 2022
Resolution: Witnessed satisfactory drills while underway.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 23 September 2022
Resolved
Propulsion engines must have a gauge to indicate revolutions per minute. STBD engine tachometer does not accurately display the engine’s RPM. Conduct repairs.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 17 October 2022
Resolution: Verified repair of the stbd engine tachometer.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 23 June 2022
Resolved
Vessel must undergo an annual inspection within the 3 months before or after each anniversary date. Vessel has been out of service since being damaged during Hurricane Ida (AUG 2021) and failed to undergo second annual inspection within the 3 months before or after the anniversary date. Vessel's anniversary date is based off Certificate of Inspection issuance date of 14JAN2020. Vessel must complete satisfactory annual inspection prior to returning to service.
Action required: 701 - Prior to carriage of passengers/cargo
Due 23 June 2022
Resolved 12 December 2022
Resolution: Completed satisfactory annual inspection.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 23 June 2022
Resolved
All fixed gas fire extinguishing systems aboard a vessel
must be approved by the Commandant. The vessel
representative was unable to provide the approval for
the installed fixed firefighting system.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 November 2022
Resolved 12 December 2022
Resolution: Fixed gas fire extinguishing system has bee submitted to MSC for aprroval.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 23 June 2022
Resolved
Propulsion machinery must be suitable in type and design
for propulsion requirements of the hull in which it’s
installed and capable of operating at constant marine
load under such requirements without exceeding its
designed limitations. Port ME was inoperable. Vessel
engine conducted repairs.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 17 October 2022
Resolved 17 October 2022
Resolution: Vessel crew troubleshot port ME and was able to get it fixed. Conducted operational test to verify repairs.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 23 June 2022
Resolved
A space containing propulsion machinery must be equipped
with fixed gas fire extinguishing. The fixed
firefighting system was inoperable due to a tripped
fuse.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 17 October 2022
Resolved 17 October 2022
Resolution: Fuse was replaced and system was returned to
service.
04 - Emergency Systems › N/A - No Subsystem › Man Overboard Drill (MOB)
Issued 13 April 2021
Resolved
At each initial and subsequent inspection for certification, the marine inspector may require that an abandon ship or man overboard drill be held under simulated emergency conditions specified by the inspector.
Vessel did not conduct man overboard drill during previous inspection for certification. Marine Inspectors observed vessel master unable to retrieve rescue mannequin, man overboard drill unsatisfactory. Vessel to complete satisfactory man overboard drill prior to carriage of passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Due 16 June 2021
Resolved 16 June 2021
Resolution: Witnessed satisfactory MOB drill using minimum manning and 185lb OSCAR dummy.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 13 April 2021
Resolved
A vessel must be provided with a satisfactory arrangement for draining any watertight compartment, other than small buoyancy compartments, under all practicable conditions.
Marine Inspectors observed vessel fixed power bilge pump inoperable.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 13 May 2021
Resolved 15 June 2021
Resolution: Witnessed satisfactory operation of newly installed bilge pump.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 13 April 2021
Resolved
Each generator and motor must be designed for an ambient temperature of 50°C (122°F).
Marine Inspectors unable to confirm vessel generator ambient temperature requirement, generator data plate partially illegible.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 May 2021
Resolved 15 June 2021
Resolution: Verified installation of new and readable data plate with 50C rating.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machinery
Issued 13 April 2021
Resolved
An exposed hazard, such as gears or rotating machinery, must be properly protected by a cover, guard, or rail.
Marine Inspectors observed belts connecting STBD main engine to fixed power bilge pump not properly protected from hazard exposure.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 May 2021
Resolved 15 June 2021
Resolution: Newly installed bilge pump doesn't require guards for operation.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 3 February 2020
Resolved
vessels fixed fire-fighting system did not secure shipboard generator. Prior to movement fixed system shall be able to secure all internal combustion engines that share the engine space and proof of proper operation shall be provided to the cognizant OCMI.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 17 February 2020
Resolved 18 February 2020
Resolution: Generator shutdown system was installed on 2/18/20 to shutdown generator in the event fire extinguisher system is deployed.
System was checked by starting both main engines and generator engine,then deploying fire extinguisher check switch. All SAT
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 12 March 2019
Resolved
EACH FIXED POWER BILGE PUMP MUST BE SELF PRIMING. BILGE PUMP DID NOT OPERATE DURING INSPECTION. BILGE PUMP IS ALSO USED AS FIRE PUMP. FIRE PUMP DID NOT OPERATE DURING INSPECTION. CORRECT TO SATISFACTION OF ATTENDING MARINE INSPECTOR. 46 CFR 182.520(c) 60c
Action required: 60 - Rectify deficiencies prior to movement
Resolved 13 March 2019
Resolution: Received proof that bilge/fire pump was operating satisfactorily.
05 - Radio Communications › N/A - No Subsystem › Main installation
Issued 12 March 2019
Resolved
VESSELS OPERATED SOLELY WITHIN 20 NAUTICAL MILES OF LAND MUST BE EQUIPPED WITH A VHF-DSC RADIO. VHF RADIO WAS NOT OPERATING DURING INSPECTION. CORRECT TO SATISFACTION OF ATTENDING MARINE INSPECTOR. 47 CFR 80.905(a)(1), 47 CFR 80.871 60c
Action required: 60 - Rectify deficiencies prior to movement
Resolved 13 March 2019
Resolution: Received proof that radio was operating normally and proper radio checks were conducted.
10 - Safety of Navigation › N/A - No Subsystem › Nautical publications
Issued 12 March 2019
Resolved
VESSEL MUST CARRY UP-TO-DATE PUBLICATIONS AND CHARTS. PROVIDE UPDATED CHARTS AND PUBS TO SATISFACTION OF ATTENDING MARINE INSPECTOR. 46 CFR 184.420 16c
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 March 2019
Resolved 13 March 2019
Resolution: All outdated pubs were replaced with current ones.
Engineering › Fuel Oil Service System › Piping
Issued 18 April 2018
Resolved
Port engine fuel lines leaking fuel; repair or replace to the satisfaction of the attending USCG MI.
Action required: 701 - Prior to carriage of passengers/cargo
Due 18 April 2018
Resolved 2 May 2018
Resolution: Confirmed proper operation of Port Main Engine.
Engineering › Lubricating Oil Service System › Tube
Issued 28 March 2018
Resolved
STBD MDE water found draining from lube oil changing tube. Conduct repair and prove proper operation to attending Marine Inspector prior to moving vessel.
Action required: 60 - Rectify deficiencies prior to movement
Due 28 March 2018
Resolved 18 April 2018
Resolution: Company rebuilt engine and installed new motor. Verified operation to the satisfaction of attending USCG MI's.
Electrical › Electrical Distribution System (service) › Cable
Issued 28 March 2018
Resolved
STBD MDE starter cable found chaffed through near entry point to battery box. Replace cable to satisfaction of attending marine inspector.
Action required: 705 - Other - as specified
Due 30 April 2018
Resolved 18 April 2018
Resolution: Company replaced affected cable, as verified by the attending USCG MI.
Engineering › Steering Gear System › Rudder Stock
Issued 28 March 2018
Resolved
Steering space port rudder post found to have crack where frame and post meet. Conduct proper repair to the satisfaction of attending marine inspector.
Action required: 705 - Other - as specified
Due 30 April 2018
Resolved 18 April 2018
Resolution: Company repaired/rewelded affected area; repairs verified by attending USCG MI's.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 28 March 2018
Resolved
Found engine space emergency lighting is inoperable. Conduct repar to satisfaction of the attending marine inspector.
Action required: 705 - Other - as specified
Due 30 April 2018
Resolved 18 April 2018
Resolution: Company replaced affected light with new, as verified by the attending USCG MI.
Electrical › Electrical Distribution System (service) › Panelboard
Issued 28 March 2018
Resolved
Electrical distribution panel's generator ammeter lens missing cover. Correct or replace meter to satisfaction of attending marine inspector.
Action required: 705 - Other - as specified
Due 30 April 2018
Resolved 18 April 2018
Resolution: Company replaced affected lens cover, as verified by the attending USCG MI.
Electrical › Electric Supply System (service) › Battery Installation
Issued 16 March 2018
Resolved
2" of water found inside battery box located forward in engine space. Remove water to the satisfaction of the attending marine inspector.
Action required: 705 - Other - as specified
Due 30 April 2018
Resolved 18 April 2018
Resolution: Company removed water from battery box, as verified by attending USCG MI's.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 1 March 2016
Resolved
Installed CO2 system annual servicing not conducted, current/last service date Dec. 2014
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 March 2016
Resolved 9 March 2016
Resolution: Had fixed system tested to satisfaction of attending MI.
Fire Fighting › Ventilation Systems › Ventilation Fire Dampers
Issued 1 March 2016
Resolved
Engine room ventilation closures inoperable, unable to secure ventilation to a CO2 protected space.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 1 March 2016
Resolved 9 March 2016
Resolution: Cleaned overpainted vent slots. Operations verified by attending MI.
Construction/Loadline › Penetrations › Bottom Plug Packing
Issued 1 March 2016
Resolved
Forward engine room through bulkhead penetration for MDE J/W gauge is loose
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 March 2016
Resolved 1 March 2016
Resolution: Bulkhead penetration was tightened forming a watertight seal.
Engineering › Fuel Oil Service System › Tank
Issued 1 March 2016
Resolved
Fuel fill electrical bonding is not connected.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 March 2016
Resolved 1 March 2016
Resolution: fuel fill electrical bonding was tightened and corrected.
Engineering › Engine Controls (Electric/Electronic) › Linkage
Issued 1 March 2016
Resolved
Port MDE tachometer inoperable.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 8 March 2016
Resolved 9 March 2016
Resolution: Reconfigured Tachometer to read correctly to satisfaction of attending MI.
Operations/Management › Drug and Alcohol Testing › EAP Training Requirements
Issued 1 March 2016
Resolved
EAP contact numbers were inaccurate.
Condition: Invalid
Action required: 705 - Other - as specified
Due 8 March 2016
Resolved 9 March 2016
Resolution: Verified correct phone numbers listed for EAP to satisfaction of attending MI.
Electrical › Electric Supply System (service) › Battery Installation
Issued 1 March 2016
Resolved
Battery installation was unsat, water found in battery box . Vessel utilizing wing nuts to secure battery cables to terminals.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 March 2016
Resolved 1 March 2016
Resolution: Water removed from battery box and wing nuts replaced with appropriate fasteners.