07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 6 October 2020
No resolution recorded
New installations of fire protection equipment on an existing vessel which are completed to the satisfaction of the cognizant Officer in Charge, Marine Inspection (OCMI) on or after March 11, 1996, must comply with the regulations of this part. Manual activation cable for Fireboy is not installed in accordance with manufacturer’s instructions. Configure according to manufacturer’s instructions.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 2 October 2020
No resolution recorded
To maintain a valid Certificate of Inspection, you must complete your annual inspection within the periods specified in §176.500(b)(1) and your Certificate of Inspection must be endorsed. Vessel has exceeded the 3 month window from its anniversary date for an annual inspection and exceeded the required drydock date without completing required inspections. Vessel shall not carry passengers until both a credit drydock and an annual COI inspection have been satisfactory completed.
Condition: Invalid
Action required: 701 - Prior to carriage of passengers/cargo
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 15 August 2019
Resolved
Vessel is required to ensure the EPIRB's battery is replaced after it is used, or before the date required by FCC regulations in 47 CFR part 80, whichever comes sooner. Vessel's EPIRB battery was past its expiration date. Replace battery to satisfaction of attending Coast Guard Marine Inspector. Vessel restricted to within one mile of shore.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 August 2019
Resolved 27 August 2019
Resolution: Verified new battery installed on EPIRB. Registration matched what was on board, all sat.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 15 August 2019
Resolved
Electrical equipment in a location normally exposed to splashing, water washdown, or other wet conditions must be dripproof. Electrical junction box underneath port aft deck speaker is exposed to the weather and allows water ingress. Provide appropriate protection from wet and corrosive environment.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 August 2019
Resolved 27 August 2019
Resolution: Waterproof sealant was used to protect electrical equipment exposed on deck, all sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 15 August 2019
Resolved
Machinery and fuel tank spaces must be separated from accommodation spaces by boundaries that prevent the passage of vapors. The starboard outermost cable penetration on the aft engine room bulkhead has a penetration that is not vapor tight. Provide a proper seal to prevent the passage of vapors.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 August 2019
Resolved 27 August 2019
Resolution: Fire retardant and waterproof sealand was used around cable penetration, all sat.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Railing, gangway, walkway and means for safe passage
Issued 15 August 2019
Resolved
Deck rails must be designed and constructed to withstand a point load of 200 pounds applied at any point in any direction. Deck rails on the port and starboard bow just forward of the stairs leading to the forecastle are loose. Provide proper support on all bow deck rails.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 August 2019
Resolved 27 August 2019
Resolution: All deck rails had been properly secured.
02 - Structural Conditions › N/A - No Subsystem › Decks - corrosion
Issued 15 August 2019
Resolved
A vessel must ensure that the material condition is satisfactory for its intended service. A portion of deck planking in the forward port side of the main deck is rotted through and no longer supports normal body weight. Repair deck planking to the satisfaction of the attending marine inspector.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 August 2019
Resolved 27 August 2019
Resolution: Cosmetic deck planking repair was satisfactory.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 15 August 2019
Resolved
Each life jacket must be marked with Type I retroreflective material approved in 46 CFR 164.018. Three life jackets were not marked with appropriate retroreflective material. Provide appropriate markings to the satisfaction of the attending marine inspector. Passenger count reduced to 46.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 29 August 2019
Resolved 27 August 2019
Resolution: Proper retroreflective material was provided for the remaining three lifejackets. PAX count returned to full COI ammount.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 1 October 2018
Resolved
The design, materials, and construction of mast, post, yards, booms, bowsprits, and standing rigging on a sailing vessel must be suitable for the intended service. Provide vessels last sail rigging survey.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 24 October 2018
Resolution: adequate survey provided.
Lifesaving › Lifebuoys › Buoyant Lifeline
Issued 14 June 2018
Resolved
Remove buoyant line from one of the three ring life buoys.
Action required: 10 - Deficiency Rectified
Resolved 14 June 2018
Resolution: All 3 liferings had lines attached. Vessel removed one immediately to satisfy deficiency.
Engineering › Fuel Oil Service System › Suction Strainer
Issued 14 June 2018
Resolved
Replace flame screen bowls under both fuel strainers in engine room.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 28 June 2018
Resolved 28 June 2018
Resolution: Received photos of bowls installed as required.
Operations/Management › Drug and Alcohol Testing › Employee Coverage
Issued 19 October 2017
Resolved
Provide drug and alcohol testing program for vessel IAW 46 CFR Part 16 and 49 CFR Part 40
Condition: Invalid
Action required: 705 - Other - as specified
Due 19 November 2017
Resolved 14 December 2017
Resolution: Completed Dapi audit
Engineering › Diesel Engine (propulsion-reduction gear) › Exhaust Manifold
Issued 19 October 2017
Resolved
Repair oil leaks on main engine. Oil leaks were located were the exhaust piping connected to the engine exhaust manifolds on both sides of the engine.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 19 November 2017
Resolved 14 December 2017
Resolution: Satisfactorily repaired
Engineering › Diesel Engine (propulsion-reduction gear) › Exhaust Manifold
Issued 19 October 2017
Resolved
Replace collapsed hose provided cooling water to the STBD exhaust piping on the engine.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 19 November 2017
Resolved 14 December 2017
Resolution: Collapsed hose replaced
Fire Fighting › Fixed Halon Fire Extinguishing System › Operating Controls
Issued 19 September 2017
Resolved
Rewire preengineered fixed fire extinguishing system to include deenergizing engine room ventilation fans. Until rewiring is complete, post instructions at helm to indicate to master to manually shut ventilation off before discharge of preengineering fixed fire extinguishing system. 46 CFR 181.420(a)(3).
Condition: Invalid
Action required: 705 - Other - as specified
Due 28 September 2017
Resolved 28 September 2017
Resolution: Operationally tested fire boy system. Verified engine and ventilation shut down.
Operations/Management › Drug and Alcohol Testing › Recordkeeping
Issued 19 September 2017
Resolved
Conduct a DAPI Audit with a qualified marine inspector. Current records indicate that company's DAPI program is inadequate. 46 CFR 16.203
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 19 November 2017
Resolved 14 December 2017
Resolution: Dapi audit complete
Accommodation/Occupational Safety › Occupational Safety › Guards for Exposed Hazards
Issued 19 September 2017
Resolved
Insulate engine exhaust elbows. 46 CFR 177.970
Action required: 705 - Other - as specified
Due 19 October 2017
Resolved 19 October 2017
Resolution: Verified that exhaust elbows were wrapped with insulation. All sat.
Accommodation/Occupational Safety › Occupational Safety › Guards for Exposed Hazards
Issued 19 September 2017
Resolved
Install guards on rotating belts on main engine.
Condition: Invalid
Action required: 705 - Other - as specified
Due 19 November 2017
Resolved 20 November 2017
Resolution: Vessel rep provided pictures for machinery guards.
Engineering › Fuel Oil Storage/Transfer System › Vent Pipe
Issued 19 September 2017
Resolved
Install 30 x 30 flame screen mesh on fuel tank vent pipes. 46 CFR 182.450
Condition: Invalid
Action required: 705 - Other - as specified
Due 19 October 2017
Resolved 19 October 2017
Resolution: Verified that 30 x 30 mesh screen was installed as a flame screen on the fuel tank vent openings.
Navigation › Piloting/Steering › Tide/Tidal Current Tables
Issued 19 September 2017
Resolved
Provide tidal current tables for operating area from an approved source. 46 CFR 184.420
Action required: 705 - Other - as specified
Due 28 September 2017
Resolved 28 September 2017
Resolution: Vessel provided print out of tidal current tables for operating area.
Electrical › Electric Supply System (service) › Overcurrent Device
Issued 3 August 2017
Resolved
Ensure all fuses are UL Listed cartridge type fuses, listed to provide branch circuit protection to protect the circuit conductors. UL Listed Class CC, G, H, J, K, RK1, RK5, & T are all UL listed to protect conductors.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 20 October 2017
Resolved 19 October 2017
Resolution: Verified all blade type fuses were replaced with UL listed cartridge type fuses, listed to protect conductors. All sat.
Electrical › Electrical Distribution System (service) › Wiring
Issued 3 August 2017
Resolved
Ensure terminal connections are made with "captive type" connectors & sized appropriately.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 20 October 2017
Resolved 19 October 2017
Resolution: Verified that terminal connectors previously found to be of the wrong type, were replaced with connectors that were captive type. All sat.
Electrical › Electrical Distribution System (service) › Ground Detection
Issued 3 August 2017
Resolved
Provide required ground-detection meter to monitor current flow in the "neutral-to-hull" connection from the inverter chasis to the ship's hull.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 20 October 2017
Resolved 19 October 2017
Resolution: Verified that required ground-detection meter was installed. All sat.
Electrical › Electric Supply System (service) › Overcurrent Device
Issued 3 August 2017
Resolved
Ensure fuses installed for bow-thruster battery bank can be disconnected by a disconnect switch installed on the supply side of the fuse.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 19 September 2017
Resolved 19 September 2017
Resolution: Battery switch has been installed so that it de-energizes the supply side of the fuses as required.
Electrical › Electrical Distribution System (service) › Wiring
Issued 3 August 2017
Resolved
Provide updated DC electrical one-line diagram & DC load analysis to reflect changes made to the electrical system.
Condition: Invalid
Action required: 705 - Other - as specified
Due 19 November 2017
Resolved 13 June 2018
Resolution: Plans submitted and verified.
Electrical › Electrical Distribution System (service) › Overcurrent Device
Issued 27 September 2016
Resolved
Replace blade-type fuses located in fuel tank shut off valve compartment, located just aft of the engine room. Fuses panel is located in upper PORT side corner of the space.
Condition: Invalid
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Vessel engineer replaced blade-type fuses with cartridge type glass-tube fuses. Requested datasheets for fuses from engineer to verify UL Listing.
Navigation › Piloting/Steering › Tide/Tidal Current Tables
Issued 27 September 2016
Resolved
Provide updated paper copies of current and tide tables
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Verified vessel had updated tide tables
Navigation › Piloting/Steering › Coast Guard Light List
Issued 27 September 2016
Resolved
Provide updated copy of USCG Light list
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Verified vessel had updated CG light list
Navigation › Piloting/Steering › Marine Charts
Issued 27 September 2016
Resolved
Provide current/updated charts of vessel's operating area/route
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Verified vessel had updated/current charts
Stability › Watertight Integrity › General
Issued 27 September 2016
Resolved
Prevent cooler drain hose from penetrating E/R boundary in aft galley void and plug/seal holes in the bulkhead.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Verified cooler drain hose penetrating E.R bulkhead was removed, and hole in E/R bulkhead was properly sealed.
Electrical › Electrical Distribution System (service) › Wiring
Issued 27 September 2016
Resolved
Complete outstanding electrical deficiencies from previous CG-835s and 2016 dry dock worklist.
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Cleared previous outstanding deficiencies.
Construction/Loadline › Hull › Longitudinal Frame
Issued 27 September 2016
Resolved
Sister or replace 3rd overhead longitudinal wood beam in FWD galley void.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Verified 3rd overhead longitudinal in FWD galley void had been sistered.
Construction/Loadline › Hull › Longitudinal Frame
Issued 27 September 2016
Resolved
Replace wood used to "sister" 2nd longitudinal wood frame in foward galley void.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Verified sister member to 2nd longitudinal frame in forward galley had been replaced.
Electrical › Electrical Distribution System (service) › Wiring
Issued 27 September 2016
Resolved
Make all electrical connections/terminal strips in away of bilges "splash proof".
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Verified terminal connections in bilge were made splash proof.
Stability › Watertight Integrity › General
Issued 27 September 2016
Resolved
Remove rust scale off of all watertight hatch sealing surfaces. Conduct fire hose test of all watertight hatches.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Verified watertight hatch sealing surfaces were free of rust scale. Witnessed hose test, all sat
Electrical › Electrical Distribution System (service) › Circuit Breaker
Issued 27 September 2016
Resolved
Replace supplemental circuit breakers located in galley panel with circuit breakers that meet 46CFR 183.380 and UL 489.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Vessel engineer added glass tube cartridge type fuses in-line with UL 1077 circuit breakers. Requested fuse datasheets to verify UL Listing.
Electrical › Electric Generation Source (service) › Generator
Issued 27 September 2016
Resolved
Clean excessive oil build up from alternator windings
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Verified alternator windings had been cleaned
Lifesaving › Lifejacket/PFD (General) › Storage
Issued 27 September 2016
Resolved
Properly mark lifejacket stowage locations on forward upper deck.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Verified stowage marking for lifejacket stowage areas.
Documentation › Markings/Placards › Lifejacket Placard
Issued 27 September 2016
Resolved
Post required lifejacket donning placards where lifejackets are stowed.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 27 October 2016
Resolved 6 October 2016
Resolution: Verified lifejacket donning placards were posted.