Inspection history · 17
14 December 1989
Administrative
Administrative · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1219112
9 January 1989
Deficiency Check
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1349937
9 December 1988
COI Inspection
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1037812
10 December 1987
Administrative
Administrative · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1001934
19 November 1987
Administrative
Administrative · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1336142
27 July 1987
Hull Examination · COI Inspection
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1030469
4 July 1987
MARPOL Annex II Examination
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1030795
13 February 1987
Deficiency Check
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1020576
6 January 1987
Administrative
Administrative · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1314581
2 December 1986
Administrative
Administrative · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1023591
17 November 1986
Administrative
Administrative · MIO NEW ORLEANS · USCG Heartland District (CGD-H) · Activity 1015606
27 October 1986
Re-Inspection
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1019553
8 October 1985
Type not recorded
No type recorded · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1301195
3 October 1985
COI Inspection
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 987218
31 August 1985
Credit Drydock
Administrative · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 987217
12 August 1985
Deficiency Check
Physical examination · ACTIVITIES NEW YORK · USCG Northeast District (CGD-NE) · Activity 1291868
31 March 1985
Type not recorded
No type recorded · MSO HONOLULU · USCG Oceania District (CGD-O) · Activity 1287731
Electrical
Issued 9 December 1988
Resolved
PROVE PROPER OPERATION OF GENERAL ALARMS IN RADIO ROOM AND EXPAT. GALLEY.
Condition: Unknown
Due 9 December 1988
Resolved 9 December 1988
Engineering
Issued 9 December 1988
Resolved
PROVE PROPER OPERATION OF BOILER LOW WATER SAFETY SWITCH.
Condition: Unknown
Due 9 December 1988
Resolved 9 December 1988
Engineering
Issued 9 December 1988
Resolved
PROVIDE APPROVED PLANS TO OCMI NEW YORK FOR THE AIR COMPRESSOR, PIPING AND AIR RECEIVERS USED IN THE DIVING AIR SYSTEM.
Condition: Unknown
Due 10 March 1989
Resolved 18 May 2002
Resolution: MISLE Maintenance - Resolved all open deficiencies issued prior to 6/1/1997 where activity was closed and deficiency due date was past
Documentation
Issued 9 December 1988
Resolved
CHANGE THE HAILING PORT ON VESSEL AND RING BUOYS TO EITHER THE HOMEPORT OR THE OWNERS ADDRESS (NEW ORLEANS, LA)
Condition: Unknown
Due 9 December 1988
Resolved 9 December 1988
Fire Fighting
Issued 27 July 1987
Resolved
REPLACE PRESENT PLYWOOD CONSTRUCTED DOORS LEADING FROM THE OPEN DECK TO THEBARGE OFFICES ON PORT SIDE WITH APPROVED METAL DOOR.
Condition: Unknown
Due 27 July 1987
Resolved 27 July 1987
Engineering
Issued 27 October 1986
Resolved
UPON INSTALLATION OF NEW OILY WATER SEPARATOR PROVE OPERATION.
Condition: Unknown
Due 27 October 1986
Resolved 27 October 1986
Engineering
Issued 27 October 1986
Resolved
CONDUCT INTERNAL AND EXTERNAL EXAMINATION OF AUXILIARY BOILER (JOHNSTON). CONDUCT HYDROSTATIC TEST. OPERATIONAL TEST AND TEST RELIEF VALVES.
Condition: Unknown
Due 27 October 1986
Resolved 27 October 1986
Construction/Loadline
Issued 27 October 1986
Resolved
REPLACE WASTED DECK PLANKING.
Condition: Unknown
Due 27 October 1986
Resolved 27 October 1986
Lifesaving
Issued 27 October 1986
Resolved
REPAIR HOLES IN SAFETY NETTING AROUND ENTIRE PERIMETER OF HELICOPTER DECK.
Condition: Unknown
Due 27 October 1986
Resolved 27 October 1986
Fire Fighting
Issued 27 October 1986
Resolved
PROVIDE COVER FOR FIXED NATURAL VENTILATION ON PAINT LOCKER TO CONFORM TO 46 CFR 95-15-35(C).
Condition: Unknown
Due 27 October 1986
Resolved 27 October 1986
Fire Fighting
Issued 27 October 1986
Resolved
PROVIDE CALIBRATION TEST GAS FOR OXYGEN/COMBUSTIBLE GAS METER AND PROVE PROPER OPERATION.
Condition: Unknown
Due 27 October 1986
Resolved 27 October 1986
Lifesaving
Issued 27 October 1986
Resolved
CONDUCT ANNUAL SERVICING OF INFLATABLE LIFE RAFT HYDROSTATIC RELEASES (13).
Condition: Unknown
Due 27 October 1986
Resolved 27 October 1986
Fire Fighting
Issued 27 October 1986
Resolved
PROVIDE ADDITIONAL 150 POUNDS OF FIXED CO2 FOR PAINT LOCKER (4352 CUBIC FEET) TO COMPLY WITH 46 CFR 95-15-5(E).
Condition: Unknown
Due 27 October 1986
Resolved 27 October 1986
Fire Fighting
Issued 27 October 1986
Resolved
REPAIR OR REPLACE AFT FIRE PUMP AND PROVE PROPER OPERATION.
Condition: Unknown
Due 27 October 1986
Resolved 27 October 1986
Fire Fighting
Issued 27 October 1986
Resolved
REPLACE 4 50' 1 1/2" FIRE HOSES WITH 4 75' 1 1/2" U.S. COAST GUARD APPROVEDFIRE HOSES AS PER MCDERMOTT FIRE CONTROL PLAN.
Condition: Unknown
Due 27 October 1986
Resolved 27 October 1986
Fire Fighting
Issued 27 October 1986
Resolved
REPLACE OR RE-HYDRO ALL DRY CHEMICAL CHARGING CYLINDERS THROUGHOUT VESSEL THAT HAVE HYDRO DATE 12 YEARS OR OLDER.
Condition: Unknown
Due 27 October 1986
Resolved 27 October 1986
Construction/Loadline
Issued 3 October 1985
Resolved
PROVIDE OCMI NY AN APPROVED PLANS OR LETTER FROM US COAST GUARD OF THE NEW INSTALLED SEA CHEST, OR VERIFY APPROVAL OF ORIGINAL PLAN M-603.
Condition: Unknown
Due 3 October 1985
Resolved 3 October 1985
Unknown
Issued 3 October 1985
Resolved
PROVE PROPER OPERATION OF VESSEL'S OILY WATER SEPERATOR.
Condition: Unknown
Due 3 October 1985
Resolved 3 October 1985
Deck/Cargo
Issued 31 March 1985
Resolved
AMERICAN DERRICK AND MAINTENANCE CRANE SHALL BE TESTED IN ACCORDANCE WITH 46CFR91.37 AND REPORTS SUBMITTED FOR REVIEW.
Condition: Unknown
Due 31 March 1985
Resolved 31 March 1985
Fire Fighting
Issued 31 March 1985
Resolved
THE VESSEL FIRE CONTROL/SAFETY EQUIPMENT DRAWING SHALL BE SUBMITTED FOR REVIEW AND APPROVAL.
Condition: Unknown
Due 31 March 1985
Resolved 31 March 1985
Lifesaving
Issued 31 March 1985
Resolved
LIFERAFT STATIONS 5,6,7 AND 10 SHALL BE FITTED WITH MEANS FOR EMBARKATION.
Condition: Unknown
Due 31 March 1985
Resolved 31 March 1985
Fire Fighting
Issued 31 March 1985
Resolved
FIRE STATION NUMBERS 2,3,12,16,17 AND 18 SHALL BE PROVIDED WITH COAST GUARDAPPROVED COMBINATION NOZZLES.
Condition: Unknown
Due 31 March 1985
Resolved 31 March 1985
Accommodation/Occupational Safety
Issued 31 March 1985
Resolved
SERVICE ELEVATOR SAFETY RETAINING GATE SHALL BE REINSTALLED. CERTIFICATE OF MANUFACTURE, TEST AND INSPECTION RECORDS SHALL BE PROVIDED FOR COAST GUARD REVIEW.
Condition: Unknown
Due 31 March 1985
Resolved 31 March 1985
Accommodation/Occupational Safety
Issued 31 March 1985
Resolved
THE VESSELS OILY WATER SEPERATOR SHALL BE REPAIRED AND A STANDARD DISCHARGE CONNECTION INSTALLED.
Condition: Unknown
Due 31 March 1985
Resolved 31 March 1985
Fire Fighting
Issued 31 March 1985
Resolved
PLANS AND DETAILS FOR THE INSTALLATION OF A FIXED FIRE FIGHTING SYSTEM TO BE INSTALLED IN THE MAIN CRANE MACHINERY SPACE SHALL BE SUBMITTED.
Condition: Unknown
Due 31 March 1985
Resolved 31 March 1985
Electrical
Issued 31 March 1985
Resolved
GENERAL ALARM BELLS SHALL BE INSTALLED IN THE MAIN CRANE MACHINERY SPACE, CONTROL CAB AND FORWARD MODULAR ACCOMIDATIONS.
Condition: Unknown
Due 31 March 1985
Resolved 31 March 1985
Fire Fighting
Issued 31 March 1985
Resolved
THE HELICOPTER LANDING DECK SHALL BE PROVIDED WITH ONE ADDITIONAL COAST GUARD APPROVED BV FIRE EXTINGUISHER.
Condition: Unknown
Due 31 March 1985
Resolved 31 March 1985
Fire Fighting
Issued 31 March 1985
Resolved
THE 13 CO2 BOTTLES SERVING THE PORT WINCH ROOM AND ONE CO2 BOTTLE SERVING THE PAINT LOCKER SHALL BE HYDROTESTED, FILLED AND REINSTALLED. ALL FLEX LOOPS (40 TOTAL) SHALL BE TESTED HYDROSTATICALLY.
Condition: Unknown
Due 31 March 1985
Resolved 31 March 1985
Electrical
Issued 31 March 1985
Resolved
HEAT DEFLECTING SHIELDS SHALL BE INSTALLED ON THE RACOR FUEL FILTERS IN THE GENERATOR ROOM.
Condition: Unknown
Due 31 March 1985
Resolved 31 March 1985