Records from 1980 to 1987. Most recent: inspection, 5 March 1987.
A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.
Inspection history · 13
5 March 1987
Administrative
Administrative · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1314454
27 January 1987
Administrative
Administrative · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1317896
10 June 1986
Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 999748
10 June 1986
Administrative
Administrative · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1011892
2 January 1986
Deficiency Check
Physical examination · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1293600
22 October 1985
Re-Inspection
Physical examination · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 996427
18 October 1984
Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1284625
7 June 1984
Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 972616
4 January 1983
Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1273080
24 November 1982
Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1274312
19 October 1982
Type not recorded
No type recorded · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1271794
15 March 1982
Type not recorded
No type recorded · MSO Mobile · USCG Heartland District (CGD-H) · Activity 1276512
20 October 1980
Type not recorded
No type recorded · MSO Mobile · USCG Heartland District (CGD-H) · Activity 968359
Documentation
Issued 22 October 1985
Resolved
SUBMIT FOR APPROVAL THE RIGS CLASSIFIED LOCATION PLAN PER 46 CFR 110.25-1(K)
Condition: Unknown
Due 22 October 1985
Resolved 22 October 1985
Deck/Cargo
Issued 22 October 1985
Resolved
PROVIDE NAMEPLATE DATA FOR ALL (04) FOUR "P" TANKS PROVIDE RELIEF VALVES NOT EXCEEDING MAWP OF THE TANKS PER 46 CFR 54.01-16
Condition: Unknown
Due 22 October 1985
Resolved 22 October 1985
Lifesaving
Issued 22 October 1985
Resolved
PROVIDE OUTBOARD MOTOR FOR THE RESCUE BOAT WITH REMOTE THROTTLE CAPABILITIES PER NVC4-78
Condition: Unknown
Due 22 October 1985
Resolved 22 October 1985
Engineering
Issued 22 October 1985
Resolved
PROVIDE SPECIFICATIONS FOR THE STOP COCK, FUEL OIL SUPPLY PIPING, ENGINES IN MOTOR ROOM PER 46 CFR 56.07-10
Condition: Unknown
Due 22 October 1985
Resolved 22 October 1985
Electrical
Issued 22 October 1985
Resolved
REPAIR INOPERATIVE OVERSPEED TRIP ON #6 ENGINE/GENERATOR SET. (46 CFR 107-231)
Condition: Unknown
Due 22 October 1985
Resolved 22 October 1985
Navigation
Issued 22 October 1985
Resolved
REPLACE BROKEN LENS ON THE STARBOARD AFTER OBSTRUCTION LIGHT PER 33 CFR 67
Condition: Unknown
Due 22 October 1985
Resolved 22 October 1985
Lifesaving
Issued 18 October 1984
Resolved
PROVIDE AN OPERATIONAL OUTBOARD MOTOR ON THE RESCUE BOAT. NVC 4-78.3.D(8) (A).
Condition: Unknown
Due 18 October 1984
Resolved 18 October 1984
Electrical
Issued 18 October 1984
Resolved
REPAIR THE NUMBER FOUR AND DRILL FLOOR DIESEL ENGINES OVERSPEED SHUTDOWN.
Condition: Unknown
Due 18 October 1984
Resolved 18 October 1984
Electrical
Issued 18 October 1984
Resolved
PROVIDE HEAT RESISTANT MATERIAL FOR THE FUEL OIL DAY TANK SIGHT GLASSES. 46 CFR 58.50
Condition: Unknown
Due 18 October 1984
Resolved 18 October 1984
Electrical
Issued 18 October 1984
Resolved
REPAIR THE NUMBER ONE FUEL OIL REMOTE SHUTDOWN. 46 CFR 111.80.
Condition: Unknown
Due 18 October 1984
Resolved 18 October 1984
Unknown
Issued 18 October 1984
Resolved
THE FOLLOWING DEFICIENCIES PERTAIN TO THE VESSEL, TRANSWORLD RIG 44, CG000253 AND WERE TO BE COMPLIED WITH BY 18NOV84.
Condition: Unknown
Due 18 October 1984
Resolved 18 October 1984
Electrical
Issued 18 October 1984
Resolved
REPAIR THE GENERAL ALARM BELL IN THE PUMP ROOM. 46 CFR 113.25.
Condition: Unknown
Due 18 October 1984
Resolved 18 October 1984
Accommodation/Occupational Safety
Issued 18 October 1984
Resolved
PROVIDE RELIEF VALVES FOR TWO BULK TANK. 46 CFR 54.15.
Condition: Unknown
Due 18 October 1984
Resolved 18 October 1984
Accommodation/Occupational Safety
Issued 18 October 1984
Resolved
PROVIDE TWO RELIEF VALVES MINIMUM ONE INCH SIZE, THAT CANNOT BE ISLOLATED FROM THE TWO PORTABLE WATER PRESSURE TANKS. 46 CFR 54.15.
Condition: Unknown
Due 18 October 1984
Resolved 18 October 1984
Lifesaving
Issued 18 October 1984
Resolved
A TOTAL OF NO MORE THAN THIRTY SEVEN 37 PERSONS WILL BE ALLOWED ON THE RIG AT ONE TIME UNITIL SUCH TIME THAT THE 25 MAN INFLATABLE LIFERAFT NOW BEING SERVICED IS RETURNED TO THE RIG. THE RAFT IS TO BE RETURNED PRIOR TO 18NOV84 46 CFR 505 AND NVC 4-78.
Condition: Unknown
Due 18 October 1984
Resolved 18 October 1984
Unknown
Issued 24 November 1982
Resolved
SUBMIT WELD PROCEDURE, TANK & REPAIR MATERIAL ASTM OR ASME SPECIFICATION & TYPE OF STRESS RELIEF USED REGARDING REPAIRS TO #3 & #4 CEMENT TANKS.
Condition: Unknown
Due 24 November 1982
Resolved 24 November 1982
Electrical
Issued 24 November 1982
Resolved
PROVIDE SLIDING LOCKOUT BAR TO PREVENT PARALLEL OPERATION OF AC GENERATORS.
Condition: Unknown
Due 24 November 1982
Resolved 24 November 1982