Records from 2010 to 2026. Most recent: inspection, 16 April 2026.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 7 January 2026
Resolved
A vessel must have one or more ring life buoys. Marine Inspector found the ring life buoy's line no longer serviceable. 46 CFR 180.70 (a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 January 2026
Resolved 26 February 2026
Resolution: Vessel added new life ring
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 7 January 2026
Resolved
Distress signals: Lakes, bays, and sounds, and rivers routes. A vessel on a lakes, bays, and sounds, or rivers route must carry: Three hand red flare distress signals approved in accordance with § 160.021 in subchapter Q of this chapter and three hand orange smoke distress signals approved in accordance with § 160.037 in subchapter Q of this chapter Marine Inspector found two expired hand flares. 46 CFR 180.68 (b)(1)(2)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 January 2026
Resolved 26 February 2026
Resolution: Vessel has correct amount of flares
09 - Working and Living Conditions › 092 - Working Conditions › Warning notices
Issued 7 January 2026
Resolved
On a vessel on which the number of passengers permitted on upper decks is limited by stability criteria, as indicated by the vessel's stability letter, the maximum number of passengers allowed on an upper deck must be indicated by a durable marking of at least 25 millimeters (1 inch) numbers and letters at the entrance to that deck. 46 CFR 185.602 (g)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 January 2026
Resolved 26 February 2026
Resolution: Vessel operator installed sign
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 7 January 2026
Resolved
Each child size life jacket must be stowed in a location that is appropriately marked and separated from adult life jackets so the child size life jackets are not mistaken for adult life jackets. Marine Inspector found child life jackets not separate from adult life jackets. 46 CFR 180.78 (a)(5)
Condition: Design Flaw
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 January 2026
Resolved 26 February 2026
Resolution: Operator seperated lifejackets
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 7 September 2022
Resolved
46 CFR 181.420(a)(2) - The fixed gas extinguishing system must be operable from outside the space. The safety pin was installed in the system, rendering the remote operation cable disabled. Fixed on the spot.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 7 September 2022
Resolution: Fixed on the spot
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 7 September 2022
Resolved
The water heater is not fitted with a nameplate, and operating specifications could not be found. Demonstrate compliance with 46 CFR 182.320(a) by submitting specifications showing that the water heater’s capacity and heat input are below 120 gallons and 200,000 BTU/hr and that it is listed under UL 174 or UL 1453.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 October 2022
Resolved 14 September 2022
Resolution: Owner provided manufacturer spec sheet showing capacity and heat input are below 120 gallons and 200,000 BTU/hr and that it is UL approved. [name withheld]
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 7 September 2022
Resolved
46 CFR 183.220 - Remove all power strips onboard that are not suitable for service in a marine environment to the satisfaction of the attending marine inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 October 2022
Resolved 6 January 2025
Resolution: Power strips removed.
04 - Emergency Systems › N/A - No Subsystem › Emergency source of power - Emergency generator
Issued 7 September 2022
Resolved
46 CFR 183.310(a)(1)(i) - Demonstrate that the fire pump and bilge pump are operable from a secondary source of power.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 October 2022
Resolved 6 January 2025
Resolution: Fire pump and bilge pump operational.
04 - Emergency Systems › N/A - No Subsystem › Emergency fire pump and its pipes
Issued 7 September 2022
Resolved
46 CFR 181.300(e) - Troubleshoot and repair intermittent failures on bridge remote fire pump start switch
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 October 2022
Resolved 14 September 2022
Resolution: Relay was tightened, testing onboard from remote switch in the pilothouse was satisfactory.
[name withheld]
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 7 September 2022
Resolved
33 CFR 86.01 - Troubleshoot and repair intermittent failures on compressor powering the ship’s horn
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 October 2022
Resolved 6 January 2025
Resolution: Ships horn operational.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 7 September 2022
Resolved
46 CFR 185.604(f) - All containers which are designated for storage of PFDs must be labeled with the number and identification of the PFDs stowed inside. Containers for child-sized PFDs must be labeled accordingly and segregated.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 October 2022
Resolved 6 January 2025
Resolution: PFD' labeled and stored properly.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Machinery space openings
Issued 7 September 2022
Resolved
46 CFR 176.800(a) - Access to the aft machinery and water tank spaces is currently made with a strip of tape on the hatch cover. Modify the hatch cover to facilitate easy access.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 October 2022
Resolved 6 January 2025
Resolution: Hatch modified.
11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 7 September 2022
Resolved
46 CFR 180.70(d) - Renew the battery in the ring buoy float light. Perform an operational test of the light to the satisfaction of the attending marine inspector.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 October 2022
Resolved 14 September 2022
Resolution: Battery installed and light working as designed - [name withheld]
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 7 September 2022
Resolved
46 CFR 183.354(b) - Modify the battery installation such that it is protected from falling objects
Action required: 50 - Rectify deficiencies w/in 30 days
Due 7 October 2022
Resolved 6 January 2025
Resolution: Batteries protected from falling objects.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 26 October 2021
Resolved
Pre-engineered fixed gas fire extinguishing system installed must be capable of manual actuation from outside the space in addition to automatic heat activation. Properly install manual pull cable and mark with directions to activate system.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 November 2021
Resolution: Received tech report from Arizona West Fire & Safety attesting to installation and testing of manual pull cable.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 26 October 2021
Resolved
Pre-engineered fixed gas fire extinguishing system installed must automatically shut down all power ventilation fans and engines that draw intake air from the space protected and be provided with a means to reset fans/engines. Properly install shutdown and reset devices for fans and generator. Provide 3rd party servicing report of proper operation.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 November 2021
Resolution: Received tech report from Arizona West Fire & Safety attesting to testing of pressure switch for generator and blower shutdown.
04 - Emergency Systems › N/A - No Subsystem › Water level indicator
Issued 26 October 2021
Resolved
An unmanned machinery space bilge subject to flooding from sea water piping within the space must be provided with a visual and audible alarm at the operating station to indicate high water level. Properly install an intrinsically safe bilge high water alarm in the generator space.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 23 November 2021
Resolution: Received picture and video of working bilge alarm.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 26 October 2021
Resolved
Provide 56 adult & 09 child Type I lifejackets. Pax count reduced to 79 adults & 05 children.
Update 11/4 - all children lifejackets on board.
Update 11/23 - 40 additional adult lifejackets on board.
Update 12/13 - 16 additional adult lifejackets on board.
Action required: 705 - Other - as specified
Resolved 13 December 2021
Resolution: Spoke with POC. All lifejackets marked and on board. Picture added to vessel file.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 26 October 2021
Resolved
Add master to random drug testing program or shared agreement from other company's program.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 November 2021
Resolved 23 November 2021
Resolution: Received proof of new USCG Consortium, master's pre-employment testing and full active random testing pool
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 26 October 2021
Resolved
Mark both stairwells to upper deck "Max Passengers 54."
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 November 2021
Resolved 4 November 2021
Resolution: Recieved pictures of max passengers 54 at each stairwell.
10 - Safety of Navigation › N/A - No Subsystem › Magnetic compass
Issued 26 October 2021
Resolved
Install illuminated magnetic compass. Illumination required prior to nighttime/reduced visibility ops.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 November 2021
Resolved 4 November 2021
Resolution: Received picture of illuminated magnetic compass.
10 - Safety of Navigation › N/A - No Subsystem › Charts
Issued 26 October 2021
Resolved
Provide chart of Lake Havasu.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 November 2021
Resolved 23 November 2021
Resolution: Lake Havasu map provided.
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 26 October 2021
Resolved
Provide watertight case for/marked “Distress Signals.”
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 November 2021
Resolved 4 November 2021
Resolution: Received picture.
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 26 October 2021
Resolved
Renew blocks for rescue platform.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 November 2021
Resolved 4 November 2021
Resolution: Received picture of new blocks installed.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Bilge pumping arrangements
Issued 26 October 2021
Resolved
Provide portable hand bilge pump with sufficient hose length. (5 Gallons per minute capacity)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 November 2021
Resolved 23 November 2021
Resolution: Picture of hand pump and 25' hose provided.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 26 October 2021
Resolved
Make lip for battery box to prevent battery acid from leaking onto deck.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 November 2021
Resolved 29 November 2021
Resolution: Picture received.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 26 October 2021
Resolved
Add additional length (50’) of anchor line.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 November 2021
Resolved 4 November 2021
Resolution: Received picture.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Covers (hatchway-, portable-, tarpaulins, etc.)
Issued 26 October 2021
Resolved
Seal deck hatches to make weathertight.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 26 November 2021
Resolved 23 November 2021
Resolution: Pictures of sealed hatches received.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 26 October 2021
Resolved
Provide ring life buoy light for one ring buoy with 3’ line & spring loaded clip. Prior to night ops.
Action required: 705 - Other - as specified
Resolved 29 November 2021
Resolution: Picture received.