Records from 2003 to 2025. Most recent: inspection, 17 November 2025.
Documentation record
Registered dimensions (L × B × D)117.8 ft × 30.0 ft × 12.0 ft
Registered tonnagegross 97 / net 66
ITC dimensions (L × B × D)117.8 ft × 30.0 ft × 12.0 ft
ITC tonnagegross 290 / net 87
BuilderBOCONCO SHIPBUILDING LLC · BAYOU LABATRE, AL, UNITED STATES · built 2003
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeNot recorded
Hull configurationNot recorded
Hailing portGALVESTON, TX
Trade endorsementsCoastwise, unrestricted, Registry
DocumentationValid · issued 9 January 2026 · expires 31 January 2027
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it290 - Convention (Subpart B), Gross Ton
97 - Regulatory (Subpart C or D), Gross Ton
87 - Convention (Subpart B), Net Ton
66 - Regulatory (Subpart C or D), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
A report is not offered for this hull: Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. Reports.
Inspection history · 34
17 November 2025
Deficiency Check · COI Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8262404
8 April 2025
Drydock Exam
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8108322
13 February 2024
Deficiency Check · Annual Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7864908
30 December 2023
Administrative Inspection · Deficiency Check
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7843778
14 March 2023
Drydock Exam · Internal Structural Exam · Examination of Repairs
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7650768
10 February 2023
Annual Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7635175
14 December 2021
Annual Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7367906
8 November 2021
Deficiency Check
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7347596
21 May 2021
Drydock Exam · Internal Structural Exam
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7215579
9 April 2021
Administrative Inspection
Administrative · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7171940
2 April 2021
Administrative Inspection
Administrative · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7167210
9 December 2020
COI Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 7109295
13 March 2020
Type not recorded
No type recorded · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 6929240
3 January 2020
Administrative Inspection
Administrative · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 6883342
16 December 2019
Administrative Inspection · MTSA Verification · Annual Inspection
Physical examination · Marine Safety Unit Lafayette · USCG Heartland District (CGD-H) · Activity 6875746
21 August 2018
Hull Examination · Examination of Repairs · Internal Structural Exam · Administrative Inspection · COI Inspection · MTSA Verification
Physical examination · Marine Safety Unit Lafayette · USCG Heartland District (CGD-H) · Activity 6525712
17 October 2017
Annual Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 6289649
10 August 2016
Annual Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5968512
12 May 2016
Drydock Exam · Examination of Repairs · Internal Structural Exam
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5875223
27 August 2015
Annual Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 5228680
22 October 2014
Annual Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 5009304
17 June 2014
Deficiency Check · Administrative Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 4891605
26 March 2014
Administrative Inspection
Administrative · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 4823578
6 October 2010
Examination of Repairs · Periodic Inspection · Damage Survey
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 3872445
10 December 2009
Type not recorded
No type recorded · Station Grand Isle · USCG Heartland District (CGD-H) · Activity 3650542
9 July 2008
Examination of Repairs · Administrative Inspection · COI Inspection · MTSA Verification · Hull Examination · Ballast Water Examination
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 3262549
29 November 2007
Re-Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 3159025
18 July 2006
MTSA Verification · Internal Structural Exam · Re-Inspection · Ballast Water Examination · Hull Examination
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 2717265
21 November 2005
Ballast Water Examination · MTSA Verification · Re-Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 2538529
8 October 2004
Deficiency Check
Physical examination · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 2217598
4 August 2004
Re-Inspection · MTSA Verification
Physical examination · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 2155689
22 December 2003
Security Plan Review - ASP
Administrative · Marine Safety Center (MSC) · Activity 1973270
21 November 2003
Deficiency Check
Physical examination · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 1952071
22 March 2003
Initial Certification · Initial Construction-Excluding Oversight · Deadweight Survey
Physical examination · MSO MORGAN CITY · USCG Heartland District (CGD-H) · Activity 1761042
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 17 November 2025
Resolved
Piping, valves, and fittings in a fire main system must comply with subpart G, part 182, of this chapter.
MI identified a substantial leak with the fire main on deck.
46 CFR 181.310(b)
Action required: 17 - Rectify deficiencies prior to departure
Resolved 18 November 2025
Resolution: MI attended, witnessed rectification.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 13 February 2024
Resolved
Flexible connections between cylinders and distribution piping of semi-portable or fixed carbon dioxide fire extinguishing systems and discharge hoses in semi-portable carbon dioxide fire extinguishing systems must be replaced or tested at a pressure of 6.9 MPa (1,000 psig). MI observed deterioration of 3 CO2 discharge hoses coming off the cylinders. Test or replace hoses to satisfaction of USCG. Provide report of testing or bill of installation to [email withheld].
Condition: Damaged By Earlier Event
Action required: 701 - Prior to carriage of passengers/cargo
Due 13 March 2024
Resolved 15 February 2024
Resolution: Vessel rep submitted photos of new installation
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 2 April 2021
Resolved
A fixed gas fire extinguishing system aboard a vessel must be approved by the Commandant.
Vessel's carbon dioxide fire extinguishing system is no
longer approved. Reference MSC Letter E1-2100892 for further details. Vessel must make revisions, resubmit plans for MSC approval, and make the required modifications to the installed system within 30 days.
If this cannot be achieved within the 30 day, contact MSU Texas City Marine Inspectors as soon as possible to determine an acceptable timeline and implementation plan.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 2 May 2021
Resolved 8 November 2021
Resolution: Vessel installed correct diameter piping and re-arranged nozzles according to MSC approved plans.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 9 December 2020
Resolved
Each vessel must have adequate emergency lighting fitted along the line of escape to the main deck from all passenger and crew accommodation spaces located below the main deck.
Vessel didn't have adequate lighting for the escape route from the engine room and one of the emergency lights to the aft escape wasn't operational.
46 CFR 183.432
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 April 2021
Resolution: Vessel added additional lighting to satisfy requirement.
07 - Fire Safety › N/A - No Subsystem › Remote Means of control (opening,pumps,ventilation,etc.) Machinery spaces
Issued 9 December 2020
Resolved
Remote fuel shutoff stations must be marked in clearly legible letters at least 25 millimeters high indicating purpose of the valve and direction of operation.
Vessel had emergency shutoff located just inside the engine room door. No markings were outside the space indicating the location of the emergency shutoff.
46 CFR 185.608
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 April 2021
Resolution: Vessel added markings to fuel station.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 9 December 2020
Resolved
Each entrance to a space storing carbon dioxide cylinders, a space protected by carbon dioxide systems, or any space into which carbon dioxide might migrate must be conspicuously marked.
Vessel had no carbon dioxide markings applied.
46 CFR 185.612
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 April 2021
Resolution: Vessel added CO2 markings
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 9 December 2020
Resolved
Independent fuel tanks tubular gauge glasses, if fitted to diesel fuel tanks, must be of heat resistant materials, adequately protected from mechanical damage, and provided at the tank connections with devices that will automatically close in the event of rupture of the gauge or gauge lines.
The fuel tanks tubular gauges are constructed of plastic and cannot provide certification they constructed of heat resistant material.
46 CFR 181.410(f)(7)
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 9 April 2021
Resolution: Vessel added a glass tubular gauge.
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 9 December 2020
Resolved
The master or person-in-charge must ensure that the valve is locked open at all times, except while maintenance is being performed on the extinguishing system, when the valve must be locked in the closed position.
MI witnessed vessel getting under way with the carbon dioxide extinguishing system valve in the closed position
46 CFR 182.440(a)(7)
Action required: 10 - Deficiency Rectified
Resolved 9 December 2020
Resolution: Cleared on the spot
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 9 December 2020
Resolved
After loading and prior to departure and at all other times necessary to assure the safety of the vessel, the master shall determine that the vessel complies with all applicable stability requirements in the vessel's trim and stability book, stability letter, Certificate of Inspection, and Load Line Certificate, as the case may be.
Vessel's stability letter states that the class 2 water tight door must be closed before getting underway. MI witnessed the vessel getting underway without the engine room watertight door closed.
46 CFR 185.315(a)
Action required: 10 - Deficiency Rectified
Resolved 9 December 2020
Resolution: Cleared on the spot
Navigation › Collision/Grounding Avoidance › Navigation Lights
Issued 22 October 2014
Resolved
Renew matt black paint on vessel port and starboard sidlight panals.
Condition: Placed in Improper Service
Due 24 October 2014
Resolved 23 October 2014
Resolution: Vessel rep sent pictures of new paint job.
Engineering › Generator (propulsion/auxiliary-electric) › Winding
Issued 22 October 2014
Resolved
Clean starboard generator windings to remove oil; check for any oil leaks.
Condition: Improper/Lack of Maintenance
Due 24 October 2014
Resolved 23 October 2014
Resolution: Vessel rep contracted 3rd party to clean and inspect generator windings; provided invoice and pictures.
Accommodation/Occupational Safety › Sleeping Accommodations › Area Per Person
Issued 26 March 2014
Resolved
Discovered access on sister vessel during ISE. Remove Fuel Oil access located in accomodation space by next drydock to be in compliance with 46 CFR 127.270 (g).
Condition: Improper Installation
Action required: 705 - Other - as specified
Resolved 17 June 2014
Resolution: Manhole access beneath bunk in lower accomodation space leads to a trunk/cofferdam and a second manhole providing actual access to fuel tank. Arrangement is deemed to be compliant with Subchapter L.
Communications › Alarms/Indicators › Propeller Direction Indicator
Issued 4 August 2004
Resolved
Repair shaft speed and direction indicators IAW 46 CFR 113.37.
Condition: Unknown
Action required: 705 - Other - as specified
Due 11 September 2004
Resolved 8 October 2004
Resolution: Repaired
Engineering › Fuel Oil Storage/Transfer System
Issued 22 March 2003
Resolved
Provide approved plans IWO fuel oil storage, day-tanks, and manifold IAW 46 CFR 127.110(2)(i).
Action required: 705 - Other - as specified
Due 4 October 2003
Resolved 21 November 2003
Resolution: Recieved