Records from 2001 to 2020. Most recent: inspection, 31 August 2020.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 12 December 2019
Resolved
A fan cover within an the duct was obstructing the operation of the starboard side engine room air damper. Re-secure fan cover.
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 December 2019
Resolved 16 March 2020
Resolution: Fan cover removed, witnessed operation of dampener, All SAT.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 12 December 2019
Resolved
A puddle of oil was found under the port side generator. Determine the source of the oil and repair as necessary.
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 December 2019
Resolved 19 August 2020
Resolution: Satisfactory repairs to generator completed and all oil removed below. SAT OPTEST completed of generator.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Auxiliary engine
Issued 12 December 2019
Resolved
Upon starting the starboard side generator, exhaust became present in the space. Determine the source of the exhaust and repair as necessary
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 December 2019
Resolved 16 March 2020
Resolution: MI witnessed operation of STBD generator, no exhaust leaks visible, All SAT.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 12 December 2019
Resolved
A wire splice aft of the starboard side steering gear was not in a junction box; This work occurred after the 23 Nov inspection. Place wire splice in an appropriate junction box.
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 December 2019
Resolved 16 March 2020
Resolution: All wires placed inside junction box, All SAT.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 12 December 2019
Resolved
The base of the rudder post bearing of starboard rudder was fractured. Repair or replace bearing as necessary.
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 December 2019
Resolved 16 March 2020
Resolution: STBD side rudder bearing replaced satisfactory.
09 - Working and Living Conditions › 092 - Working Conditions › Protection machines/parts
Issued 12 December 2019
Resolved
Port side generator missing machinery guard. Install machinery guard.
Action required: 701 - Prior to carriage of passengers/cargo
Due 12 December 2019
Resolved 16 March 2020
Resolution: Machinery guard on Port generator installed satisfactory.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 26 November 2019
Resolved
VESSEL REPORTED CASUALTY TO #1 GENERATOR.
SUBMIT WRITTEN AND SIGNED CAUSAL ANALYSIS.
SUBMIT TECHNICAL REPORT STATING THAT GENERATOR IS FULLY FUNCTIONAL, OPERATING PROPERLY AND WHAT CORRECTIVE ACTIONS HAVE BEEN TAKEN.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 27 November 2019
Resolution: MI's attended. Received causal analysis and technical report. All sat.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 23 November 2019
Resolved
Missing insulation on Engine Room hatch port side.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 16 March 2020
Resolution: Insulation replaced all SAT.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 23 November 2019
Resolved
Emergency light port and starboard side held in place with zip ties. Mount emergency light properly.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 16 March 2020
Resolution: Emergency lights on Port and STBD side engine rooms installed properly.
02 - Structural Conditions › N/A - No Subsystem › Bulkheads - cracking
Issued 23 November 2019
Resolved
Cracked welded spacers in forepeak tank need welded.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 16 March 2020
Resolution: Spacers properly welded in forepeak tank.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 23 November 2019
Resolved
Water pump had exposed wires. Enclose wire to fresh water pump in wateright enclosure.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 16 March 2020
Resolution: Wires for water pump were placed inside an enclosure.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 23 November 2019
Resolved
Exhaust leak on port generator. Investigate cause and make permenent repairs.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 16 March 2020
Resolution: MI witnessed operation of port generator, no exhaust leaks visible, All SAT.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 23 November 2019
Resolved
Batteries on port engine room missing fill caps. Replace caps.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 16 March 2020
Resolution: Cleared all SAT.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 23 November 2019
Resolved
Broken hand rail port side aft. Re-weld to satisfaction of Marine Inspector.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 19 August 2020
Resolution: Hand rail repair completed satisfactorily.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 23 November 2019
Resolved
Light cover in engine room port side was zipped tied. Repair or replace.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 16 March 2020
Resolution: Light cover replaced all SAT.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 23 November 2019
Resolved
Axe was laying on deck. Permenently mount fire axe.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 16 March 2020
Resolution: Fire Axe permanently mounted all SAT.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 23 November 2019
Resolved
Vessel has unknown hydraulic leak in lazerette from steering gear. Diagnose failure and make repairs to system components.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 16 March 2020
Resolution: attending MI witnessed operational test of steering system, no leaks at the time of inspection.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 23 November 2019
Resolved
Broken mounts at bottom of ladder port side aft compartment. Reweld to secure ladder to reduce crew hazard.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 16 March 2020
Resolution: Cleared all SAT.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 23 November 2019
Resolved
Light fixture in life jacket locker on main deck has exposed wires and no cover. Remove or replace light fixture.
Action required: 701 - Prior to carriage of passengers/cargo
Due 7 December 2019
Resolved 16 March 2020
Resolution: Light fixture in life jacket locker permanently removed, All SAT.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 3 September 2019
Resolved
Vessels fire detection system was found in inoperable condition. Vessel must return system to operational service prior to carrying passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 5 September 2019
Resolution: Conducted satisfactory test of fire detection system.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 3 September 2019
Resolved
Vessels fire suppression system was found to have expired servicing. Vessel must have fire suppression serviced and tested prior to carrying passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 5 September 2019
Resolution: Vessel provided current servicing records.
02 - Structural Conditions › N/A - No Subsystem › Other (Structural condition)
Issued 3 September 2019
Resolved
All vessel spaces where found to have excessive water in the bilge. Vessel was unable to determine where water was coming from. Vessel must clean bilges and investigate source of water ingress. prior to carrying passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 5 September 2019
Resolution: Vessel bilge cleaned of excessive amounts of water.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 3 September 2019
Resolved
Vessels air conditioning system was found to not maintain fire boundaries. Vessel must maintain fire boundaries. Prior to carrying passengers.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 5 September 2019
10 - Safety of Navigation › N/A - No Subsystem › Automatic Identification System (AIS)
Issued 6 November 2018
Resolved
Vsl is broadcasting incorrect Name, Vsl is not broadcasting dimension information (AIS Antenna Position ABCD values equals 0) and Vsl is not broadcasting static draft information
Condition: Invalid
Action required: 705 - Other - as specified
Resolved 25 August 2020
Resolution: Data inputs entered and broadcasting appropriately.
Engineering › Diesel Engine (propulsion-direct drive) › Pump, High Pressure (fuel injection)
Issued 14 July 2017
Resolved
Engine had low power.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 14 July 2017
Resolution: Sea trials successfully completed.
Engineering › Generator (propulsion-electric) › Circuit Board
Issued 8 September 2015
Resolved
Gauges for generator were not functional at operating station as per requirement 46CFR 119.410
Due 22 September 2015
Resolved 30 September 2015
Resolution: Received email notification attesting to the repairs to the INOP gauges; picture of operational gauge included. Gauges for generator have been repaired and are functional at operating station. All SAT
Construction/Loadline › Hull › Hull Plating
Issued 8 September 2015
Resolved
Provide repair proposal for pitting in Portside Crash compartment.
Due 22 September 2015
Resolved 23 October 2015
Resolution: Received email (w/pictures) attesting to the repairs of the pitting in Portside Crash compartment. Vessel master utilized local welder to complete the repairs. ALL SAT. Note: Repair proposal was received and approved by this office prior to hull repairs.
Engineering › Fuel Oil Service System › Hose
Issued 19 August 2014
Resolved
Fuel lines must be protected from mechanical injury. Place chaffing gear at points where the fuel lines make contact with the vessel and its machinery.
Condition: Improper Installation
Due 2 September 2014
Resolved 2 September 2014
Resolution: Attended vessel and cleared above deficiency.
Engineering › Sea-water System (primary cooling) › Sea Chest
Issued 19 August 2014
Resolved
A suitable hull strainer must be installed in the raw water intake. Clean/ replace the filter.
Condition: Improper/Lack of Maintenance
Due 2 September 2014
Resolved 2 September 2014
Resolution: Attended vessel and cleared above deficiency.
Engineering › Fuel Oil Service System › Filter
Issued 19 August 2014
Resolved
A suitable marine type strainer must be fitted in the fuel supply line. Replace dirty fuel filter.
Condition: Improper/Lack of Maintenance
Due 2 September 2014
Resolved 2 September 2014
Resolution: Attended vessel and cleared above deficiency.
Fire Fighting › Fixed Gas Fire Extinguishing System › Quantity of Gas
Issued 19 August 2014
Resolved
Replace extinguished pre-engineered fix gas fire extinguishing system. (1100 cubic foot FE-241)
Condition: Damaged By Earlier Event
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 20 August 2014
Resolution: Bottle was replaced and installed.
Fire Fighting › Fixed Gas Fire Extinguishing System › Operating Controls
Issued 19 August 2014
Resolved
The construction and arrangement of a vessel must allow the safe operation of the vessel in accordance with its certificate of inspection giving consideration to guards in hazardous places. Install a guard to prevent the accidental discharge of fire equipment.
Condition: Improper Installation
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 20 August 2014
Resolution: A plastic tie was placed on the pull station''s pin. An additional guard will be installed.
Fire Fighting › Structural - A Class Divisions › Machinery Spaces
Issued 19 August 2014
Resolved
A-Class bulk heads must be so installed with approved structural insulation. Repair or replace areas in the engine room where there is missing or damaged insulation.
Condition: Damaged By Earlier Event
Due 2 September 2014
Resolved 2 September 2014
Resolution: Attended vessel and cleared above deficiency.
Navigation › Piloting/Steering › US Coast Pilot
Issued 9 May 2012
Resolved
Coast Pilot missing, obtain a current edition and maintain o/b the vessel.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2012
Resolution: Current edition of the Coast Pilot obtained & maintained o/b the vessel.
Operations/Management › Drug and Alcohol Testing › Proof of Enrollment
Issued 9 May 2012
Resolved
Proof of enrollment in a drug consortium missing, provide current list as required.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2012
Resolution: Proof of enrollment into a drug consortium provided to the CG marine inspector.
Lifesaving › Lifebuoys › Markings (ship name/port)
Issued 9 May 2012
Resolved
Reflective tape on 3 ring buoys not SOLAS approved reflective tape. Replace with SOLAS approved reflective tape.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2012
Resolution: SOLAS reflective tape applied to all 3 life rings.
Accommodation/Occupational Safety › Occupational Safety › Guards for Exposed Hazards
Issued 9 May 2012
Resolved
Machinery guards for port & starboard side generators missing, provide as required.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 9 June 2012
Resolved 31 May 2012
Resolution: Machinery guards installed over the belts on both generators.
Engineering › Bilge Water Management System › Strainer
Issued 9 May 2012
Resolved
Strainers missing from bilge pick-up in starboard side sewage tank compt and port side lazarette. Replace as required.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 19 May 2012
Resolved 28 May 2012
Resolution: Strainers placed over the bilge pick-ups in the starbaord side sewage tank compartment & port side lazarette.
Engineering › Fuel Oil Service System › Filter
Issued 9 May 2012
Resolved
Diesel fuel in the Raycor Filter Bowls in the starboard side engine room. Remove diesel fuel as required.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2012
Resolution: Diesel fuel removed from the Raycor Filter bowls.
Engineering › Feedwater/Condensate Water System › Tank
Issued 9 May 2012
Resolved
Leak on coolant tank on the starboard side generator. Make permanent repairs.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 19 May 2012
Resolved 16 May 2012
Resolution: Coolant tank repaired to the satisfaction of the CG marine inspector.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 9 May 2012
Resolved
Starboard side generator didn't secure when the leads for the Fire Boy were disconnected. Make permanent repairs to ensure that the starboard generator secures when the leads to the Fire Boy are disconnected.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2012
Resolution: Starboard side generator secured when the FireBoy was activated to the satisfaction of the CG marine inspector.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Operating Controls
Issued 9 May 2012
Resolved
Port side main engine and generator didn't secure when the leads for the Fire Boy were disconnected. Make permanent repairs to ensure that the port side main engine and generator secures when the leads to the Fire Boy are disconnected.
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2012
Resolution: Port side main engine & generator secured when the FireBoy was activated to the satisfaction of the CG marine inspector.
Fire Fighting › Combustible Materials › Paints/Varnishes/Other Finishes
Issued 9 May 2012
Resolved
Mineral spirits and paints inproperly stored in the fuel tank comptarment. Remove all flammable material from space.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 10 May 2012
Resolution: All flammable material removed from the fuel tank compartment.
Engineering › Bilge Water Management System › Strainer
Issued 16 March 2010
Resolved
Strainer on bilge suction lines in starboard engine room and space aft of engine room missing or broken, replace as new.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 April 2010
Resolved 15 April 2010
Resolution: Strainer on bilge suction lines replaced as new.
Engineering › Fuel Oil Service System › Valve
Issued 16 March 2010
Resolved
Fuel shut-off handles at starboard side fuel tanks severally corroded, replace as new.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 April 2010
Resolved 15 April 2010
Resolution: Fuel shut-off valves replaced as new.
Stability › Weathertight Integrity › General
Issued 16 March 2010
Resolved
Three (3) inch coaming missing from underneath door on main deck aft, replace as new.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 16 April 2010
Resolved 15 April 2010
Resolution: Three inch coaming added to main deck door aft.
Personnel › Training › First Aid/CPR
Issued 23 February 2010
Resolved
Provide proof of First Aid/CPR training
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 16 March 2010
Resolution: Proof of First Aid/CPR training presented to the CG Marine Inspector.
Operations/Management › Drug and Alcohol Testing › Proof of Enrollment
Issued 23 February 2010
Resolved
Provide proof of enrollment in Drug and Alcohol Program for all crew.
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 16 March 2010
Resolution: Proof of Drug & Alcohol Program enrollment presented to the CG Marine Inspector.
Navigation › Piloting/Steering › Coast Guard Light List
Issued 23 February 2010
Resolved
Provide navigation publications for the area of operations.
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 16 March 2010
Resolution: Proper navigation pubs presented to the CG Marine Inspector.
Stability › Weathertight Integrity › General
Issued 23 February 2010
Resolved
Repair/Replace cracked window in Pilothouse
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 24 February 2010
Resolution: Window was replaced.
Navigation › Piloting/Steering › Compass Deviation Table
Issued 23 February 2010
Resolved
Provide Compass Deviation Table
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 16 March 2010
Resolution: Compass Deviation Table presented to the CG Marine Inspector.
Construction/Loadline › Structures › Door
Issued 23 February 2010
Resolved
Repair/Replace door handle on Pilothouse door.
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 23 February 2010
Resolution: Door handle was replaced.
Fire Fighting › Nozzles › Number
Issued 23 February 2010
Resolved
Provide required number of fire nozzles.
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 24 February 2010
Resolution: Verified proper number of fire nozzles.
Fire Fighting › Fire Hydrants › Condition
Issued 23 February 2010
Resolved
Spanner wrench is missing for each Fire Hydrant.
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 16 March 2010
Resolution: Spanner wrench purchased & o/b for the fire hydrant.
Lifesaving › Lifebuoys › Buoyant Lifeline
Issued 23 February 2010
Resolved
Line was not properly attached to Ring Buoy.
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 24 March 2010
Resolution: Verfied proper arrangement for Ring Buoy and attached line.
Engineering › Steering Gear System › Ram
Issued 23 February 2010
Resolved
Stbd Tiller Steering arm is loose (bolt).
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 24 February 2010
Resolution: Bolt was tightened and thread locked to keep from coming loose.
Fire Fighting › Structural Fire Protection - General › Structural Bulkhead Construction
Issued 23 February 2010
Resolved
Port tank room upper wire run. Remove foam and replace with fire stop or other suitable material.
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 16 March 2010
Resolution: Fire stop installed in the port tank room upper wire run.
Construction/Loadline › Penetrations › Valve Flange
Issued 23 February 2010
Resolved
Cap off discharge line in Port storage room.
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 24 February 2010
Resolution: Verified proper cap on discharge line.
Operations/Management › Bilge/Bilge System Management › Control of Oil Mixtures
Issued 23 February 2010
Resolved
Remove oil from Port Sewage Tank Space.
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 24 February 2010
Resolution: Oil was removed from space.
Operations/Management › Pollution › Control of Discharge of Sewage
Issued 23 February 2010
Resolved
Stbd Sewage tank has a leak from piping coming out the top.
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 24 February 2010
Resolution: Piping was tightened and the leaking was mitigated.
Electrical › Electrical Distribution System (service) › Panelboard
Issued 23 February 2010
Resolved
E/R panel boards were not provided with drip shields. Seal all cable penetrations IWO E/R electrical panel tops and provide gasket IWO of panel.
Action required: 705 - Other - as specified
Due 23 March 2010
Resolved 16 March 2010
Resolution: Drip shields installed under panel boards. All cable penetrations sealed.
Operations/Management › Drills/Instruction › Not Conducted
Issued 23 February 2010
Resolved
Drills need to be conducted.
Action required: 701 - Prior to carriage of passengers/cargo
Due 24 February 2010
Resolved 16 March 2010
Resolution: Drills conducted to the satisfaction of the CG Marine Inspector.
Electrical › Lighting (emergency) › Lighting Fixture
Issued 22 October 2008
Resolved
Replace/repair broken e-light fixture in starboard engineroom.
Due 5 November 2008
Resolved 12 November 2008
Documentation › Markings/Placards › Official Number (US)
Issued 22 October 2008
Resolved
Permanently mark official number
Due 5 November 2008
Resolved 12 November 2008
Construction/Loadline › Hull › Weld
Issued 11 April 2008
Resolved
In the most forward compartment overhead between frames 2 and 3 several of the longitudinal brackets have broken away from their welds, two spacer blocks between overhead frame #2 and the lower frame #2. The stbd sewage tank appears to have a crack iwo forward outboard bracket weld and appears to be leaking sewage. The inboard fwd bracket weld at the frame is also broken.
Action required: 17 - Rectify deficiencies prior to departure
Due 16 May 2008
Resolved 21 May 2008
Resolution: Completed final walk through of vessel all items noted for repair have been repaired satisfactorily.
Fire Fighting › Fire Hoses › Condition
Issued 30 June 2006
Resolved
Replace port side fire hose, hose is dripping and showing signs of dry rot.
Condition: Improper/Lack of Maintenance
Due 10 July 2006
Resolved 1 August 2006
Fire Fighting › Fire Main › Condition
Issued 30 June 2006
Resolved
Secure/repair small leak on starboard fire main, leak below hydrant on and piping next to fire pump.
Condition: Improper/Lack of Maintenance
Due 10 July 2006
Resolved 30 June 2006
Lifesaving › Lifebuoys › Serviceable
Issued 30 June 2006
Resolved
Replace worn clip with non-corrosive clip on life ring located next to pilot house.
Condition: Improper Installation
Due 10 July 2006
Resolved 1 August 2006
Deck/Cargo › Mooring/Anchoring › Anchor
Issued 30 June 2006
Resolved
Replace anchor that was removed during drydock.
Condition: Unknown
Due 5 July 2006
Resolved 1 August 2006
Deck/Cargo › Mooring/Anchoring › Winch
Issued 6 June 2006
Resolved
Port side anchor windlass winch has hose clamps. Install new hydraulic hose with appropriate hydraulic fittings.
Condition: Improper/Lack of Maintenance
Due 31 July 2006
Resolved 28 August 2007
Documentation › Certificates/Documents › Certificate of Inspection
Issued 22 June 2005
Resolved
COI was missing from vessle
Condition: Improper/Lack of Maintenance
Due 22 July 2005
Resolved 28 July 2005
Resolution: posted COI
Personnel › Certificates/Documents/Licenses › License, Mate
Issued 22 June 2005
Resolved
Vessel did not have a licensed mate or Senior deckhand designated in writing.
Condition: Improper/Lack of Maintenance
Due 22 July 2005
Resolved 31 October 2005
Resolution: Vessel reduced from Sub K to T. Deckhand not required.
Communications › Radio Communications › Radiotelephone Transceiver (2-4 MHz)
Issued 22 June 2005
Resolved
Repair or remove single sideband radio on bridge
Condition: Unknown
Due 22 July 2005
Resolved 28 July 2005
Resolution: Radio is operable.
Documentation › Markings/Placards › Lifejacket Placard
Issued 22 June 2005
Resolved
Provide proper donning placard for PFD's on board
Condition: Improper Installation
Due 22 July 2005
Resolved 28 July 2005
Resolution: corrected
Communications › Radio Communications › EPIRB
Issued 22 June 2005
Resolved
Replace Hydrostatic release on EPIRB.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 22 July 2005
Resolved 22 July 2005
Resolution: corrected.
Communications › Radio Communications › EPIRB
Issued 22 June 2005
Resolved
Provide proof of NOAA registration for EPIRB.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 22 July 2005
Resolved 28 July 2005
Resolution: corrected
Accommodation/Occupational Safety › Occupational Safety › Rubbish/Waste Materials
Issued 22 June 2005
Resolved
Replace rubber trashcans with non-combustible trashcans.
Condition: Improper Installation
Due 22 July 2005
Resolved 31 October 2005
Communications › Alarms/Indicators › Fire Alarm
Issued 22 June 2005
Resolved
Replace locks on fire alarm boxes and remove tape.
Condition: Improper Installation
Due 22 July 2005
Resolved 28 July 2005
Resolution: corrected and tested.
Documentation › Manifests/Lists › Muster List/Emergency Instructions
Issued 22 June 2005
Resolved
retain voyage plan listing passengers for all Oceans voyages.
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 28 July 2005
Resolution: corrected.
Accommodation/Occupational Safety › Occupational Safety › Tripping/Falling Hazard
Issued 22 June 2005
Resolved
Secure ladders in Engine room to deck.
Condition: Improper/Lack of Maintenance
Due 22 July 2005
Resolved 28 July 2005
Resolution: corrected
Engineering › Lubricating Oil Service System › Hose
Issued 22 June 2005
Resolved
Repair leaking hydraulic hoses on Port and Stbd generators.
Condition: Improper/Lack of Maintenance
Due 22 July 2005
Resolved 28 July 2005
Resolution: corrected.
Accommodation/Occupational Safety › Occupational Safety › Tripping/Falling Hazard
Issued 22 June 2005
Resolved
Remove hooks from engine room doors and install method for egress out of engine room.
Condition: Improper Installation
Due 22 July 2005
Resolved 28 July 2005
Resolution: corrected.
Construction/Loadline › Structures › Door
Issued 22 June 2005
Resolved
Make Aft door threshold watertight.
Condition: Improper Installation
Due 22 August 2005
Resolved 29 June 2006
Resolution: Installed threshold cover plate
Electrical › Lighting (emergency) › Lighting Fixture
Issued 22 June 2005
Resolved
Mark all emergency lighting.
Condition: Improper Installation
Due 22 July 2005
Resolved 31 October 2005
Electrical › Lighting (service) › Lighting Fixture
Issued 22 June 2005
Resolved
Replace wasted lighting fixture covers on STBD side of main deck.
Condition: Improper/Lack of Maintenance
Due 22 July 2005
Resolved 31 October 2005
Accommodation/Occupational Safety › Occupational Safety › Welding/Hot Work
Issued 22 June 2005
Resolved
Repair cracked welds on stbd aft rail door.
Condition: Improper/Lack of Maintenance
Due 22 July 2005
Resolved 28 July 2005
Resolution: corrected
Accommodation/Occupational Safety › Other Accommodation Spaces › Recreation Space
Issued 22 June 2005
Resolved
Repair broken windows on stbd side of main deck.
Condition: Damaged By Earlier Event
Due 22 July 2005
Resolved 28 July 2005
Resolution: corrected.
Accommodation/Occupational Safety › Occupational Safety › Portable Electric Equipment/Appliances
Issued 22 June 2005
Resolved
Install portable lighting at operating station and enterence to both engine rooms.
Condition: Improper Installation
Due 22 July 2005
Resolved 28 July 2005
Resolution: corrected.
Deck/Cargo › Mooring/Anchoring › Mooring Line/Hawser
Issued 22 June 2005
Resolved
Replace aft port mooring line and provide better mooring arrangement for vessel.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Resolved 28 July 2005
Resolution: corrected
Fire Fighting › Remote Fuel Shutoff › General
Issued 22 June 2005
Resolved
Repack thru-hull fittings for both remote fuel shutoffs in stbd and port engine rooms.
Condition: Improper/Lack of Maintenance
Due 22 July 2005
Resolved 28 July 2005
Resolution: corrected
Documentation › Markings/Placards › Official Number (US)
Issued 22 June 2005
Resolved
Change homeport port on stern to reflect documentation certificate.
Condition: Improper Installation
Due 22 July 2005
Resolved 28 July 2005
Resolution: corrected.
Construction/Loadline › Hull › Hull Plating
Issued 31 December 2004
Resolved
Discontinue use of vsl until it can be dry-docked to affect repairs. Vsl has cracks in the bottom plate iwo the rudder space.
Condition: Design Flaw
Action required: 701 - Prior to carriage of passengers/cargo
Resolved 3 January 2005
Accommodation/Occupational Safety › Other Accommodation Spaces › Open Deck Space
Issued 30 November 2004
Resolved
Weld cracks in the following seat backs: main cabin seats 1-3 & 5-6, upper cabin seat 5.
Condition: Improper Installation
Due 6 December 2004
Resolved 6 December 2004
Accommodation/Occupational Safety › Other Accommodation Spaces › Open Deck Space
Issued 30 November 2004
Resolved
Re-install the deck coaming for the aft cabin door.
Condition: Placed in Improper Service
Due 6 December 2004
Resolved 6 December 2004
Engineering › Sea-water System (primary cooling) › Valve
Issued 30 November 2004
Resolved
Replace the PVC plug in the non-use through hull vlv in the stbd eng rm with a brass one.
Condition: Placed in Improper Service
Due 6 December 2004
Resolved 6 December 2004
Accommodation/Occupational Safety › Washroom/Toilet
Issued 26 August 2003
Resolved
Install shower for crew's use. Vessel restricted from voyages exceeding 12 hours in any 24 hour period until completed.
LEGACY COMPONENT DESC: Shower/Bathtub
Due 26 August 2003
Resolved 29 August 2003
Accommodation/Occupational Safety › Sleeping Accommodations
Issued 26 August 2003
Resolved
Install 3 berths for crew's use. Vessel restricted from voyages exceeding 12 hours in any 24 hour period until completed. LEGACY COMPONENT DESC: Berth
Due 26 August 2003
Resolved 29 August 2003
Construction/Loadline › Hull
Issued 3 June 2003
Resolved
C/R bottom plate in way of port/stbd rudders (area repaired pursuant to LeMole Naval Architecture letter dated 30May03). Vessel restricted to rivers route no more than 1 mile from shore with passengers until corrected. LEGACY COMPONENT DESC: Bottom Plating
Action required: 701 - Prior to carriage of passengers/cargo
Due 3 July 2003
Resolved 27 June 2003
Resolution: Rcvd e-mail photographs follwing repairs & dye penetrant testing from [name withheld] (Derecktor Shipyard).
Fire Fighting › Ventilation Systems
Issued 14 May 2003
Resolved
Prove proper operation of port/stbd engineroom ventilation closures. LEGACY COMPONENT DESC: Ducts
Due 21 May 2003
Resolved 21 May 2003
Operations/Management
Issued 14 May 2003
Resolved
Provide copy of U.S. Coast Guard approved or examined plans to [name withheld] (those listed at 46 CFR 116.202). Vessel restricted to carrying no more than 150 passengers until completed & as built verification completed by [name withheld] marine inspector.
Due 14 May 2003
Resolved 29 May 2003
Engineering › Bilge Water Management System
Issued 14 May 2003
Resolved
Replace broken handles to port & stbd screw down bilge suction valves in #2 compartment. LEGACY COMPONENT DESC: Valve
Due 21 May 2003
Resolved 21 May 2003
Documentation › Safety/Response Plans/Programs
Issued 14 May 2003
Resolved
Provide copy of fire control plan to [name withheld] & post on vessel in a location that is visible & accessible to all passengers in accordance with 46 CFR 116.530. Vsl restricted to carrying no more than 150 passengers until completed & as built verification completed by [name withheld] marine inspector. LEGACY COMPONENT DESC: Fire Control Plans
Due 14 May 2003
Resolved 29 May 2003
Construction/Loadline › Hull
Issued 14 May 2003
Resolved
Properly weld 2 stiffeners stbd/1 stiffener port to collision bulkhead in compartment #2. LEGACY COMPONENT DESC: Stiffener
Due 21 May 2003
Resolved 21 May 2003
Fire Fighting › Fire Pumps
Issued 14 May 2003
Resolved
Replace cracked fire pump pressure gauge (port). LEGACY COMPONENT DESC: Pressure
Due 21 May 2003
Resolved 21 May 2003
Accommodation/Occupational Safety › Occupational Safety
Issued 14 May 2003
Resolved
Smooth edges to compartment hatches.
Due 21 May 2003
Resolved 21 May 2003
Electrical › Electrical Distribution System (service)
Issued 14 May 2003
Resolved
Install non-conductive electrical matting IWO main distribution panel. LEGACY COMPONENT DESC: Non-conducting Deck Covering
Due 21 May 2003
Resolved 21 May 2003
Construction/Loadline › Hull
Issued 14 May 2003
Resolved
Weld frame #4 to sideshell long #1 in bay 4 of compartment #3, outboard side. LEGACY COMPONENT DESC: Transverse Frame
Due 21 May 2003
Resolved 21 May 2003
Operations/Management › Drills/Instruction
Issued 5 May 2003
Resolved
Perform drills to the satisfaction of the attending marine inspector. LEGACY COMPONENT DESC: Man Overboard Recovery
Action required: 705 - Other - as specified
Due 5 May 2003
Resolved 14 May 2003
Engineering › Steering Gear System
Issued 5 May 2003
Resolved
Address leak to stbd hydraulic line. LEGACY COMPONENT DESC: Hydraulic line
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 5 May 2003
Resolved 14 May 2003
Accommodation/Occupational Safety › Occupational Safety
Issued 5 May 2003
Resolved
Place portable light at operating station. LEGACY COMPONENT DESC: Portable lighting
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 14 May 2003
Documentation › Certificates/Documents
Issued 5 May 2003
Resolved
Update marine operator's permit. LEGACY COMPONENT DESC: Marine Operators Permit
Condition: Unknown
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 14 May 2003
Electrical › Electric Supply System (service)
Issued 5 May 2003
Resolved
Install grommets as needed IWO port side support (fwd). LEGACY COMPONENT DESC: Wiring
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 21 May 2003
Navigation › Collision/Grounding Avoidance
Issued 5 May 2003
Resolved
Paint navigation light screens flat black. LEGACY COMPONENT DESC: Navigation Lights
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 14 May 2003
Accommodation/Occupational Safety › Occupational Safety
Issued 5 May 2003
Resolved
Anchor all ceiling straps for drop ceiling. LEGACY COMPONENT DESC: Drop ceiling
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 14 May 2003
Engineering › Fuel Oil Storage/Transfer System
Issued 5 May 2003
Resolved
Install 30 x 30 mesh on fuel vents. LEGACY COMPONENT DESC: Vent Pipe Flame Screen
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 5 May 2003
Resolved 21 May 2003
Construction/Loadline › Structures
Issued 5 May 2003
Resolved
Address rough edges as needed. LEGACY COMPONENT DESC: Frames/supports throughout
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 14 May 2003
Accommodation/Occupational Safety › Occupational Safety
Issued 5 May 2003
Resolved
Provide proper securing devices for hatches (when in open position). LEGACY COMPONENT DESC: Hatch securing device
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 14 May 2003
Pollution Prevention/Response › Prevention Equipment
Issued 5 May 2003
Resolved
Provide plugs for containment box at fuel fills. LEGACY COMPONENT DESC: Drains/Scuppers (means of closure)
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 14 May 2003
Electrical › Electric Supply System (service)
Issued 5 May 2003
Resolved
Address/ensure wires are properly bracketed. LEGACY COMPONENT DESC: Cable
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 14 May 2003
Accommodation/Occupational Safety › Occupational Safety
Issued 5 May 2003
Resolved
Ensure bilge spaces are properly cleaned. LEGACY COMPONENT DESC: General housekeeping
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 14 May 2003
Deck/Cargo › Mooring/Anchoring
Issued 5 May 2003
Resolved
Properly secure anchor line ensuring there is chain. LEGACY COMPONENT DESC: Anchor Rope
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 14 May 2003
Fire Fighting › Miscellaneous Items
Issued 5 May 2003
Resolved
Provide fire stops for stbd fuel tank space. LEGACY COMPONENT DESC: Fire stops
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 12 May 2003
Resolved 21 May 2003