PEGASUS

PEGASUS is a 1980 passenger vessel (inspected). The Coast Guard has recorded 76 inspections since 1984, most recently in July 2025, along with 86 deficiencies and 1 casualty investigation in 2025.

Records from 1984 to 2025. Most recent: inspection, 16 July 2025.

Built
1980
Last inspected
16 July 2025
Documentation
Valid · documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

WCQ7394
Flag
UNITED STATES
366671040 (licence lapsed)
Maury page id
psix-51212

Inspections, by type

…with no type recorded6
Years with a record 35 calendar years (1984–2025)
The 76 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Registered dimensions (L × B × D)64.8 ft × 19.1 ft × 8.0 ft
Registered tonnagegross 64 / net 47
ITC dimensions (L × B × D)Not recorded
ITC tonnageNot recorded
BuilderKELLY'S ENTERPRISES INC · WESTPORT WA, UNITED STATES · built 1980
Hull materialFRP (Fiberglass)
PropulsionDiesel Reduction
Hull shapeNot recorded
Hull configurationNot recorded
Hailing portSAN DIEGO, CA
Trade endorsementsCoastwise, unrestricted, Registry
DocumentationValid · issued 29 April 2026 · expires 31 March 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it64 - Regulatory (Subpart C or D), Gross Ton
47 - Regulatory (Subpart C or D), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.

Radio station licence

WCQ7394MMSI 366671040 · expired · compulsorily equipped · granted 13 January 2015, cancelled 24 May 2025
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown. A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.

Inspection history · 76

16 July 2025 Vessel Attendance · Internal Structural Exam · Damage Survey · Drydock Exam · COI Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 8188333
16 July 2025 Type not recorded
No type recorded · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 8199937
28 April 2025 Annual Inspection · Deficiency Check
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 8123192
19 February 2025 Drydock Exam · Deficiency Check · Internal Structural Exam
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 8081429
4 April 2024 Annual Inspection · Deficiency Check
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7890150
6 April 2023 Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7643377
27 March 2023 In-Service Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7662823
14 February 2023 Drydock Exam
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7636456
21 October 2022 In-Service Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7573597
11 April 2022 Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7429068
16 March 2021 Deficiency Check · COI Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7150895
9 February 2021 Internal Structural Exam · Drydock Exam
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 7138121
28 April 2020 Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6944852
29 January 2020 Deficiency Check
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6899273
30 September 2019 In-Service Inspection · Deficiency Check
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6824402
16 April 2019 Deficiency Check · Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6663555
5 March 2019 Drydock Exam
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6636850
7 March 2018 Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6367921
7 February 2018 Hull Examination
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6351122
16 January 2018 Administrative Inspection
Administrative · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6338791
17 April 2017 Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6126167
21 March 2016 COI Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 5833417
5 January 2016 Hull Examination · Internal Structural Exam
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 5791072
17 March 2008 Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 3166131
17 January 2008 Hull Examination
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 3130674
13 March 2007 Deficiency Check · Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 2882058
24 March 2006 COI Inspection · Deficiency Check · Administrative Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 2607568
8 February 2006 Hull Examination
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 2575942
18 November 2005 Construction Oversight
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 2537323
24 March 2005 Annual Inspection
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 2318865
2 April 2004 Annual Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 2029691
11 December 2003 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1962535
7 April 2003 Re-Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1768252
19 March 2002 Re-Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1492910
16 January 2002 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1478966
27 March 2001 Deficiency Check
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1061478
5 March 2001 COI Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1430994
29 January 2001 Type not recorded
No type recorded · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1391632
21 March 2000 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1448078
6 March 2000 Re-Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1436341
21 June 1999 Type not recorded
No type recorded · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 881524
8 March 1999 Re-Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1436174
5 March 1999 Plan Review "T" Boat
Administrative · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 801180
6 May 1998 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1390770
9 March 1998 COI Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1445324
13 March 1997 Re-Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1402404
14 June 1996 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1363774
6 June 1996 Administrative
Administrative · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 878827
13 March 1996 Re-Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 1441045
28 November 1995 Type not recorded
No type recorded · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 143633
10 March 1995 COI Inspection
Physical examination · MSO LOS ANGELES/LONG BEACH · USCG Southwest District (CGD-SW) · Activity 863747
2 December 1994 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1389928
26 September 1994 Drydock Extension
Administrative · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1354951
17 May 1994 Re-Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1419274
15 April 1993 Deficiency Check
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1150467
15 April 1993 Re-Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1460632
30 September 1992 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1249334
10 June 1992 Administrative
Administrative · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 954115
5 March 1992 COI Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1314872
15 May 1991 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 900404
20 March 1991 Deficiency Check
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1236179
8 March 1991 Re-Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1215903
30 April 1990 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1225439
7 March 1990 Re-Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1214751
27 June 1989 Deficiency Check
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1203467
20 April 1989 Deficiency Check
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1198144
14 April 1989 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1204634
27 March 1989 Deficiency Check
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1038518
9 March 1989 COI Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 889612
20 April 1988 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1340002
17 March 1988 Re-Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1030979
22 April 1987 Hull Examination
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1003930
13 March 1987 Deficiency Check · Re-Inspection
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1009274
20 March 1986 Deficiency Check · COI Inspection · Credit Drydock
Physical examination · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1304241
22 March 1985 Type not recorded
No type recorded · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 1288792
9 November 1984 Type not recorded
No type recorded · MSO SAN DIEGO · USCG Southwest District (CGD-SW) · Activity 974552

Deficiency record · 86

02 - Structural Conditions › N/A - No Subsystem › Hull damage impairing seaworthiness
Issued 16 July 2025 Resolved
The FRP port side, side-shell in the forward storage compartment suffered de-lamination from a fire on board the vessel. The vessel is required to be hauled out and the failed fiberglass area cut out and removed to good material. Damaged area extends below the chine. Request USCG attendance once damaged area is removed and to solid FRP. Submit written repair proposal to Sector San Diego prior to making any repairs.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 April 2026
Resolution: Vessel completed satisfactory repairs
02 - Structural Conditions › N/A - No Subsystem › Bulkheads - operational damage
Issued 16 July 2025 Resolved
Forward and aft plywood bulkheads both suffered structural damage, submit written repair proposal to renew both forward and aft bulkheads on the port side of forward storage compartment.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 April 2026
Resolution: Vessel completed satisfactory repairs
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-op. damage
Issued 16 July 2025 Resolved
Port side deck beams and compartment overhead suffered structural damage, submit plan to renew port side deck beams and overhead.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 April 2026
Resolution: Vessel completed satisfactory repairs
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 16 July 2025 Resolved
All electrical equipment and cabling was damaged beyond repair. Submit written electrical plans to renew all equipment and wiring.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 15 April 2026
Resolution: Vessel completed satisfactory repairs
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 28 April 2025 Resolved
A visual and audible indicator must be provided at the operating station to indicate when any automatic bilge pump is operating. Bilge pump indicator at helm not operational. Provide visual and audible indicator for bilge pumps.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 May 2025
Resolution: [name withheld] attended vessel. All SAT.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 28 April 2025 Resolved
Vessel that have overnight accommodations must have interconnected fire detection system. Smoke detectors would operate but would not turn off until battery was removed. Fix interconnected smoke detection and notify local OCMI.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 May 2025
Resolution: [name withheld] attended vessel. All SAT.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 28 April 2025 Resolved
The owner, charterer, master, or managing operator of a vessel carrying overnight passengers shall have a suitable number of watchmen patrol throughout the vessel during the nighttime, whether or not the vessel is underway, to guard against, and give alarm in case of, a fire, man overboard, or other dangerous situation. Vessel watchman system operated but does not have a dedicated way to communicate with the system other than an app on a personal cell phones. Master of the vessel must have app installed on phone to operate watchman system until a permanent solution is on board.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 May 2025
Resolution: Observed Master operate watch system alarm, tested E/R and bunk spaces. All SAT
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 28 April 2025 Resolved
Portable and semi-portable extinguishers must be inspected and maintained in accordance with NFPA 10. The owner or managing operator must provide satisfactory evidence of the required servicing to the marine inspector.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 May 2025
Resolution: [name withheld] attended vessel. All SAT.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 28 April 2025 Resolved
Marine employers shall establish programs for the chemical testing for dangerous drugs on a random basis of crewmembers on inspected vessels who occupy a position or perform the duties and functions of a position, required by the vessel's COI. Marine employers may form or otherwise use sponsoring organizations, or may use contractors to conduct the random chemical testing programs. Vessel's consortium enrollment paperwork expired.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 May 2025
Resolution: [name withheld] attended vessel. All SAT.
05 - Radio Communications › N/A - No Subsystem › Other (radio communication)
Issued 28 April 2025 Resolved
The owner or managing operator of a vessel shall ensure that the vessel complies with the laws and regulations applicable to the vessel and that the vessel is otherwise satisfactory for the intended service. The initial inspection may include an inspection of the following items: Certificates and operating manuals, including certificates issued by the FCC. FCC Safety Radio Certificate not issued by FCC licensed technician.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 May 2025
Resolved 1 May 2025
Resolution: [name withheld] attended vessel. All SAT.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 28 April 2025 Resolved
A pre-engineered fixed gas fire extinguishing system must: Be installed in accordance with the manufacturer's instructions. 3" hole between engine room and head allow fixed fire extinguishing medium to communicate through bulkhead. Make vapor tight to ensure quantity of extinguisher is sufficient.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 May 2025
Resolution: [name withheld] attended vessel. All SAT.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 28 April 2025 Resolved
Provision must be made for closing all supply duct cowls or scoops and exhaust duct discharge opening for a space protected by a fixed gas extinguishing system. Vent closure was not operational. Provide operational vent closures for engine room.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 May 2025
Resolution: [name withheld] attended vessel. All SAT.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 28 April 2025 Resolved
Electrical equipment on a vessel must be installed and maintained to minimize accidental personnel contact with energized parts. Dead end wires found in engine room(Gen) and under helm. Remove dead end wiring and update electrical plans.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2025
Resolved 1 May 2025
Resolution: [name withheld] attended vessel. All SAT.
09 - Working and Living Conditions › 092 - Working Conditions › Lighting (Working spaces)
Issued 28 April 2025 Resolved
Each lighting fixture must be fixed and covered. Vessel had 1 light in E/R that was not fixed and 1 that had no cover. Replace and notify local OCMI.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 13 May 2025
Resolved 1 May 2025
Resolution: [name withheld] attended vessel. All SAT.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 28 April 2025 Resolved
Battery installations must be mounted t46 CFR 183.350 to protect against shifting of the vessel and free from exposure to water splash or spray. Vessel's MDE's batteries were siting in water and not properly secured/enclosed. Provide suitable protection against exposure to water or spray.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 May 2025
Resolution: [name withheld] attended vessel. All SAT.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 28 April 2025 Resolved
Each vessel must have adequate emergency lighting fitted along thee of escape to the main deck from all passenger and crew accommodation spaces located below the main deck. MI closed both hatches to the accommodation spaces and was unable to see the emergency exit sign. Provide lights to illuminate the emergency exit signs.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 1 May 2025
Resolution: [name withheld] attended vessel. All SAT.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 28 April 2025 Resolved
Electrical equipment on a vessel must be installed and maintained to protect passengers, crew, other persons, and the vessel from electrical hazards, including fire, caused by or originating in electrical equipment, and electrical shock. Both MDE's ECU's showed signs of salt water leaking on it. Water leak could not be traced. Clean electrical connect and cover ECU's to protect from salt water damage.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 May 2025
Resolution: Observed ECUs connections, covers, and observed no leakage of salt water at time of inspection. All SAT
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 28 April 2025 Resolved
Propulsion machinery must be suitable in type and design for propulsion requirements of the hull in which it is installed and capable of operating at constant marine load under such requirements without exceeding its designed limitations. Vessel MDE's failed to start when trying to get underway. Correct issue with MDE's and notify local OCMI.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 May 2025
Resolution: Observed starting of both MDEs. All SAT
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 April 2025 Resolved
Vessel still needs to get underway to conduct drills and fire boy still needs to be tested before inspection is complete.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 5 May 2025
Resolution: Conducted U/W drills, tested Fire boy, and Fire boy over-ride. All SAT
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 19 February 2025 Resolved
Vessel completed dry dock and has not completed IFR drills. Vessel is prohibited from carrying overnight passengers or allowing passengers in the bunk rooms until an egress drill is completed.
Action required: 705 - Other - as specified
Resolved 3 April 2025
Resolution: Egress drills complete, final IFR approval letter signed 03APR25.
01 - Certificates & Documentation › 012 - Crew Certificates › Certificates for radio personnel
Issued 4 April 2024 Resolved
A vessel must comply with the applicable requirements for any radio and Electronic Position Indicating Radiobeacon (EPIRB) installations, including the requirements for a station license and installation certificates to be issued by the Federal Communications Commission, as set forth in 47 CFR part 80. Marine Inspector (MI) found the operator does not have a radio operators permit and the radio station authorization is still under the old owners name. Get a radio operator permit and update the radio station authorization.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 April 2024
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 4 April 2024 Resolved
No marine employer shall engage or employ any individual to serve as a crewmember unless the individual passes a chemical test for dangerous drugs for that employer. Owner must have new crewmembers produce a negative chemical test prior to employing ion a safety sensitive position. 2 new crewmember were recently hired and need to complete a preemployment drug test. Also, the DAPI program crew list needs to be updated to reflect the current crew.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 April 2024
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 4 April 2024 Resolved
eans, coastwise, limited coastwise, and Great Lakes routes. A vessel on an oceans, coastwise, limited coastwise, or Great Lakes route must carry a certian number of flares. MI found the vessel had 09 flare out of the required 12. Add 3 more flare in accordance with the regulation.
Action required: 705 - Other - as specified
Resolved 10 April 2024
03 - Water/Weathertight Conditions › N/A - No Subsystem › Scuppers, inlets and discharges
Issued 4 April 2024 Resolved
in systems and applications where flexible hoses are permitted to be clamped, two clamps must be used on each end of the hose, or one hose clamp can be used if the pipe ends are expanded or beaded to provide a positive stop against hose slippage.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 April 2024
04 - Emergency Systems › N/A - No Subsystem › Functionality of Safety Systems
Issued 4 April 2024 Resolved
The installation of fuel lines, including pipe, tube, and hose, must comply with the requirements of this paragraph. MI found that the reach rod for the emergency fuel shut-off was not properly secured and the valve was started to break. Properly secure reach rod and fix valve.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 April 2024
03 - Water/Weathertight Conditions › N/A - No Subsystem › Manholes/flush scuttles
Issued 4 April 2024 Resolved
A hatch exposed to the weather must be watertight, except that the following hatches may be weathertight. MI found 2 dogs on the hatch to the lazarette were not functioning properly. Replace 2 dogs and inform local OCMI when repaired.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 April 2024
03 - Water/Weathertight Conditions › N/A - No Subsystem › Scuppers, inlets and discharges
Issued 4 April 2024 Resolved
Each watertight bulkhead must be of sufficient strength to be capable of remaining watertight with a head of water to the top of the bulkhead. MI found 2 fitting in the engine room that were not capped off. Cap off both to protect from flooding.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 10 April 2024
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 16 March 2021 Resolved
Prove operation of faulty bilge high water alarm in lazarette.
Condition: Damaged By Earlier Event
Action required: 10 - Deficiency Rectified
Due 16 March 2021
Resolved 16 March 2021
Resolution: Replaced float switch.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 30 September 2019 Resolved
Vessel has been identified as having various A/C electrical modifications since initial certification. Sector San Diego does not have vessels electrical plans on file or current installations do not match what we have on file. Provide a one-line electrical drawing for all A/C switchboards and distribution panels. Include all circuit loads, conductor sizes, over current protection, and max panel ratings in amps.
Action required: 705 - Other - as specified
Due 30 December 2019
Resolved 29 January 2020
Resolution: Verified corrected plans.
01 - Certificates & Documentation › 012 - Crew Certificates › Manning specified by the minimum safe manning doc
Issued 30 September 2019 Resolved
While underway or drifting at sea, every vessel shall at all times maintain a proper look-out by sight and hearing. The designated watchmen required by 46 CFR 185.410 cannot preform both roving patrolling and look-out watch simultaneously. Vessel has been instructed to operate with a look-out and watchman while conducting drift operations.
Action required: 10 - Deficiency Rectified
Due 30 September 2019
Resolved 30 September 2019
Resolution: On the spot cleared, educated operator.
07 - Fire Safety › N/A - No Subsystem › Ventilation
Issued 30 September 2019 Resolved
Provision shall be made by means of plugs, covers, etc. to prevent the admission of air into the space protected by CO2 fixed fire fighting system. Provide ventilation closure devices for ventilation supply and exhaust openings. Devices shall be kept in vicinity of vents.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 October 2019
Resolved 30 October 2019
Resolution: Vessel constructed covers that are attached using bungee cords.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 30 September 2019 Resolved
Electrical equipment must be installed and maintained to protect passengers, crew and the vessel from electrical hazards, including fire, caused by or originating in electrical equipment and electrical shock. Correct the following: (1)Label sub-panel for sodium-vapor lamps (2)Remove "daisy chained" surge protectors in wheelhouse as discussed (3) Remove extension cord found passing through two bulkheads on port side from storage area. (4) Properly wire lighting fixture in storage area as discussed.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 30 October 2019
Resolved 30 October 2019
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 30 September 2019 Resolved
Mark emergency exit signage with arrows indicating direction to emergency exit. Mark emergency exit hatch with push and arrow of direction to push hatch.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 October 2019
Resolved 11 October 2019
Resolution: Verified signs installed.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 16 April 2019 Resolved
Repair 02 life floats with weather damage. Seal cracks and holes on exterior.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 May 2019
Resolved 17 April 2019
Resolution: Received pictures.
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 21 March 2016 Resolved
Provide proper color life ring buoy for aft location
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2016
Resolved 30 March 2016
Fire Fighting › Ventilation Systems › Ducts
Issued 21 March 2016 Resolved
Provide acceptable means to prevent the admission of air into the into the space protected by the fixed fire fighting sytems.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2016
Resolved 30 March 2016
Resolution: An acceptable means to prevent air from entering the E/R after a fire was inspected by by the attending Marine Inspector.
Electrical › Electric Supply System (service) › Battery Installation
Issued 21 March 2016 Resolved
Cover terminals on batteries under the pilothouse.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 April 2016
Resolved 30 March 2016
Resolution: Battery terminals are now covered.
Communications › Radio Communications › Radiotelephone Transceiver (2-27.5 MHz)
Issued 17 March 2008 Resolved
Vsl is limited to 100 n-mile to shore util DSC/SSB is installed
Action required: 705 - Other - as specified
Resolved 20 April 2009
Navigation › Piloting/Steering › Notices to Navigation
Issued 13 March 2007 Resolved
Vsl is limited to 100 mile from shore until Navtex is installed.
Action required: 705 - Other - as specified
Resolved 20 August 2007
Resolution: Vsl installed Navtex
Documentation › Certificates/Documents › Certificate of Inspection
Issued 24 March 2006 Resolved
COI expired. Vessel to complete COI inspection prior to carrying passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 March 2006
Resolved 24 March 2006
Resolution: Completed satisfactory COI exam.
Fire Fighting › Ventilation Systems › Exhaust Ducts (Galley Ranges)
Issued 24 March 2006 Resolved
Clean excessive grease from grease trap/ventilation system in galley.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 24 April 2006
Resolved 29 March 2006
Lifesaving › Lifebuoys › Self-igniting Lights
Issued 24 March 2006 Resolved
Provide removable metallic clip on life ring waterlight lanyard vice splicing lanyard around lifering.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 24 April 2006
Resolved 26 August 2016
Resolution: New clip installed.
Operations/Management › Navigation Safety › Carriage of Charts and Publications
Issued 24 March 2006 Resolved
Provide up-to-date chart, U.S. Coast Pilot, and CG Light List, or excerpts from same, for areas vessel transits.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 24 April 2006
Resolved 29 March 2006
Electrical › Electrical Distribution System (service) › Wiring
Issued 24 March 2005 Resolved
Ensure freezer is hardwired to vessel electrical system.
Condition: Unknown
Due 20 April 2005
Resolved 12 April 2005
Electrical › Electrical Distribution System (service) › Wiring
Issued 24 March 2005 Resolved
Disconnect or hardwire secondary bilge pump in engine room.
Condition: Improper Installation
Due 20 April 2005
Resolved 12 April 2005
Lifesaving › Buoyant Apparatus › Serviceable
Issued 2 April 2004 Resolved
Port Life Floats were missing one paddle and the sea painter was not properly installed and needed to be renewed. LEGACY COMPONENT DESC: Sea Painter
Action required: 701 - Prior to carriage of passengers/cargo
Due 9 April 2004
Resolved 5 April 2005
Communications › Radio Communications › EPIRB
Issued 2 April 2004 Resolved
Hydrostatic release was expired on EPIRB. Instructed master to renew and provide receipt.
Action required: 701 - Prior to carriage of passengers/cargo
Due 9 April 2004
Resolved 6 April 2005
Resolution: Hydrostatic release was up to date.
Lifesaving › Lifebuoys › Serviceable
Issued 2 April 2004 Resolved
Grab line on aft life ring needed to be renewed. LEGACY COMPONENT DESC: Buoyant Lifeline
Condition: Unknown
Action required: 701 - Prior to carriage of passengers/cargo
Due 9 April 2004
Resolved 5 April 2005
Construction/Loadline › Structures
Issued 19 March 2002 Resolved
Seal hydraulic lines through ER and Lazarette bulkheads LEGACY COMPONENT DESC: Transverse Bulkhead
Condition: Improper/Lack of Maintenance
Due 22 March 2002
Resolved 21 March 2002
Construction/Loadline › Structures
Issued 19 March 2002 Resolved
Seal electrical cable way from Lazarette to ER LEGACY COMPONENT DESC: Transverse Bulkhead
Condition: Improper/Lack of Maintenance
Due 21 March 2002
Resolved 21 March 2002
Electrical › Electrical Distribution System (service)
Issued 19 March 2002 Resolved
Reseat electrical cable into connector on hot water heater. LEGACY COMPONENT DESC: Cable
Condition: Improper/Lack of Maintenance
Due 22 March 2002
Resolved 21 March 2002
Fire Fighting › Remote Fuel Shutoff
Issued 19 March 2002 Resolved
Replace broken reach rod on port FO cutoff valve and properly label.
Condition: Improper/Lack of Maintenance
Due 22 March 2002
Resolved 21 March 2002
Engineering › Bilge Water Management System
Issued 19 March 2002 Resolved
Repair inoperative Lazarette bilge alarm. LEGACY COMPONENT DESC: Interface Detector
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 22 March 2002
Resolved 21 March 2002
Lifesaving › Buoyant Apparatus
Issued 19 March 2002 Resolved
Replace retro reflective tape on port, lower life-float
Condition: Improper/Lack of Maintenance
Due 22 March 2002
Resolved 21 March 2002
Engineering › Fuel Oil Service System
Issued 19 March 2002 Resolved
Properly ground fuel fill piping LEGACY COMPONENT DESC: Piping
Condition: Improper Installation
Due 22 March 2002
Resolved 21 March 2002
Documentation
Issued 5 March 2001 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Unknown
Due 5 March 2001
Resolved 5 March 2001
Lifesaving
Issued 5 March 2001 Resolved
Limited to carry total of (30) passengers & crew if additional life floats are not received by 11 March, 2001.
Condition: Unknown
Due 5 March 2001
Resolved 5 March 2001
Documentation
Issued 5 March 2001 Resolved
Training logs for man overboard & e-pirb testing not current.
Condition: Unknown
Due 5 March 2001
Resolved 7 March 2001
Construction/Loadline
Issued 29 January 2001 Resolved
Provide damage control kit consisting of a mallet, various sized cone plugsand oakum in a labeled container/bag. Kit is to be stored in an accessible area above the bulkhead deck.
Condition: Unknown
Due 8 February 2001
Resolved 8 February 2001
Construction/Loadline
Issued 29 January 2001 Resolved
Provide metallic valves and penetrations for PVC piping traversing watertight bulkhead.
Condition: Unknown
Due 1 February 2002
Resolved 8 March 2002
Accommodation/Occupational Safety
Issued 8 March 1999 Resolved
Overnight accommodation compartment missing independent modular smoke and fire alarms as per 46CFR181.410
Condition: Unknown
Due 22 March 1999
Resolved 16 March 1999
Lifesaving
Issued 8 March 1999 Resolved
Vessels name not clearly marked on lifefloat paddles & ring Buoy lifeline needs renewed (worn). IAW 46 CFR 185.604 & 46 CFR 180.70.
Condition: Unknown
Due 22 March 1999
Resolved 16 March 1999
Engineering
Issued 8 March 1999 Resolved
Missing protective screen on engine room supply fan, IAW 46 CFR 182.465
Condition: Unknown
Due 22 March 1999
Resolved 16 March 1999
Lifesaving
Issued 8 March 1999 Resolved
EPIRB monthly test not logged as per 46 CFR 185.728.
Condition: Unknown
Due 9 March 1999
Resolved 16 March 1999
Documentation
Issued 5 March 1992 Resolved
PROVIDE ALL REQUIRED RADIO EQUIPMENT OUTLINED IN 47CFR80.905(a)(3), OR OBTAIN AN EXEMPTION FROM FCC. VESSEL ROUTE LIMITED TO 100 NAUTICAL MILES OFFSHORE.
Condition: Unknown
Due 5 March 1992
Resolved 5 March 1992
Accommodation/Occupational Safety
Issued 8 March 1991 Resolved
INCREASE MARINE SANITATION DEVICE HOLD TANKS CAPACITY TO AT LEAST 48_x001C_ GALLONS PROVIDED THAT THE ONE GALLON PER FLUSH ADJUSTMENT FOR THE FLUSHOMETER FOR THE TOILETS ADEQUATELY OPERATES.
Condition: Unknown
Due 8 March 1991
Resolved 8 March 1991
Accommodation/Occupational Safety
Issued 8 March 1991 Resolved
PROVIDE PLANS TO [name withheld] FOR MODIFICATION OF PRESENT MARINE_x001C_ SANITATION TANKS IN ORDER TO INCREASE CAPACITY._x001C_ _x001C_ _x001C_
Condition: Unknown
Due 8 March 1991
Resolved 8 March 1991
Navigation
Issued 14 April 1989 Resolved
REPLACE HARD PLASTIC HYDRAULIC LINES FOR THE STEERING SYSTEM WITH A COAST GUARD APPROVED HYDRAULIC LINES.
Condition: Unknown
Due 14 April 1989
Resolved 14 April 1989
Unknown
Issued 27 March 1989 Resolved
INSTALL A VENT FOR THE BATTERY CHARGING SYSTEM UNDERNEATH CONTROL CONSOLE IN THE PILOTHOUSE TO EXHAUST OUTSIDE THE PILOTHOUSE.
Condition: Unknown
Due 27 March 1989
Resolved 27 March 1989
Unknown
Issued 9 March 1989 Resolved
PROVIDE CURRENT NAVIGATION PUBLICATIONS SUCH AS PACIFIC COAST PILOT, TIDE AND CURRENT TABLES.
Condition: Unknown
Due 9 March 1989
Resolved 9 March 1989
Unknown
Issued 9 March 1989 Resolved
POST A NO SMOKING SIGN IN THE PILOTHOUSE DUE TO NATURAL VENTILATION OF BATTERY CHARGING SYSTEM EXHAUST LEADS INSIDE THE PILOTHOUSE.
Condition: Unknown
Due 9 March 1989
Resolved 9 March 1989
Lifesaving
Issued 9 March 1989 Resolved
REPLACE THE TWO(2) WORN OUT 15-MAN LIFE FLOATS.
Condition: Unknown
Due 9 March 1989
Resolved 9 March 1989
Navigation
Issued 9 March 1989 Resolved
PROVIDE A CURRENT MAGNETIC COMPASS DEVIATION CARD.
Condition: Unknown
Due 9 March 1989
Resolved 9 March 1989
Electrical
Issued 17 March 1988 Resolved
REPAIR ELECTRICAL WIRING SPLICES BEHIND PILOTHOUSE CONTROL CONSOLE WITH METAL CRIMP CONNECTOR.
Condition: Unknown
Due 17 March 1988
Resolved 17 March 1988
Electrical
Issued 17 March 1988 Resolved
REMOVE ELECTRICAL WIRES BEHIND PILOTHOUSE CONTROL CONSOLE THAT ARE NOT IN SERVICE.
Condition: Unknown
Due 17 March 1988
Resolved 17 March 1988
Lifesaving
Issued 17 March 1988 Resolved
REPLACE WORN/WASTED GRAB LINES ON TWO(2) LIFE FLOATS PRIOR TO PLACING VESSEL IN OPERATION.
Condition: Unknown
Due 17 March 1988
Resolved 17 March 1988
Lifesaving
Issued 17 March 1988 Resolved
REPAIR INOPERABLE FLOAT LIGHTS ON TWO(2) LIFE FLOATS PRIOR TO PLACING VESSEL IN OPERATION.
Condition: Unknown
Due 17 March 1988
Resolved 17 March 1988
Navigation
Issued 17 March 1988 Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Unknown
Due 17 March 1988
Resolved 17 March 1988
Lifesaving
Issued 13 March 1987 Resolved
MARK VESSELS NAME ON STBD BOUYANT APPARATUS.
Condition: Unknown
Due 13 March 1987
Resolved 13 March 1987
Lifesaving
Issued 13 March 1987 Resolved
MARK VESSELS NAME ON PADDLES FOR BOUYANT APPARATUS.
Condition: Unknown
Due 13 March 1987
Resolved 13 March 1987
Lifesaving
Issued 13 March 1987 Resolved
MARK HAILING PORT ON BOTH LIFE RINGS.
Condition: Unknown
Due 13 March 1987
Resolved 13 March 1987
Construction/Loadline
Issued 13 March 1987 Resolved
TREAT WOOD IN OVERHEAD OF LAZARETTE AND FWD BUNKROOM COMPARTMENT IN WAY OF DRY ROT.
Condition: Unknown
Due 13 March 1987
Resolved 13 March 1987
Lifesaving
Issued 13 March 1987 Resolved
REPAIR BOTH BOUYANT APPARATUS.
Condition: Unknown
Due 13 March 1987
Resolved 13 March 1987
Lifesaving
Issued 20 March 1986 Resolved
RENEW TENDING LINES ON BOTH 15 MAN LIFEFLOATS
Condition: Unknown
Due 20 March 1986
Resolved 20 March 1986
Lifesaving
Issued 20 March 1986 Resolved
PROCURE 2 CG APPROVED ADULT PFD WITH LIGHTS
Condition: Unknown
Due 20 March 1986
Resolved 20 March 1986
Electrical
Issued 20 March 1986 Resolved
PROVE PROPER OPERATION OF EMERGENCY LIGHTS
Condition: Unknown
Due 20 March 1986
Resolved 20 March 1986

Casualty record · 1

16 July 2025Routine · role: Involved in a Marine Casualty · activity 8199937
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it, and the bridge, lock or dam the investigation names where it names one. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.