07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 22 May 2024
Resolved
Every oil fuel pipe... shall be fitted with a cock or valve directly on the tank capable of being closed from a safe position outside the space concerned in the event of a fire occuring in the space in which such tanks are situated. PSCO obswerved wooden blocks inserted on quick closing valves LSFO #5 and #8 preventing remote closure.
(74 SOLAS (01) II-2/15.2.5)
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Due 22 May 2024
Resolved 22 May 2024
Resolution: Vessel crew removed the wooden blocks from the quick closing valve. Test Sat.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 22 May 2024
Resolved
Propulsion shall be made to facilitate cleaning, inspection, and maintenance of main propulsion machinery. PSCO observed active L/O leak on M/E L/O line valve with catch pan. F/o leak on #6 cylinder high pressure fuel line. (74 SOLAS (04) II-1/26.7)
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 May 2024
Resolution: Crew replaced gasket on L/O valve and replaced high pressure furel line.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 22 May 2024
Resolved
Any required fixed fire detection and fire alarm system w/ manually operated call points shall be capable of immediate operation at all times. Psco witnessed smoke detector above boiler hot well covered with rag disrupting operational readiness.
(74 SOLAS (01) II-2/13.1.1)
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 May 2024
Resolution: Crew removed rag from smoke detector. Crew stated it was covered while they were painting 03 days ago. Tested smoke detector, test SAT.
09 - Working and Living Conditions › 092 - Working Conditions › Steam pipes and pressure pipes
Issued 22 May 2024
Resolved
The machinery, boilers, and other pressure vessels associated piping systems and fittings shall be of a design and construction adequate for service for which they are intended and shall be so installed and protected as to reduce at minimum any dangers on board, due regard being paid to moving parts, hot surfaces, and other hazards. PSCO observed steam leak on heating line for F/O in purifier room.
74 SOLAS (04) II-1/26.1
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 May 2024
Resolution: Crew tightened loose fittings and leak was repaired.
09 - Working and Living Conditions › 092 - Working Conditions › Pipes, wires (insulation)
Issued 22 May 2024
Resolved
In a ship in which oil fuel is used, the arrangements for the storage, distribution, and utilization of the oil fuel shall be such as to ensure the safety of the ship and persons onboard. PSCO observed oil soaked lagging in the purifier room.
74 SOLAS (01) II-2/15.2
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 22 May 2024
Resolution: Crew replaced the oil soaked lagging with spares onboard.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 22 May 2024
Resolved
In a ship in which oil fuel is used, the arrangement for the storage, distribution, and utilization of the oil fuel shall be such to ensure safety of the ship and persons onboard. PSCO observed flexible hoses on air compressor auto drain line into 55 gallon drum in the engine room 1/3 full of oil.
74 SOLAS (01) II-2/15.2
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 May 2024
Resolution: Crew removed the flexible hose and 55 gallon drum from the engine room.