Records from 2016 to 2026. Most recent: inspection, 13 March 2026.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 1 April 2024
Resolved
Fire extinguishing equipment installed on a vessel in excess of the requirements of §§ 181.400 and 181.500 must be designed, constructed, installed, and maintained in accordance with a recognized industry standard acceptable to the Commandant (CG-ENG-4).Vessel does not have annual fire detection service certificate.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: Operator attained documentation showing annual servicing was completed.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 1 April 2024
Resolved
For vessels other than those covered in paragraphs (b) and (c) of this section, the name of the vessel must be marked on some clearly visible exterior part of the port and starboard bow and the stern of the vessel. The hailing port of the vessel must be marked on some clearly visible exterior part of the stern of the vessel. Paint name on stern to be contrasting in color.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: vls name painted on the vessel stern in contrasting color
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 1 April 2024
Resolved
Each ring life buoy on a vessel must: Be approved in accordance with § 160.050 in subchapter Q of this chapter, or other standard specified by the Commandant, including, but not limited to, approval series 160.150. Each ring life buoy needs CG approval sticker. Also renew Worn reflective tape.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: Life rings installed with new retro reflective tape.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 1 April 2024
Resolved
A hatch cover must: Have securing devices; Escape hatch
on bow missing a dog and had a loose dog.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: New securing dog installed on the bow's emergency escape hatch.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 1 April 2024
Resolved
Each life float must be fitted with a lifeline, pendants, two paddles, a painter, and a light. Life float paddles not secured, retro-reflective tape worn, light missing battery and closure device.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: Life floats have been maintained and arranged to conform with regulations.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 1 April 2024
Resolved
Each vessel must have adequate emergency lighting fitted along the line of escape to the main deck from all passenger and crew accommodation spaces located below the main deck. Provide adequate lighting for aft engine room escape access.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: emergecy lighting has been added and found sat.
09 - Working and Living Conditions › 092 - Working Conditions › Obstruction/slipping, etc.
Issued 1 April 2024
Resolved
At each initial and subsequent inspection for certification and re inspection the marine inspector shall examine the passenger and crew quarters, toilet and washing spaces, galleys, serving pantries, lockers, etc., to determine that they are serviceable and in a sanitary condition. Secure stove in the galley to prevent movement during rough seas or emergencies.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: Stove was secured to prevent moving while underway.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 1 April 2024
Resolved
Where rigid nonmetallic material is permitted for use in piping systems by this subpart, the following restrictions shall be adhered to: Protection from mechanical damage shall be specially considered. Protective covering or shields shall be installed to the
satisfaction of the Officer in Charge, Marine
Inspection. Replace chaffed oil line to the #1 MDE reduction gear unit.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: Chaffed Oil line to the #1 MDE reduction gear unit was changed new.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 1 April 2024
Resolved
Remove paper towel used to bypass fire alarm located in the galley overhead.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: MI verified the paper towel used to bypass the galley heat/smoke alarm was removed. Alarm was tested sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 1 April 2024
Resolved
If your vessel's Certificate of Inspection is renewed annually, the marine inspector must check the settings of the safety or relief valves on all pressure vessels, except cargo tanks, at each inspection for certification. Relief valve did not reset on its own.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: replaced both SRV on the UPVs
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 1 April 2024
Resolved
Propulsion machinery shall be
suitable in type and design for propulsion requirements of the hull in which it is installed and capable of operating at constant marine load under such requirements without exceeding its designed limitations. Repair fuel control arm tensioner on #3 Main Diesel Engine.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: Repaired #3 MDE's throttle body tensioner.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 1 April 2024
Resolved
Battery terminals shall be of the soldered type and all connections shall be made to the battery terminals with permanent type connectors. Spring clips or other temporary type clamps are not permitted. Properly secure battery charger leads to battery terminals.
Action required: 705 - Other - as specified
Due 5 April 2024
Resolved 3 April 2024
Resolution: Battery cable terminals have been replaced new.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 4 April 2023
Resolved
Vessels described by 46 CFR 175.110(c) must have an interconnected fire detection system in compliance with § 181.450 installed in all enclosed areas where passengers and crew have routine access, including accommodation spaces and machinery spaces. Vessel did not have smoke detection in all accommodation spaces. Ensure smoke detectors are provided in all accommodation spaces and proved technician service report to satisfaction of attending marine inspector.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 6 April 2023
Resolution: Received, reviewed, and accepted technician service report for fire alarm panel. Deficiency cleared.
11 - Life Saving Appliances › N/A - No Subsystem › Launching arrangements for survival craft
Issued 4 April 2023
Resolved
Each life float and buoyant apparatus must be individually attached to the painter by a line meeting § 180.175(f)(3) (ii), (iii), and (iv) and long enough that each life float or buoyant apparatus can float without contacting any other life float or buoyant apparatus in the group. Life float arrangement had tangled lines and may not properly float free. Ensure life floats and lines are properly installed/arranged per NVIC 01-83.
Action required: 10 - Deficiency Rectified
Due 4 April 2023
Resolved 4 April 2023
Resolution: Vessel organized and ensured life floats would float free.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 4 April 2023
Resolved
All observed unsafe practices and hazardous situations shall be corrected. Washer and dryer are not secured. Properly secure washer and dryer to satisfaction of attending marine inspector.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 18 April 2023
Resolved 4 April 2023
Resolution: Received, reviewed, and accepted photographs clearing deficiency.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 4 April 2023
Resolved
Each Class 1 door of a vessel on ocean service must be designed to withstand a head of water equivalent to 10 feet. Fastening devices on the forward escape door in the passenger area need to be adjusted to proved a tighter closure.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 18 April 2023
Resolved 5 April 2023
Resolution: Received, reviewed, and accepted photographs clearing deficiency.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 4 April 2023
Resolved
Vessels shall be equipped with a suitable number of portable battery lights. Install an additional emergency light in the engine room entrance.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 18 April 2023
Resolved 6 April 2023
Resolution: Received, reviewed, and accepted photos of e-lighting installation.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 4 April 2023
Resolved
Protective gratings shall be provided at such locations where persons or gear might come into contact with the exhaust pipe. Exhaust pipe was exposed, install protection on exhaust pipe.
Action required: 10 - Deficiency Rectified
Due 4 April 2023
Resolved 4 April 2023
Resolution: Vessel installed lagging on all main engine exhausts.
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 4 April 2023
Resolved
All observed unsafe practices and hazardous situations shall be corrected. Hot water heater safety relief valve not operational due to corrosion and needs replacement.
Action required: 10 - Deficiency Rectified
Due 4 April 2023
Resolved 4 April 2023
Resolution: Vessel replaced safety relief valve.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 19 May 2022
Resolved
46CFR183.200(b): Electrical equipment on a vessel must be installed and maintained to: Protect passengers, crew, other persons and the vessel from electrical hazards, including fire, caused by or originating in electrical equipment, and electrical shock. Vessels Port and Stbd Generator windings were dirty.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 8 June 2022
Resolution: P/S generator's windings have been cleaned of excessive oil and dirt.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 19 May 2022
Resolved
46CFR320(e): Each motor must have a nameplate attached to it containing the information required by Article 430 of NFPA 70, and for a motor derated in accordance with paragraph (b) (2) of this section, the derated capacity. Vessel Missing date plate on Stbd generator.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 8 June 2022
Resolution: Data plate has been attached to the Stbd generator.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 19 May 2022
Resolved
Electrical equipment and installations must be suitable for the roll, pitch and vibration of the vessel underway. Vessel Port and Stbd generator pedestal bolts were loose.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 8 June 2022
Resolution: Verified all mount bolts tightened on generators.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 19 May 2022
Resolved
46 CFR 183.200 (b): Electrical equipment on a vessel must be installed and maintained to: Protect passengers, crew, other persons, and the vessel from electrical hazards, including fire, caused by or originating in electrical equipment, and electrical shock. Vessel port generator air intakes were saturated with oil and spry paint.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 8 June 2022
Resolution: Intakes cleaned of oil and spray paint.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 19 May 2022
Resolved
Each distribution panel or switchboards must be totally enclosed and of the dead front type. Vessel Switchboard had openings on the side and loose cover.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 8 June 2022
Resolution: Opening on main switch board have covers installed to prevent shock hazard.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 19 May 2022
Resolved
Each propulsion, power, lighting, or distribution system having a neutral bus or conductor must have the neutral grounded. Vessel Ground detection system test function was inoperable.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 8 June 2022
Resolution: Ground detecton amp meter test button was tested and proven operational. Tech report provided.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 19 May 2022
Resolved
A voltmeter and an ammeter, which can be used for measuring voltage and current of a generator that is in operation.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 8 June 2022
Resolution: New ammeter and voltage meter installed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Propulsion main engine
Issued 19 May 2022
Resolved
Two clamps must be used on each end of the hose, or hose clamp can be used if the pipe ends are expanded or beaded to provide a positive stop against hose slippage. Vessel missing a number of hose clamp on all MDE's reduction gear.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 8 June 2022
Resolution: MI verified clamps installed on MDE reduction gear unit's pneumatic hoses.
04 - Emergency Systems › N/A - No Subsystem › Public address system
Issued 19 May 2022
Resolved
Except as noted in paragraphs (d) and (e) below, each vessel must be equipped with a public address system. Vessel Public address was inoperable.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 8 June 2022
Resolution: PA system tested sat in all living spaces aboard.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 19 May 2022
Resolved
Each Battery must be located as high above the bilge as practicable, secured to protect against shifting with the roll and pitch of the vessel. Vessel battery had loose connections and exposed wires.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 8 June 2022
Resolution: Battery loose connections have been secured and made tight.
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 19 May 2022
Resolved
The Shutoff valve at the tank must be manually operable from outside the compartment in which the valve is located , preferably from an accessible position on the weather deck. Vessel fuel tank return valve handle loose and fuel shut off is bound and leaking.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 23 June 2022
Resolution: Received email with attached pictures attesting to proper connection of fuel shut off valve.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 5 June 2019
Resolved
No repairs or alterations affecting the safety of the vessel or its machinery shall be made unless applicable requirements in this chapter are met. The procedures to be followed in notifying the Coast Guard about vessel repairs vary according to the type of vessel and service in which engaged.
Vessel sustained a fire with an associated fuel spill on the afternoon of 04JUN2019. Vessel has extensive damage from smoke and fire primarily in the galley and above the galley in the crew space. Prior to movement, company must provide to the OCMI a satisfactory marine damage survey and a satisfactory transit plan (to repair facility) to be approved by the USCG Marine Inspector.
If vessel is to transit to repair facility under own power, prove satisfactory sea trials conducted to [name withheld] not, vessel will use assist vessel(s) to transit to repair facility. After vessel arrives at repair facility, the company must provide a repair plan to be approved by the OCMI prior to start of repairs.
Condition: Damaged By Earlier Event
Action required: 60 - Rectify deficiencies prior to movement
Due 5 July 2019
Resolved 9 September 2019
Resolution: Completed repairs on all affected systems and structure, followed by satisfactory deficiency check.
Fire Fighting › Fire Hoses › Condition
Issued 2 February 2017
Resolved
Stbd fire hose failed pressure test.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 2 February 2017
Resolved 2 February 2017
Resolution: Hose replaced
Lifesaving › Lifefloat › Painter
Issued 2 February 2017
Resolved
Lifefloat painter lines were incorrectly tied to lifefloats.
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Due 2 February 2017
Resolved 2 February 2017
Resolution: Painter line installed correctly.
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 2 February 2017
Resolved
Renew stenciling on starboard lifebuoy
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 2 February 2017
Resolved 2 February 2017
Resolution: Stenciling renewed.
Stability › Watertight Integrity › General
Issued 2 February 2017
Resolved
Soft patch IVO starboard cargo deck to facilitate main engine removal was missing fasteners allowing water intrusion.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 9 February 2017
Resolved 2 February 2017
Resolution: Fasteners installed.
Fire Fighting › Remote Fuel Shutoff › General
Issued 2 February 2017
Resolved
Starboard remote fuel cut off valve was inoperable.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 2 February 2017
Resolved 2 February 2017
Resolution: Valve reach rod was repaired during exam.
Fire Fighting › Nozzles › Type
Issued 2 February 2017
Resolved
Additional fire fighting equipment required for carriage of flammable/combustible did not have an approved nozzle.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Due 6 February 2017
Resolved 6 February 2017
Resolution: Approved nozzle placed onboard.
Lifesaving › Buoyant Apparatus › Float-free Link
Issued 10 May 2016
Resolved
Improper grouping of lifefloats & attachment to incorrectly sized weak links.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 3 June 2016
Resolved 3 June 2016
Resolution: ALL 3 lifefloats have been grouped & attached to single weak link of proper breaking strength.
Item was corrected onboard to satisfaction of the Marine Inspector.
Lifesaving › Buoyant Apparatus › Float Free
Issued 10 May 2016
Resolved
Mast halyard secured to aft rail directly crossing over life float installations causing potential obstruction to float free arangement.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 3 June 2016
Resolved 3 June 2016
Resolution: Halyard moved and now secured to outboard railings. Life float floatation path no longer obstructed. Cleared onboard.