Records from 1984 to 1998. Most recent: inspection, 27 July 1998.
A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.
Inspection history · 33
27 July 1998
Administrative
Administrative · Activities Europe · Activity 1129661
14 November 1997
Administrative
Administrative · Activities Europe · Activity 1121794
3 June 1997
Administrative
Administrative · Activities Europe · Activity 775872
31 January 1997
Deficiency Check
Physical examination · Activities Europe · Activity 1101573
10 December 1996
COI Inspection
Physical examination · Activities Europe · Activity 1357825
8 December 1995
Re-Inspection
Physical examination · Activities Europe - OLD · USCG Northeast District (CGD-NE) · Activity 1353833
7 April 1995
Deficiency Check
Physical examination · Activities Far East · USCG Oceania District (CGD-O) · Activity 842135
12 January 1995
COI Inspection · MARPOL Annex V Examination · Hull Examination
Physical examination · Activities Far East · USCG Oceania District (CGD-O) · Activity 864387
22 July 1994
Type not recorded
No type recorded · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1175360
19 July 1994
Administrative
Administrative · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 862327
24 October 1993
Re-Inspection · MARPOL Annex V Examination
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 845168
8 March 1993
Hull Examination
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1147351
26 November 1992
COI Inspection
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1134752
29 January 1992
Re-Inspection
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 943498
26 November 1990
COI Inspection
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1232421
5 August 1990
Deficiency Check
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 912731
26 July 1990
Deficiency Check
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1236156
5 January 1990
Deficiency Check
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 921863
4 January 1990
Hull Examination
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1134503
4 January 1990
Re-Inspection · Hull Examination
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1231412
29 December 1989
Administrative
Administrative · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 921698
28 December 1989
Type not recorded
No type recorded · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1227745
23 June 1989
Drydock Extension
Administrative · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 897384
5 December 1988
Drydock Extension · COI Inspection
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 893080
25 October 1988
Administrative
Administrative · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1199774
29 February 1988
Deficiency Check
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 987351
18 February 1988
Deficiency Check
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1023429
25 November 1987
Re-Inspection
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1335023
3 December 1986
Hull Examination · COI Inspection
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1026376
17 May 1986
Deficiency Check
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 987784
13 January 1986
Re-Inspection
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 992691
27 October 1985
Deficiency Check
Physical examination · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 994147
3 December 1984
Type not recorded
No type recorded · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1288496
Engineering
Issued 10 December 1996
Resolved
MAKE PERMANENT REPAIRS TO SALT WATER OVERBOARD DISCHARGE LINES LOCATED AT GENERATOR #2 AND #3 RISERS AND OVERBOARD PIPING.
Condition: Unknown
Due 10 December 1996
Resolved 10 December 1996
Fire Fighting
Issued 10 December 1996
Resolved
REPLACE FLEX LINES ON CO2 CONTROL SYSTEM FOR FIXED HALON SYSTEM IN ENGINE ROOM.
Condition: Unknown
Due 17 December 1996
Resolved 6 January 1997
Lifesaving
Issued 12 January 1995
Resolved
CONDUCT EMERGENCY DRILLS (FIRE, ABANDON SHIP, & MAN OVERBOARD) WHEN VESSEL IS CREWED AND PRIOR TO COMMENCING DRILLING OPERATIONS.
Condition: Unknown
Due 15 March 1995
Resolved 6 April 1995
Lifesaving
Issued 26 November 1990
Resolved
Provide/install one 25 person, davit launched liferaft. Until this item _x001C_ is completed, the total number of persons permitted aboard may not exceed 76.
Condition: Unknown
Due 26 November 1990
Resolved 26 November 1990
Unknown
Issued 4 January 1990
Resolved
SUBMIT TO COAST GUARD G-MSC FOR APPROVAL AN UPDATED OPERATIONS MANUAL IN ACCORDANCE WITH 46 CFR 109.121(C).
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Fire Fighting
Issued 4 January 1990
Resolved
SERVICE FIXED HALON EXTINGUISHING SYSTEM. PROVIDE COPY OF SERVICING REPORT TO [name withheld] , HI.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Lifesaving
Issued 4 January 1990
Resolved
PROVIDE 1 ADDITIONAL CURRENTLY SERVICED DAVIT LAUNCHED LIFERAFT. UNTIL LIFERAFT IS INSTALLED MAX PERSONS ALLOWED ON BOARD IS LIMITED TO 81.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Unknown
Issued 4 January 1990
Resolved
PROVIDE DRUG AND ALCOHOL TEST KITS IN ACCORDANCE WITH 46 CFR 4.06-20.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Lifesaving
Issued 4 January 1990
Resolved
FOR THE STBD LIFEBOAT: PROVIDE 1 ADDITIONAL (2 TOTAL) FIRE EXTINGUISHERS, PROVIDE A CG APPROVED 3-CELL FLASHLIGHT, PROVIDE 2 ROW OARS AND REPLACE 1 OTHER ROW OAR NOW TEMPORARILY REPAIIRED, PROVIDE 1 QUART ILLUMINATING OIL.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Construction/Loadline
Issued 4 January 1990
Resolved
CLEAN AN DRESS THE FOLLOWING DUMP VALVES: #3, 7, & 20. REPLACE GATE AND OVERHAUL OR RENEW DUMP VALVE #36 & 35.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Electrical
Issued 4 January 1990
Resolved
FOR THE GENERAL ALARM SYSTEM, INSTALL A SIREN IN THE MUD PIT ROOM AND A BELL ON THE DRILL FLOOR SUITABLE FOR HAZARDOUS LOCATIONS, UNTIL THIS ITEM IS CORRECTED, THE EXISTING SIREN ANND BELL SHOULD BE DE-ENERGIZED.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Electrical
Issued 4 January 1990
Resolved
PROPERLY SUPPORT AND STRAP HOSE ELECTRICAL CABLE IN THE FOLLOWING AREAS: MUD PIT ROOM, SHALE SHAKER AREA AND CELLAR DECK.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Fire Fighting
Issued 4 January 1990
Resolved
IAW RECOMMENDATION OF ROCKWOOD ANALYSIS RPT DATED 12/21/89, RESUBMIT A FOAM SAMPLE FOR ANALYSIS IN 6 MONTHS AND FORWARD RESULTS TO [name withheld],HI. SAMPLE TO BE DRAWN IN JUN 1990.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Construction/Loadline
Issued 4 January 1990
Resolved
PERMANENTLY REPAIR BY INSERT IN KIND. THE HOLED BOTTOM PLATE IN PRE LOAD TANK #36 IN WAY OF DUMP VALVE WHICH HAS BEEN REPAIRED TEMPORARILY BY DOUBLER.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Electrical
Issued 4 January 1990
Resolved
REPAIR/REPLACE AND PROVE OPERATION OF EMERGENCY GENERATOR LOW LUBE OIL TRIP. PROVIDE RESULTS OF TEST TO [name withheld], HI.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Electrical
Issued 4 January 1990
Resolved
PROVIDE AND ATTACH TO INSIDE OF DOOR, FOR EACH MOTOR CONTROLLER AND MOTOR CONTROLS CENTER, AN ELEMENTARY WIRING DIAGRAM.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Lifesaving
Issued 4 January 1990
Resolved
FOR THE STBD LIFEBOAT, PERMANENTLY REPAIR CRACK IN BENCH SEAT STBD SIDE AND HULL GEL COAT CRACKS STBD SIDE USING MFG APPROVED REPAIR KIT AND PROCEDURES.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Lifesaving
Issued 4 January 1990
Resolved
FOR THE PORT LIFEBOAT; PROVIDE ONE ADDITIONAL (2 TOTAL) METALLIC BUCKET, PROVIDE 1 ADDITIONAL (2 TOTAL) B-I FIRE EXTINGUISHERS, PROVIDE A CG APPROVED 3-CELL FLASHLIGHT, PROVIDE 2 ROW OARS, PROVIDE 1 QUART ILLUMINATING OIL.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Fire Fighting
Issued 4 January 1990
Resolved
REPLACE SPANNER WRENCHES ON FIRE STATION #3 & 4 WITH ONES THAT PROPERLY FIT HOSE CONNECTIONS AND PROVIDE BRACKETS FOR FOG APPLICATORS IN WAY OF FIRE STATIONS # 2 & 5.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Lifesaving
Issued 4 January 1990
Resolved
FOR THE PORT LIFEBOAT, HYDROSTATICALLY TEST THE THREE DOT AIR BOTTLES, TESTTO BE CONDUCTED AT A DOT APPROVED FACILITTY. REMOVE NO MORE THAN 1 AIR BOTTLE FROM THE LIFEBOAT AT ANY ONE TIME.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Lifesaving
Issued 4 January 1990
Resolved
RENEW 7 RING BUOYS AND REPAIR/REPLACE PORT RING BUOY WITH SMOKE SIGNAL RELEASE UNIT.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Lifesaving
Issued 4 January 1990
Resolved
PRROVIDE 9 ADDITIONAL (108 TOTAL) ADULT PFD'S PROPERLY MARKED AND EQUIPPED.UNTIL THIS ITEM IS CORRECTED THE TOTAL PERSONS ONBOARD IS LIMITED TO 79 PERSONS.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Fire Fighting
Issued 4 January 1990
Resolved
HYDROSTATICALLY TEST THREE CO2 PORTABLE FIRE EXTINGUISHERS NOW OVERDUE ((F/E#15, 18 & 21). TEST TO BE CONDUCTED AT AN APPROVED DOT FACILITY.
Condition: Unknown
Due 4 January 1990
Resolved 4 January 1990
Unknown
Issued 23 June 1989
Resolved
MAKE LIFERAFTS 3 AND 4 AVAILABLE FOR ANNUAL SERVICE AT COAST GUARD APPROVED SERVICING FACILITY
Condition: Unknown
Due 23 June 1989
Resolved 23 June 1989
Fire Fighting
Issued 5 December 1988
Resolved
RENEW THE FOLLOWING FIRE HYDRANT SHUTOFF VALVES: STATION NO. 15, HALLIBURTON ROOM, AND MUD PUMP ROOM.
Condition: Unknown
Due 5 December 1988
Resolved 5 December 1988
Fire Fighting
Issued 5 December 1988
Resolved
RENEW BOTH SEMI-PORTABLE FIRE EXTINGUISHERS ON THE HELO DECK.
Condition: Unknown
Due 5 December 1988
Resolved 5 December 1988
Lifesaving
Issued 5 December 1988
Resolved
RENEW ALL FLOATING ORANGE SMOKE AND HAND HELD FLARES IN BOTH THE PORT AND STARBOARD LIFEBOATS.
Condition: Unknown
Due 5 December 1988
Resolved 5 December 1988
Lifesaving
Issued 5 December 1988
Resolved
INSTALL TWO (2) ADDITIONAL DAVIT LAUNCHED LIFERAFTS, TO MAKE A TOTAL OF FOUR (4).
Condition: Unknown
Due 5 December 1988
Resolved 5 December 1988
Electrical
Issued 5 December 1988
Resolved
INSTALL A STARTER MOTOR ON THE NUMBER THREE (3) MAIN ENGINE.
Condition: Unknown
Due 5 December 1988
Resolved 5 December 1988
Electrical
Issued 5 December 1988
Resolved
REPAIR AND TEST THE AIR CONDITIONING AND VENTILATION REMOTE TRIPS FOR THE ACCOMMODATION SPACES.
Condition: Unknown
Due 5 December 1988
Resolved 5 December 1988
Documentation
Issued 5 December 1988
Resolved
PROVIDE A HAZARDOUS AREA PLAN AS PART OF THE OPERATIONS MANUAL, REQUIRED BY 46 CFR 109.121.
Condition: Unknown
Due 5 December 1988
Resolved 5 December 1988
Fire Fighting
Issued 5 December 1988
Resolved
RENEW THE DAMAGED FLEIBLE HOSE (FLEX LOOP) LEADING FROM THE FIXED CO2 TO THE HALON ACTUATION MANIFOLD.
Condition: Unknown
Due 5 December 1988
Resolved 5 December 1988
Lifesaving
Issued 25 November 1987
Resolved
LINE THROWING APPARATUS WAS LEFT OUT TO THE ELEMENTS. AS A RESULT THE FOLLOWING ARE TO BE RENEWED: FOUR (4) LINES, TWO (2) FLOATING ROCKETS, TWO (2) NON-FLOATING ROCKETS, AND FOUR (4) IGNITION CARTRIDGES.
Condition: Unknown
Due 25 November 1987
Resolved 25 November 1987
Fire Fighting
Issued 25 November 1987
Resolved
HYDROSTATICALLY TEST THE CO2 BOTTLES ON THE B-V EXTINGUISHER LOCATED ON THEFLIGHT DECK.
Condition: Unknown
Due 25 November 1987
Resolved 25 November 1987
Unknown
Issued 3 December 1986
Resolved
REPLACE FORWARD LIMIT SWITCH FOR #2 MOTOR LIFEBOAT DAVIT. WRITTEN CERTIFICATION OF COMPLIANCE FROM THE PERSON-IN-CHARGE WILL BE ACCEPTABLE.
Condition: Unknown
Due 3 December 1986
Resolved 3 December 1986
Unknown
Issued 3 December 1986
Resolved
REPLACE PORTABLE CORD AND CIRCUIT RELAY CONTROLLER FROM DIESEL AUTOMATIC SHUTDOWN FOR HALON SYSTEM WITH NEC EQUIVALENT CABLE AND U.L. APPROVED CONTROL BOX. WRITTEN CERTIFICATION OF COMPLIANCE FROM PERSON-IN-CHARGE WILL BE ACCEPTABLE.
Condition: Unknown
Due 3 December 1986
Resolved 3 December 1986
Unknown
Issued 13 January 1986
Resolved
PROVIDE USCG APPROVED, IN-DATE, DISTRESS PARACHUTE FLARES.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
BOTH PORT AND STARBOARD LIFE RING BUOY'S SMOKE SIGNALS SHALL BE REFITTED SOWHEN RELEASED THEY WILL DROP INTO THE WATER.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
THE PERSON IN CHARGE SHALL ENSURE THAT FIRE DRILLS ARE HELD WEEKLY AND LOGGED IN THE VESSELS LOG BOOK.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
INSTALL A LADDER FOR ACCESS TO THE VENT CLOSURE BETWEEN THE FIRE PUMP COMPARTMENT AND THE AUXILIARY PUMP COMPARTMENT.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
LIFEBOAT 2 SHALL BE PROVIDED THE FOLLOWING: BOAT COMPASS, JACK KNIFE, ILLUMINATING OIL, 8 LBS OF PROVISIONS, LIFESAVING SIGNALS, NO. 1 OXYGEN BOTTLE RECHARGED, DIESEL FUEL CHANGED AND BOW & STERN SAFETY WIRE TO DAVIT SHALL BE FITTED WITH A DEVICE WHICH CAN BE RELEASED UNDER TENSION.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
LINE THROWING DEVICE SHALL BE PROVIDED WITH INSTRUCTIONS AND ROCKETS SHALL BE IN DATE (LESS THAN 04 YEARS OLD).
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
PURGED AIR SYSTEM DRILL FLOOR ELECTRICAL METER & INDICATING PANEL SHALL BE FITTED WITH A DEVICE SHOWING UNIT UNDER PURGE OR PURGE FAILURE.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
MUD PIT DOORS SHALL BE SELF-CLOSING AND GAS TIGHT.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
REPAIR THE MUD PIT EXHAUST VENTILATION BLOWER AND THE LOSS OF VENTILATION ALARM LOCATED ON THE DRILL FLOOR.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
SHALE SHAKER GAS SAMPLER AND SIGNAL HORN SHALL BE EXPLOSIVE PROOF OR REMOVED FROM THE HAZARDOUS AREA.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
PROVIDE AN AUTOMATICALLY CLOSING VALVE FOR THE GAGE GLASS ON THE DIESEL FUEL OIL DAY TANK.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
FUEL OIL PURIFIER SHALL BE FITTED WITH AN EMERGENCY STOP REMOTELY CON- TROLLED FROM OUTSIDE THE SPACE.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
PROVIDE THE U.S. COAST GUARD A COPY OF THE FOAM ANALYSIS REPORT.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Unknown
Issued 13 January 1986
Resolved
LIFE BOAT 1 SHALL BE PROVIDED THE FOLLOWING: BOAT COMPASS, JACK KNIFE, ILLUMINATING OIL, 4 LBS OF PROVISIONS, NO. 1 OXYGEN BOTTLE RECHARGED, DIESEL FUEL CHANGED AND BOW & STERN SAFETY WIRE TO DAVIT SHALL BE FITTED WITH A DEVICE WHICH CAN BE RELEASED UNDER TENSION.
Condition: Unknown
Due 13 January 1986
Resolved 13 January 1986
Construction/Loadline
Issued 27 October 1985
Resolved
CROP AND RENEW LOWER SECTION OF THE WATER MAKER OVERBOARD DISCHARGE LINE FROM THE WELDED JOINT 1 FOOT ABOVE THE TANK TOP TO THE HULL PLATING.
Condition: Unknown
Due 27 October 1985
Resolved 27 October 1985
Construction/Loadline
Issued 27 October 1985
Resolved
PROVIDE A POSITIVE CLOSING VALVE IN THE WATER MAKER OVERBOARD DISCHARGE LINE AT THE TANK TOP ELEVATION IN THE ENGINE ROOM.
Condition: Unknown
Due 27 October 1985
Resolved 27 October 1985
Deck/Cargo
Issued 3 December 1984
Resolved
PROVIDE DOCUMENTATION SHOWING THAT THE FORKLIFT ON BOARD IS UL OR FM ACCEPTED AS PER 46 CFR 108.613 OR REMOVE SAME FROM RIG.
Condition: Unknown
Due 3 December 1984
Resolved 3 December 1984
Unknown
Issued 3 December 1984
Resolved
PROVIDE THREE RELIEF VALVES WITH LIFTING DEVICES FOR THREE AIR RECEIVERS AS PER 46 CFR 54.15-10(C).
Condition: Unknown
Due 3 December 1984
Resolved 3 December 1984
Unknown
Issued 3 December 1984
Resolved
PROVIDE NAME PLATE DATA ON AIR RECEIVERS LOCATED ON RIG FLOOR AND IN THE ENGINE ROOM.
Condition: Unknown
Due 3 December 1984
Resolved 3 December 1984
Unknown
Issued 3 December 1984
Resolved
PROVIDE TWO STANDARD DISCHARGE CONNECTION PIECES FOR THE DISCHARGE OF RESI-DUES FROM MACHINERY BILGES TO RECEPTION FACILITIES AS PER MARPOL 73/78 REGULATION 19.
Condition: Unknown
Due 3 December 1984
Resolved 3 December 1984
Lifesaving
Issued 3 December 1984
Resolved
PROPERLY SERVICE ONE DAVIT LAUNCHED INFLATABLE LIFERAFT.
Condition: Unknown
Due 3 December 1984
Resolved 3 December 1984
Lifesaving
Issued 3 December 1984
Resolved
PROVIDE ON BOARD ONE MISSING DAVIT LAUNCHED INFLATABLE LIFERAFT.
Condition: Unknown
Due 3 December 1984
Resolved 3 December 1984
Electrical
Issued 3 December 1984
Resolved
PROVIDE ONE GENERAL ALARM BELL FOR CLASS I DIVISION TWO HAZARD AREA IN THE MUD PIT ROOM.
Condition: Unknown
Due 3 December 1984
Resolved 3 December 1984
Lifesaving
Issued 3 December 1984
Resolved
PROPERLY HYDROSTATICALLY TEST A TOTAL OF SIX AIR RECEIVERS IN BOTH MOTOR LIFEBOATS.
Condition: Unknown
Due 3 December 1984
Resolved 3 December 1984