Records from 1984 to 1998. Most recent: inspection, 22 June 1998.
Fire Fighting
Issued 19 May 1997
Resolved
provide referenced drawings for emergency generator room fixed CO2 system as outlined in Det Norske Veritas type approval certificate F-9860.
Condition: Unknown
Due 19 July 1997
Resolved 3 July 1997
Unknown
Issued 18 October 1996
Resolved
Prove proper operation of all preload tank remote operated valve indicators.
Condition: Unknown
Due 18 October 1996
Resolved 18 October 1996
Unknown
Issued 18 October 1996
Resolved
Replace all 8 preload tank dump valves.
Condition: Unknown
Due 18 October 1996
Resolved 18 October 1996
Unknown
Issued 18 October 1996
Resolved
Provide proper type of international shore connection.
Condition: Unknown
Due 18 October 1996
Resolved 18 October 1996
Unknown
Issued 18 October 1996
Resolved
Demonstrate proper operation of the H2S calibration meter.
Condition: Unknown
Due 18 October 1996
Resolved 18 October 1996
Unknown
Issued 18 October 1996
Resolved
Hydrostatic test the starboard galley fire suppression system cyclinder.
Condition: Unknown
Due 18 October 1996
Resolved 18 October 1996
Lifesaving
Issued 22 March 1996
Resolved
PROVIDE AN APPROVED FISHING KIT, BOTH LIFE BOATS.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
REPAIR / REPLACE THE HOLED METAL STORM OIL CONTAINER, STARBOARD LIFEBOAT.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
REPAIR / REPLACE ALL 12 PRELOAD TANK DUMP VALVES.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
HYDROSTATICALLY TEST THE EMERGENCY EQUIPMENT AIR CYLINDERS AS NEEDED.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
PROPERLY CALIBRATE AND PROVE PROPER OPERATION OF EACH PORTABLE O2/LEL INDICATOR.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
REINSTALL BOW DECK DRAIN PIPE.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
PROVE PROPER HYDROSTATIC TEST OF BOTH 100 LBS CO2 CYLINDERS PROTECTING THE EMERGENCY GENERATOR ROOM. ALL FIXED FIRE FIGHTING SYSTEM CYLINDERS ON BOARD THE VESSEL MUST BE HYDROSTATICALLY TESTED AT AN APPROVED U.S. DOT FACILITY.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Navigation
Issued 22 March 1996
Resolved
PROVE PROPER OPERATION OF THE STARBOARD OBSTRUCTION LIGHT.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
PROVIDE CORRECT SIZE BOAT HOOK FOR STARBOARD LIFE BOAT.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
INSTALL SCREEN ON SUPPLY VENT DUCT IN THE MUD PUMP ROOM.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Electrical
Issued 22 March 1996
Resolved
PLACE PERMANENT DRIP SHIELD OVER ELECTRICAL TRANSFORMER.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
INSTALL MISSING LIGHT COVER, STARBOARD LIFEBOAT.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
CONDUCT HYDROSTATIC TEST OF THE STARBOARD LIFEBOAT COMPRESSED AIR CYLINDER.FACILITY AND CYLINDER MUST BE U.S. DOT APPROVED.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
PROVIDE A SECOND BOAT HOOK OF 10 FEET IN LENGTH AND AT LEAST 1.75 INCHES DIAMETER FOR THE PORT LIFE BOAT.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
PROVE PROPER HYDROSTATIC TEST OF ALL B-V SEMI PORTABLE FIRE EXTINGUISHERS BY AN APPROVED U.S. DOT SERVICING FACILITY. ALL CYLINDERS MUST BE U.S. DOT STAMPED.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Electrical
Issued 22 March 1996
Resolved
REPAIR BROKEN CABLE WAY LOCATED IN THE OVERHEAD BEHIND THE PAINT LOCKER.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
CONDUCT HYDROSTATIC TEST OF THE APPROVED O2 CYLINDER LOCATED IN THE HOSPITAL. SERVICING FACILITY MUST BE U.S. DOT APPROVED.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
PROVIDE CG APPROVED RING BUOYS AND WATERLIGHTS FOR THE STATIONS BELOW THE DRILL FLOOR.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
REMOVE ALL PAINT AND GREASE OBSTRUCTING THE PROPER OPERATION OF EXPLOSION PROOF FIXTURES.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
REPLACE THE DAMAGED 2 1/2" RIG FLOOR FIRE STATION HOSE AT STATION #22.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Accommodation/Occupational Safety
Issued 22 March 1996
Resolved
PROVE PROPER OPERATION OF ALL FIRE DAMPERS, SECOND DECK ACCOMODATIONS.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
REPLACE THE 1 1/2" HOSE AT FIRE STATION #6.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
REMOVE FROM VESSEL THE 3 NON U.S. DOT O2 CYLINDERS LOCATED IN THE HOSPITAL.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
CROP AND RENEW WASTED BULKHEAD BELOW PLATFORM "I" BEAM BETWEEN MUD PITS NOS. 1 & 2.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
CROP AND RENEW WASTED DIESEL OIL TANK TOPS (MUD PIT BOTTOMS).
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
PROVE PROPER OPERATION OF THE AUTOMATIC FOAM WATER SUPPLY VALVE CONTROL LOCATED AT THE HELIDECK.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
REPLACE BOTH 2 1/2" WASTED FOAM HOSE DIFFUSERS.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
PROVIDE CURRENT FOAM ANALYSIS REPORT.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
REPAIR / REPLACE THE BILGE OVERBOARD AND THE MAIN SEA SUCTION VALVES.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
REPAIR OR REPLACE THE 3" GALLEY AND GARBAGE OVERBOARD DISCHARGE VALVES.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
PROVE PROPER OPERATION OF BOTH 600 GPM ENGINEROOM BILGE PUMPS. PUMP IMPELLERS ARE WASTED.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
PROVIDE 8 ADDITIONAL COAST GUARD APPROVED NON EXPIRED PARACHUTE FLARES AS REQUIRED.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
REPLACE THE WASTED, DEEP WELL PUMP SEA SUCTION VALVES NOS. 1 & 3, AND THE FIRE MAIN SUCTION VALVE.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
REPLACE LEAKING PIPE FROM ROOM BELOW TRANSFORMER ROOM UP THROUGH DECK AND INTO TRANSFORMER ROOM.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Documentation
Issued 22 March 1996
Resolved
PROVIDE ABS AND COAST GUARD APPROVAL LETTERS OF PRELOAD TANK DRAIN PLUGS.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
REPAIR OR REPLACE AND PROVE PROPER OPERATION OF THE DISTORTED LARGE WATERTIGHT DOOR BETWEEN THE SACK STORAGE ROOM AND THE GEL/BARITE TANK ROOM.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Electrical
Issued 22 March 1996
Resolved
REPLACE THE BROKEN EXHAUST FAN ELECTRICAL SWITCH LOCATED IN THE CHANGE ROOM.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Electrical
Issued 22 March 1996
Resolved
SECURE THE STORE ROOM LIGHT AND PLACE PROTECTIVE CAGE OVER THE LIGHT IN THESTOREROOM, ON THE FIRST DECK NEXT TO THE STAIRWELL.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
REPLACE THE BROKEN PORT AFT RING BUOY.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
CROP AND RENEW THE HOLED / WASTED DECK ON THE STAND PIPE.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
SERVICE THE B-V SEMI PORTABLE FIRE EXTINGUISHER LOCATED IN THE OUTER WORKSHOP AREA.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Accommodation/Occupational Safety
Issued 22 March 1996
Resolved
CROP AND RENEW WASTED LADDER IN THE 2P PRELOAD TANK.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Engineering
Issued 22 March 1996
Resolved
PROVE PROPER OPERATION OF THE NO. 3 MDG RPM GAUGE.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
PROVE PROPER OPERATION OF ALL PRELOAD TANK REMOTE OPERATED VALVE INDICATORS.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
REPLACE THE WASTED MAIN DIESEL GENERATOR SEA WATER OVERBOARD DISCHARGE VALVE AND SPOOL PIECE.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
PROVE PROPER OPERATION OF THE DEEP WELL PUMP SEA SUCTION STRAINER GUILLOTINE VALVES, AND REPAIR/REPLACE WASTED STRAINER BASKETS.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
PROPERLY INSTALL A CO2 ACTIVATED SHUT DOWN ON THE EMERGENCY GENERATOR PRIMEMOVER.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Accommodation/Occupational Safety
Issued 22 March 1996
Resolved
CROP AND RENEW WASTED HANDRAILS AND STANCHIONS AROUND THE STARBOARD LEG.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Accommodation/Occupational Safety
Issued 22 March 1996
Resolved
REWELD THE WATER TOWER'S BROKEN LADDER (2 PLACES).
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Deck/Cargo
Issued 22 March 1996
Resolved
MAKE PERMANENT REPAIRS TO THE DRILL FLOOR AIR RECEIVER. REPAIRS MUST BE IN ACCORDANCE WITH APPROVED PROCEDURES. HYDRO TEST TO 1.5 X MAXIMUM ALLOWABLE WORKING PRESSURE.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
PROVE PROPER OPERATION OF THE MUD FLOW LOSS OF PRESSURIZED AIR INDICATOR ONTHE DRILL FLOOR.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Electrical
Issued 22 March 1996
Resolved
REMOVE ALL DEAD END ELECTRICAL WIRING AND REMOVE WIRE RUNS AROUND ALL HANDRAILS. WIRE RUNS MUST BE PROPERLY SUPPORTED BY CABLE WAYS AND METAL TIES.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Construction/Loadline
Issued 22 March 1996
Resolved
REPAIR OR REPLACE THE FORWARD 4" SANITARY BYPASS OVERBOARD DISCHARGE VALVE.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
PROVE PROPER OPERATION OF THE PRESSURIZED DRILLERS CONSOLE LOSS OF PRESSUREALARM.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Unknown
Issued 22 March 1996
Resolved
PROVIDE A COPY OF THE CURRENT CERTIFICATE OF FINANCIAL RESPONSIBLITY (COFR).
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
PROVIDE AND POST OPERATING INSTRUCTIONS FOR BOTH GALLEY FIRE SUPRESSION SYSTEMS.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Electrical
Issued 22 March 1996
Resolved
PROVE BARE WIRE IS DEAD OR PROPERLY DEAD END IT IN THE EMERGENCY GENERATOR ROOM, ON A CABLE WAY, LEFT OF THE TELEPHONE.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
PROVIDE CORRECT TYPE OF INTERNATIONAL SHORE CONNECTION WITH HARDWARE.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Accommodation/Occupational Safety
Issued 22 March 1996
Resolved
CROP AND RENEW WASTED DECK GRATING SUPPORTS ON THE WATER TOWER.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Unknown
Issued 22 March 1996
Resolved
PROVIDE DIVER'S UNDERWATER HULL EXAM VIDEO, STILL PHOTOGRAPHS AND REPORT.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Electrical
Issued 22 March 1996
Resolved
REPLACE PLASTIC WIRE TIES WITH METAL ON ALL ELECTRICAL WIRING RUNS LOCATED AT THE TOP AFT DRILL FLOOR BULKHEAD.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
SERVICE, CLEAN AND PROVE PROPER OPERATION OF ALL DRILL FLOOR EMERGENCY EQUIPMENT AIR BREATHING APPARATUS.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Electrical
Issued 22 March 1996
Resolved
PROVIDE MANUFACTURERS INFORMATION THAT PROVES THE DRILL FLOOR EXPLOSION PROOF BOXES ARE PROPERLY STUFFED WITH CLASS I DIVISION I ELECTRICAL FITTINGS. BRASS COLORED FITTINGS ONLY.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Accommodation/Occupational Safety
Issued 22 March 1996
Resolved
LOCATE SOURCE OF VESSEL'S POTABLE WATER DISCOLORATION AND REPAIR.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
PROPERLY CALIBRATE THE H2S CALIBRATION METER.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
RELABEL THE HALON SCR ELECTRICAL CUTOUT SWITCHES TO INCLUDE RIG SHUT DOWN.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 22 March 1996
Resolved
REPAIR THE LOCAL ELECTRICAL EXHAUST FAN SWITCH TO THE MUD PIT ROOM.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
PROVIDE UPDATED FIRE DETECTION SYSTEM LINE DRAWING.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
HYDROSTATICALLY TEST THE STARBOARD GALLEY FIRE SUPPRESION SYSTEM CYLINDER.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
INSTALL PRESSURE GAUGE ON THE NO. 1 HALON CYLINDER.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Fire Fighting
Issued 22 March 1996
Resolved
INSTALL DATA PLATES ON ALL 5 HALON CYLINDERS. MUST INCLUDE TARE WEIGHT, CHARGE WEIGHT AND MANUFACTURER IDENTIFICATION.
Condition: Unknown
Due 22 March 1996
Resolved 22 March 1996
Lifesaving
Issued 25 September 1995
Resolved
Hydrostatically test the air supply cylinders for the #1 and #2 lifeboats at a U.S. DOT approved facility._x001C_
Condition: Unknown
Due 25 September 1995
Resolved 25 September 1995
Electrical
Issued 19 February 1995
Resolved
Make permanent repair to non-operational emergency light in sack room and prove proper operation.
Condition: Unknown
Due 19 February 1995
Resolved 19 February 1995
Lifesaving
Issued 19 February 1995
Resolved
Number 3 motor lifeboat Rottmer release gear hook locks not in proper alignment. Hook pin is making partial contact with hook lock. Lifeboat #3is not to be boarded by personnel except when waterborne, until Rottmer release is renewed/repaired by a competent factory authorized representatit
Condition: Unknown
Due 3 May 1995
Resolved 3 May 1995
Fire Fighting
Issued 19 February 1995
Resolved
Repair or renew broken/damage portable fire extinguishers brackets located at stations 10 and 18.
Condition: Unknown
Due 19 February 1995
Resolved 19 February 1995
Lifesaving
Issued 19 February 1995
Resolved
Bring two quick release ring buoys into compliance with 46CFR108.515(d) by providing release mechanism that can be operated from the bridge or other central location.
Condition: Unknown
Due 4 May 1995
Resolved 4 May 1995
Lifesaving
Issued 19 February 1995
Resolved
Provide five year hydrostatic test for lifeboat air supply cylinders.
Condition: Unknown
Due 15 May 1995
Resolved 11 May 1995
Fire Fighting
Issued 19 February 1995
Resolved
Provide annual servicing of semi-portable and fixed fire extinguishing systems in accordance with 46CFR107.235(a),(b).
Condition: Unknown
Due 4 May 1995
Resolved 4 May 1995
Fire Fighting
Issued 19 February 1995
Resolved
Numerous fire screen doors missing latches, including doors in stair tower and machinery spaces. Repair or renew all fire screen door latches & door knobs.
Condition: Unknown
Due 11 May 1995
Resolved 11 May 1995
Fire Fighting
Issued 19 February 1995
Resolved
Trouble shoot and make permanent repair to all fire dampers in disrepair including correcting fire damper handle obstructing national mess interior door.
Condition: Unknown
Due 4 May 1995
Resolved 4 May 1995
Fire Fighting
Issued 19 February 1995
Resolved
Trouble shoot and make permanent repair and restore H2S detector to operation.
Condition: Unknown
Due 4 May 1995
Resolved 4 May 1995
Fire Fighting
Issued 19 February 1995
Resolved
Provide complete but simple operating instructions located in a conspicuousplace at or near all pull boxes, stop valve controls and in the CO2 storageroom for fixed HALON/CO2 systems. Instruct must incl alternate operating means of operating fixed fire systems iaw 46CFR76.15-10 and NVIC6-72.
Condition: Unknown
Due 4 May 1995
Resolved 4 May 1995
Lifesaving
Issued 19 February 1995
Resolved
Renew all defective life preservers with US Coast Guard/Solas approved lifepreservers. Until renewed, vessel is to maintain immersion suits onboard ready for use.
Condition: Unknown
Due 19 February 1995
Resolved 19 February 1995
Electrical
Issued 19 February 1995
Resolved
Numerous runs of electric cable secured with plastic tie wraps. Properly secure electric cable with metal tie wraps in accordance with IEEE 45.
Condition: Unknown
Due 19 February 1995
Resolved 19 February 1995
Fire Fighting
Issued 19 February 1995
Resolved
Properly label each cabinet or space that contains a valve control, or manifold of a fixed fire extinguishing system IAW 46CFR108.631..."Foam fireapparatus, Carbon dioxide fire apparatus"... in letters at least 2 inches high.
Condition: Unknown
Due 4 May 1995
Resolved 4 May 1995
Documentation
Issued 11 November 1994
Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Unknown
Due 4 December 1994
Resolved 20 December 1994
Lifesaving
Issued 11 November 1994
Resolved
SUBMIT TO COGNIZANT O.C.M.I. FOR APPROVAL A REVISED FIRE SAFETY PLAN AND STATION BILL TO REFLECT ADDITION OF THIRD LIFE BOAT.
Condition: Unknown
Due 11 November 1994
Resolved 11 November 1994
Fire Fighting
Issued 15 April 1994
Resolved
HAVE ALL FIXED CO2 FIRE EXTINGUISHING SYSTEM BOTTLES WHICH HAVE NOT BEEN HYDROSTATICALLY TESTED WITHIN TWELVE (12) YEARS AND ALL PORTABLE AND SEMIPORTABLE FIRE EXTINGUISHERS WHICH HAVE NOT BEEN HYDROSTATICALLY TESTED WITHIN FIVE (5) YEARS TESTED BY A DOT APPROVED FACILITY.
Condition: Unknown
Due 15 April 1994
Resolved 15 April 1994
Lifesaving
Issued 15 April 1994
Resolved
PROVIDE INFORMATION ON THE LAST DATE OF THE PORT & STBD LIFEBOATS FALLS END/END TO [name withheld] THIS DATE IS GREATER THAN 2.5 YEARS, THEN THELIFEBOAT FALLS MUST BE END FOR ENDED, AND THE LIFEBOATS MUST BE WEIGHT TESTED IN THE PRESENCE OF A COAST GUARD MARINE INSPECTOR.
Condition: Unknown
Due 15 April 1994
Resolved 15 April 1994
Electrical
Issued 15 April 1994
Resolved
PERFORM TWO (2) HR LOAD TEST AND DEMONSTRATE EMERGENCY GENERATOR SAFETY SHUTDOWN DEVICES PRIOR TO COMMENCEMENT OF DRILLING OPERATIONS. NOTIFY OCMIHONOLULU BY LETTER (SIGNED BY OIM/ELECTRICIAN) OF THE SATISFACTORY TEST RESULTS.
Condition: Unknown
Due 15 April 1994
Resolved 15 April 1994
Construction/Loadline
Issued 15 April 1994
Resolved
REPAIR THE HORIZONTAL BRACE FWD ON STBD LEG (APPROX 145 FT) TO ABS APPROVEDREPAIR PROCEDURE AT NEXT SCHEDULED ABS SURVEY AND NLT 19 MAR 95. COPY OF ABS APPROVED REPAIR PROCEDURE TO BE PROVIDED TO [name withheld] PRIOR TO COMMENCEMENT OF REPAIRS.
Condition: Unknown
Due 15 April 1994
Resolved 15 April 1994
Engineering
Issued 15 April 1994
Resolved
PROVE PROPER OPERATION OF THE OILY WATER SEPARATOR.
Condition: Unknown
Due 15 April 1994
Resolved 15 April 1994
Construction/Loadline
Issued 21 December 1993
Resolved
GOUGE AND WELD FRACTURE AT STARBOARD LEG, "B" CHORD, AT APPROXIMATELY 15 FOOT LEVEL. WELDER IS TO BE "ABS" CERTIFIED. SUBMIT REPORT AND PHOTOGRAPHS, INCLUDING PHOTOS OF DYE PENETRANT TESTING AT COMPLETION OF REPAIRS.
Condition: Unknown
Due 31 January 1994
Resolved 31 January 1994
Documentation
Issued 17 April 1991
Resolved
PROVIDE COPY OF DIVCON INT'L UNDERWATER SURVEY REPORT TO [name withheld] INTO CASE FILE.
Condition: Unknown
Due 8 August 1991
Resolved 8 August 1991
Lifesaving
Issued 17 April 1991
Resolved
PROVIDE ON BOARD ONE ADDITIONAL O2/COMBUSTIBLE GAS LEL METER TO COMPLY WITHIMO REG 9.8.2 AND 9.9.1.
Condition: Unknown
Due 8 August 1991
Resolved 8 August 1991
Documentation
Issued 17 April 1991
Resolved
PROVIDE ON BOARD AN OPERATIONS MANUAL WHICH MEETS REQUIREMENTS SPECIFIED IN46 CFR 109.121.
Condition: Unknown
Due 17 April 1991
Resolved 17 April 1991
Fire Fighting
Issued 17 April 1991
Resolved
SUBMIT PLANS AND BILL OF MATERIAL FOR NEWLY INSTALLED EMERGENCY GENERATOR COMPARTMENT FIXED CO2 SYSTEM TO USCG MARINE SAFETY CENTER FOR REVIEW AND APPROVAL.
Condition: Unknown
Due 17 April 1991
Resolved 17 April 1991
Fire Fighting
Issued 17 April 1991
Resolved
INSTALL INSIDE STEEL COVERS FOR HOUSE WINDOWS WHICH FACE DRILL FLOOR TO COMPLY WITH IMO CODE REG 9.2.13.
Condition: Unknown
Due 8 August 1991
Resolved 8 August 1991
Engineering
Issued 17 April 1991
Resolved
INSTALL FUEL SUPPLY LINE SHUT OFF VALVE OPERABLE FROM OUTSIDE EMERGENCY GENERATOR COMPT FOR E GEN SKID MOUNTED FUEL TANK.
Condition: Unknown
Due 8 August 1991
Resolved 8 August 1991
Engineering
Issued 17 April 1991
Resolved
REPOSITION EMERGENCY GEN SKID FUEL TANK VENT FROM INSIDE COMPARTMENT TO OUTSIDE COMPARTMENT AND PROVIDE FLAME SCREEN FOR SAME.
Condition: Unknown
Due 8 August 1991
Resolved 8 August 1991
Engineering
Issued 4 December 1989
Resolved
INSTALL GLASS IN FUEL OIL DAY TANK SIGHT GLASS.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Fire Fighting
Issued 4 December 1989
Resolved
REPLACE TEMP FIRE HOSES WITH NFPA APPROVED HOSES AND NOZZLES AS SOON AS POSSIBLE, BUT NOT LATER THAN RETURNING RIG TO SERVICE.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Lifesaving
Issued 4 December 1989
Resolved
REPAIR THE OILY WATER SEPARATOR SENSOR, DEMONSTRATE PROPER OPERATION, AND PROVIDE IOPP FLANGE.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Electrical
Issued 4 December 1989
Resolved
REPAIR AND/OR RENEW ALL ELECTRICAL CABLE, JUNCTION BOXES, LIGHTS, CABLE TRAYS, SWITCHES, AND RECEPTACLES IN SHALE SHAKER AREA PRIOR TO COMMENCING ANY DRILLING OPERATION.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Engineering
Issued 4 December 1989
Resolved
INSULATE EXTERIOR EXHAUST LINES ON DIESEL ENGINES FOR CEMENT UNIT IN VICINITY OF WALKWAYS.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Lifesaving
Issued 4 December 1989
Resolved
PROVIDE 125% LIFE JACKETS (TOTAL 109). THE TOTAL PERSONS ALLOWED ONBOARD IS LIMITED TO 84 UNITL THIS REQUIREMENT IS MET.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Unknown
Issued 4 December 1989
Resolved
HAVE HALON BOTTLES #3 & #4 REMOVED, HYDRO TESTED, REFILLED AND RETURNED TO SERVICE PRIOR TO ENGAGING IN ANY DRILLING OPS. PLACE 2 SPARE B5 SEMI-PORT EXTINGUISHERS IN VICINITY OF ENTRANCES TO ENGINE ROOM AND MAKE AND LOG HOURLY FIRE WATCH UNITL BOTTLES ARE RETURNED AND PROPERLY INSTALLED.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Lifesaving
Issued 4 December 1989
Resolved
SUBMIT UPDATED LIFESAVING PLAN TO REFLECT CHANGE IN LIFE BOATS AND LIFE RINGS FOR REVIEW AND APPROVAL.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Electrical
Issued 4 December 1989
Resolved
PROVIDE EYS FITTINGS ON ALL DRILL FLOOR ELECTRICAL INSTALLATIONS AS REQUIRED BY 46 CFR 111.105.15.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Documentation
Issued 4 December 1989
Resolved
PROVIDE THE COAST GUARD WITH A COPY OF THE LOADLINE ENDORSEMENT AND CRANE WEIGHT TEST RESULTS UPON COMPLETION OF ABS SURVEYS.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Lifesaving
Issued 4 December 1989
Resolved
PROVIDE PYROTECHNICS FOR THE LIFE BOATS WHICH ARE WITHIN EXPIRATION DATE PRIOR TO ENGAGING IN ANY DRILLING OPERATIONS.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Fire Fighting
Issued 4 December 1989
Resolved
REPLACE UNSATISFACTORY FIREFIGHTING FOAM WITH NEW FOAM.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Lifesaving
Issued 4 December 1989
Resolved
PROVIDE ONE ADDITIONAL SPEEDLINE 250 LINE THROWING DEVICE BEFORE STARTING ANY TOWING OPERATION.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Lifesaving
Issued 4 December 1989
Resolved
PROVIDE A COPY OF COMDT (G-MTH) APPROVED LETTER ON NEW LIFEBOAT INSTALLATIONS.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Lifesaving
Issued 4 December 1989
Resolved
CONDUCT FIRE AND BOAT DRILLS BEFORE PERFORMING ANY TOWING OPERATIONS.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Lifesaving
Issued 4 December 1989
Resolved
SERVICE LIFE RAFT WHICH WAS DUE IN OCT 1989. PERSONS ONBOARD LIMITED TO 75.SERVICE LIFE RAFT WHICH WAS DUE IN DEC 1989. PERSONS ONBOARD LIMITED TO 50 AS OF 01 JAN 1990, OR UNTIL RAFTS SERVICED IN NOV 1989 ARE BROUGHT ONBOARD.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Deck/Cargo
Issued 4 December 1989
Resolved
PROVIDE DEAD MAN TYPE FUEL NOZZLES AT ALL 3 FUEL STATIONS (1 AT EACH CRANE)BEFORE ANY TOWING OPERATIONS ARE PERFORMED.
Condition: Unknown
Due 4 December 1989
Resolved 4 December 1989
Lifesaving
Issued 17 January 1989
Resolved
PROVIDE TWO USCG APPROVED FLOATING ORANGE SMOKE DISTRESS SIGNALS FOR PORT AND STARBOARD CAPSULES.
Condition: Unknown
Due 17 January 1989
Resolved 17 January 1989
Lifesaving
Issued 17 January 1989
Resolved
PROVIDE AN APPROVED SELF ACTIVATING SMOKE SIGNAL (UNDER SUBPART 160.057) WHICH ATTACHED TO THE RING LIFE BUOY.
Condition: Unknown
Due 17 January 1989
Resolved 17 January 1989
Construction/Loadline
Issued 17 January 1989
Resolved
CROP OUT AND RENEW WASTED BOTTOM PLATING IN WAY OUTBOARD OF FORWARD DUMP VALVE IN NO.1 CENTER PRELOAD TANK. INSERT SHALL NOT BE LESS THAN 1 1/2 SQUARE FEET AND ALL CORNERS TO BE ROUNDED.
Condition: Unknown
Due 17 January 1989
Resolved 17 January 1989
Lifesaving
Issued 17 January 1989
Resolved
REPAIR OR REPLACE THE EXISTING LIFEBOATS WHICH HAVE BEEN SUBJECT TO SEVERE OSMOTIC BLISTERING. IF REPAIRED, PROCEDURE IS TO BE APPROVED BY MANUFAC- TURER.
Condition: Unknown
Due 17 January 1989
Resolved 17 January 1989
Lifesaving
Issued 17 January 1989
Resolved
PROVIDE FOUR ROCKETS (2 BUOYANT) AND FOUR SERVICE LINES TO COMPLY WITH LINE THROWING APPLIANCE REQUIREMENT.
Condition: Unknown
Due 17 January 1989
Resolved 17 January 1989
Lifesaving
Issued 17 January 1989
Resolved
PROVIDE TWELVE HAND HELD ROCKET PROPELLED PARACHUTE RED FLARES.
Condition: Unknown
Due 17 January 1989
Resolved 17 January 1989
Lifesaving
Issued 23 July 1988
Resolved
SUBMIT A REPAIR PROPOSAL FOR THE BLISTERING AND DELAMINATION ON THE PORT AND STBD SURVIVAL CAPSULES. THE REPAIR PROPOSAL SHOULD INDLUDE DETAIL, ENDORSED BY THE BOAT MANUFACTURER, AND A SCHEDULE FOR COMPLETION OF REPAIRS.
Condition: Unknown
Due 23 July 1988
Resolved 23 July 1988
Lifesaving
Issued 23 March 1988
Resolved
PROVIDE COPY OF CERTIFICATE CONFIRMING SERVICING IN PRESENCE OF A USCG INSPECTOR OF PORT AFT DAVIT LAUNCHED INFLATABLE LIFERAFT REPLACED 28JAN88 AS PER YOUR 26FEB88 LETTER.
Condition: Unknown
Due 23 March 1988
Resolved 23 March 1988
Accommodation/Occupational Safety
Issued 3 December 1987
Resolved
ROOM 102 IS CURRENTLY ACCOMODATING 6 MEN, PROVIDE EVIDENCE OF USCG APPROVALFOR CONVERSION TO A 6 MAN BERTHING OR RE-ARRANGE SUBJECT BERTHING UNTIL SUCH APPROVAL IS OBTAINED.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Lifesaving
Issued 3 December 1987
Resolved
RENEW THE GRAB LINES ON BOTH LIFE CAPSULES.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Unknown
Issued 3 December 1987
Resolved
CONDUCT A DRILL AND TEST OF THE LINE THROWING APPLIANCE, LOG THE RESULTS, AND PROVIDE A COPY OF THE LOGGED ENTRY TO THE [name withheld], HI.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Unknown
Issued 3 December 1987
Resolved
CONDUCT FIRE AND BOAT DRILL, LOG THE RESULTS AND PROVIDE A COPY OF THE RESULTS TO THE [name withheld], HI.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Accommodation/Occupational Safety
Issued 3 December 1987
Resolved
REPLACE THE 5TH TOILET WHICH HAS BEEN REMOVED FROM THE 2 LEVEL HEAD FACILITY. THE CURRENT QUANTITY OF 4 TOILET STOOLS ARE NOT IN CONFORMANCE WITH THE VESSELS APPROVED PLANS.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Unknown
Issued 3 December 1987
Resolved
PROVIDE ASME LABLED RELIEF VALVES FOR ALL ON BOARD AIR RECEIVERS AND P-TANKS. RESET THE INITIAL RELIEF VALVES ON THE BULK TANKS TO LIFT NO HIGHER THAN THE MAWP.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Lifesaving
Issued 3 December 1987
Resolved
REPLACE THE OUT OF DATE SMOKE DEVICE LOCATED ON THE PORT BRIDGE.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Lifesaving
Issued 3 December 1987
Resolved
SERVICE THE OUT OF DATE INFLATABLE LIFERAFT LOCATED ON THE PORT SIDE AFT.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Electrical
Issued 3 December 1987
Resolved
PROVIDE AUTOMATIC DOOR CLOSURES ON BOTH MUD PIT DOORS.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Lifesaving
Issued 3 December 1987
Resolved
REPLACE THE DETERIORATED STARBOARD EMBARKATION LADDER.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Electrical
Issued 3 December 1987
Resolved
RE-INSTALL THE VOLTMETER FOR NO. 1 GENERATOR.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Lifesaving
Issued 3 December 1987
Resolved
PROVIDE THE PROPER TOOL KITS FOR EACH LIFE CAPSULE IN ACCORDANCE WITH 46 CFR 94.20-15(II).
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Deck/Cargo
Issued 3 December 1987
Resolved
REPAIR OR REPLACE THE DEFECTIVE PROXIMITY SWITCH FOR THE WHIP BLOCK ON THE BOW CRANE.
Condition: Unknown
Due 3 December 1987
Resolved 3 December 1987
Unknown
Issued 21 January 1987
Resolved
PROVIDE TWO FLAME SAFETY LAMPS FOR THE FIREMAN'S OUTFITS.
Condition: Unknown
Due 21 January 1987
Resolved 21 January 1987
Unknown
Issued 21 January 1987
Resolved
PROVIDE 162 QUARTS OF USCG APPROVED DRINKING WATER FOR MOTOR LIFEBOAT #2.
Condition: Unknown
Due 21 January 1987
Resolved 21 January 1987
Unknown
Issued 21 January 1987
Resolved
REPLACE THE PORT AND STBD DAVIT LAUNCHED LIFERAFT FALLS.
Condition: Unknown
Due 21 January 1987
Resolved 21 January 1987
Unknown
Issued 21 January 1987
Resolved
PROVIDE INSTRUCTION FOR KILGRO LINE THROWING APPLIANCE.
Condition: Unknown
Due 21 January 1987
Resolved 21 January 1987
Unknown
Issued 21 January 1987
Resolved
CONDUCT ANNUAL LIFERAFT SERVICING OF THE PORT SIDE FWD (25 MAN) LIFERAFT.
Condition: Unknown
Due 21 January 1987
Resolved 21 January 1987
Unknown
Issued 21 January 1987
Resolved
PROVIDE 162 QUARTS OF USCG APPROVED DRINKING WATER FOR MOTOR LIFEBOAT #1.
Condition: Unknown
Due 21 January 1987
Resolved 21 January 1987
Unknown
Issued 6 July 1986
Resolved
MAKE PERMANENT REPAIRS TO DAMAGED SIDESHELL AND BRACKETS IN NUMBER 1 PRELOAD TANK.
Condition: Unknown
Due 6 July 1986
Resolved 6 July 1986
Unknown
Issued 6 July 1986
Resolved
INSPECT SEA CHESTS, SPOOL PIECES, AND THROUGH HULL FITTINGS.
Condition: Unknown
Due 6 July 1986
Resolved 6 July 1986
Unknown
Issued 11 December 1985
Resolved
PROVIDE ONE ADDITIONAL PARACHUTE FLARE AND ONE QUART OF WATER FOR THE STARBOARD LIFEBOAT.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Unknown
Issued 11 December 1985
Resolved
REPAIR CRACKS IN TOP PART OF PORT AND STARBOARD LIFEBOATS. REPAIRS TO BE MADE BY A QUALIFIED SERVICE REPRESENTATIVE FROM WHITTAKER.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Unknown
Issued 11 December 1985
Resolved
CONDUCT INTERNAL INSPECTION OR HYRDOTEST AT 1.25 X'S MAWP/THE DRILL FLOOR AIR RECEIVER, 2 BARITE AND 1 BENTONITE TANKS.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Unknown
Issued 11 December 1985
Resolved
PROVIDE ONE CLASS BII FIRE EXTINGUISHER OUTSIDE OF THE PAINT LOCKER.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Unknown
Issued 11 December 1985
Resolved
PROVIDE SIX USCG APPROVED RING BUOYS AT THE LIFEBOAT/LIFERAFT DECK.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Unknown
Issued 11 December 1985
Resolved
MAKE PERMANENT REPAIRS TO TRIPPED FRAMES IN #6 PORT AND #6 STARBOARD PRE- LOAD TANKS.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Unknown
Issued 11 December 1985
Resolved
PROVIDE ONE ADDITIONAL 50 FEET OF 1.5" APPROVED FIRE HOSE.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Unknown
Issued 11 December 1985
Resolved
TEST RELIEF VALVES ON THE DRILL FLOOR AIR RECEIVER, 2 BARITE AND 1 BENTONITE TANKS.
Condition: Unknown
Due 11 December 1985
Resolved 11 December 1985
Lifesaving
Issued 5 December 1984
Resolved
PROVIDE 24 HAND HELD RED FLARES FOR NO. 1 AND NO. 2 SURVIVAL CAPSULES (12/CAPSULE).
Condition: Unknown
Due 5 December 1984
Resolved 5 December 1984
Lifesaving
Issued 5 December 1984
Resolved
PROVIDE TOTAL OF 4 (2 PER CAPSULE) FLOATING ORANGE DISTRESS SIGNALS FOR NO.1 AND NO. 2 SURVIVAL CAPSULES.
Condition: Unknown
Due 5 December 1984
Resolved 5 December 1984
Lifesaving
Issued 5 December 1984
Resolved
PROPERLY SERVICE ONE INFLATABLE LIFERAFT.
Condition: Unknown
Due 5 December 1984
Resolved 5 December 1984
Lifesaving
Issued 5 December 1984
Resolved
PROVIDE TOATAL OF 24 (12 PER CAPSULE) RED PARACHUTE FLARES FOR N0.1 AND N0.2 SURVIVAL CAPSULES.
Condition: Unknown
Due 5 December 1984
Resolved 5 December 1984