Records from 2011 to 2025. Most recent: inspection, 28 March 2025.
10 - Safety of Navigation › N/A - No Subsystem › Automatic Identification System (AIS)
Issued 28 March 2025
Resolved
The following vessels must have on board a properly installed, operational Coast Guard type-approved AIS Class A device: A self-propelled vessel of 65 feet or more in length, engaged in commercial service. AIS had incorrect Call Sign. Update AIS.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: AIS updated.
07 - Fire Safety › N/A - No Subsystem › Fixed fire extinguishing installation
Issued 28 March 2025
Resolved
fire-extinguishing systems, fire-detection systems must be inspected or tested at least once every 12 months. No evidence that batteries replaced on detecting unit per report. Perform all req's per report with documentation.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: Fire servicing conducted including batteries.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 March 2025
Resolved
Each towing vessel must be equipped with an industrial type first aid cabinet or kit, appropriate to the size of the crew and operating conditions. Eyewash station bottles found expired. Replace bottles.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: Eyewash bottles replaced.
02 - Structural Conditions › N/A - No Subsystem › Wheelhouse -door -window
Issued 28 March 2025
Resolved
Windows and other openings at the operating station must be of sufficient size and properly located to provide a clear field of vision for safe operation in any condition. Window broken. Replace window.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 May 2025
Resolved 30 May 2025
Resolution: Window replaced.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 28 March 2025
Resolved
The following alarms must be provided: (1) Main engine low lubricating oil pressure;(2) Main engine high cooling water temperature;(3) Auxiliary generator engine low lubricating oil pressure;(4) Auxiliary generator engine high cooling water temperature;(5) High bilge levels;(6) Low hydraulic steering fluid levels, if applicable; and(7) Low fuel level, if fitted with a day tank.Be visible and audible at each operating station. The alarm located at the operating station may be a summary alarm; if the alarm at the operating station is a summary alarm, the specific alarm condition must be indicated at the machinery or bilge location. Provide all alarms at operating stations including aft control.
Condition: Placed in Improper Service
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: Alarms installed at appropriate locations.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 28 March 2025
Resolved
Each towing vessel must perform the applicable tests in Table 143.245(b) of this section. Alarm setpoints: Twice every 5 years, with no more than 3 years elapsing since last test. Pressure vessel relief valves: Twice every 5 years, with no more than 3 years elapsing since last test. Provide evidence tests have been conducted.
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 May 2025
Resolved 30 May 2025
Resolution: Tests conducted.
10 - Safety of Navigation › N/A - No Subsystem › Bridge Navigation Watch Alarm System (BNWAS)
Issued 28 March 2025
Resolved
a towing vessel with overnight accommodations and alternating watches (shift work)must have a system to detect when its master or mate (pilot) becomes incapacitated. No system installed. Install system or provide additional person in pilothouse.
Condition: Invalid
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: Pilothouse alerter installed.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 28 March 2025
Resolved
The design of the fire detection system and its installation on the towing vessel is certified and inspected by a registered professional engineer with experience in fire-detection system design, by a technician with qualifications as a National Institute for Certification in Engineering Technologies (NICET) level IV fire alarm engineering technician, or by an authorized classification society with equivalent experience, to comply with paragraphs (a)(1) through (6) of this section. Provide certification.
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 May 2025
Resolved 30 May 2025
Resolution: Certification Provided.
05 - Radio Communications › N/A - No Subsystem › VHF radio installation
Issued 28 March 2025
Resolved
Each towing vessel must perform the applicable tests in Table 143.245(b) of this section. Charge of storage batteries if the vessel is so equipped, for emergency lighting and power. Operator unaware of test requirements. Conduct tests per above.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 1 May 2025
Resolved 30 May 2025
Resolution: Batteries tested.
10 - Safety of Navigation › N/A - No Subsystem › Charts
Issued 28 March 2025
Resolved
A towing vessel must carry adequate and up-to-date charts, maps, and nautical publications for the intended voyage. Electronic charts not updated. Update charts regularly.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: Electronic charts updated.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 28 March 2025
Resolved
The owner, managing operator, or master of a towing vessel must ensure that the vessel's lifesaving and fire suppression and detection equipment is in good working order. Fire extinguisher bracket found broken near "forepeak" space. Replace bracket.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: bracket replaced.
11 - Life Saving Appliances › N/A - No Subsystem › On board training and instructions
Issued 28 March 2025
Resolved
The master of a towing vessel must ensure that drills are conducted and instructions are given to ensure that all crewmembers are capable of performing the duties expected of them during emergencies. Emergency instructions must be updated to new operators prescription or followed as written.
Condition: Invalid
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: emergency procedures updated.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 28 March 2025
Resolved
A record of the type, size, and service of each towline, face wire, and spring line, used to make the towing vessel fast to her tow, must be available to the Coast Guard or third-party auditor for review. No towing gear record provided. Provide record.
Condition: Invalid
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: Towing gear record provided.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 28 March 2025
Resolved
Each towing vessel must be equipped with a means to detect smoke in the berthing spaces and lounges that alerts individuals in those spaces. This may be accomplished by an installed detection system, or by using individual battery-operated detectors meeting UL
217. Detection systems or individual detectors must be
kept operational at all times when the crew is onboard. No smoke detection provided in main deck berthing. Crew unable to test per manufacturer instructions function of fire detection in other spaces including lower "forepeak" berthing. Provide detectors and test units per manufacturer instructions in presence of Marine Inspector.
Condition: Invalid
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: smoke detectors installed and tested.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 28 March 2025
Resolved
Where practicable and except as provided in § 144.515, each space where crew may be quartered or normally employed must have at least two means of escape. Berthing furniture, i.e. bunks, in forepeak, blocks 2nd means of escape (scuttles and hatch). Provide 2nd means of escape.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: 2nd means of escape made readily accessible
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 28 March 2025
Resolved
Paints, coatings, or other flammable or combustible products onboard a towing vessel must be stored in a designated storage room or cabinet when not in use. Multiple highly flammable portable torches found throughout accommodation spaces. Store all flammables in approved locker/space.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: flammable items stored in designated lockers.
07 - Fire Safety › N/A - No Subsystem › Evaluation of crew performance (fire drills)
Issued 28 March 2025
Resolved
The master of a towing vessel must ensure that each crew
member participates in fire fighting drills and receives
instructions at least once each month. Master and
deckhands were unfamiliar on use of provided fire
extinguishing systems. Train crew on installed/portable/semi portable systems and in accordance with revised emergency instructions. Demonstrate proficiency to USCG.
Condition: Invalid
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: Crew re-trained and demonstrated profiency with fire supression devices.
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 28 March 2025
Resolved
The owner, managing operator, or master of a towing vessel must ensure that the vessel's lifesaving and fire suppression and detection equipment complies with the applicable requirements of parts 141 and 142 of this subchapter and is in good working order. Liferaft rigged so as to not deploy automatically in float free arrangement, repeating improper rigging on other inspected vsls owned and operated by company. Train crew on proper rigging of liferaft.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: Crew trained on proper rigging of float free assembly and liferaft found in satisfactory setup condition.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 28 March 2025
Resolved
Each lifebuoy on a towing vessel must: Be marked in block capital letters with the name of the vessel. At least one lifebuoy must have a lifeline, secured around the body of the lifebuoy. At least two lifebuoys on a towing vessel greater than 26 feet must be fitted with a floating electric water light approved under approval series 161.010 or 161.110. 01 lifebuoy starboard side, outside pilothouse found with lifeline not around buoy,
electric light on deck without bracket, stenciling
fading, and reflective tape chipped/faded. Repair all.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: lifebuoy light, stenciling, bracket repaired/replaced. All found satisfactory.
04 - Emergency Systems › N/A - No Subsystem › Shipboard Marine Pollution emergency operations
Issued 28 March 2025
Resolved
Piping for flammable or combustible liquid, seawater cooling, or firefighting systems must be fitted with isolation valves that are clearly marked by labeling or color coding that enables the crew to identify its function. Fuel transfer pump shutdown incorrectly identified as fire extinguishing activation point. Provide fuel piping diagram and label essential systems and controls.
Condition: Invalid
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: Labels and diagrams provided.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 28 March 2025
Resolved
Each towing vessel must be maintained and operated so as to minimize fire hazards. Temporary fiberboard panels installed overhead on ladderway entering engine room near fidley space. Remove all combustible materials from engine room.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 1 April 2025
Resolved 30 May 2025
Resolution: Panels removed.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 30 October 2024
Resolved
Shaft bearing was inspected with wear readings indicating that it was worn past the manufacturer's recommended service life and must be replaced.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 November 2024
Resolved 15 November 2024
Resolution: Shaft bearing was replaced with approved material, and the deficiency is cleared.
02 - Structural Conditions › N/A - No Subsystem › Hull damage impairing seaworthiness
Issued 30 October 2024
Resolved
The Marine Inspector must examine the hull and all appendages for damage, fractures, pitting, wastage, or improper repair. The following items were noted during the latest DDX and must be corrected before resuming commercial operations.
1) overhead structure in the forepeak is excessively wasted and must be cropped & renewed.
2) Structure near the bottom of the chain locker is wasted and must be cropped and renewed.
3) vertical frame in starboard aft ballast tank is wasted and seperated from the hull and must be cropped and renewed.
Action required: 705 - Other - as specified
Due 15 November 2024
Resolved 4 March 2025
Resolution: Examined internal framing repairs, all found satisfactory.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Other (load lines)
Issued 30 October 2024
Resolved
The reach-rod for the forepeak is disconnected from the valve servicing the space's bilge. The owner must prove proper operation prior to departure.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 November 2024
Resolved 15 November 2024
Resolution: Reach-rod and valve function as designed, and the deficiency is cleared.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Manholes/flush scuttles
Issued 30 October 2024
Resolved
Closure devices must be provided for hull penetrations to prevent water intrusion. The hatch over the steering gear space is wasted and must be replaced.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 15 November 2024
Resolved 15 November 2024
Resolution: A new hatch was installed, and the deficiency is cleared.
02 - Structural Conditions › N/A - No Subsystem › Hull damage impairing seaworthiness
Issued 30 October 2024
Resolved
A vessel must maintain adequate structural integrity, so as not to be questioned by the OCMI or TPO. Multiple areas on the tug's hull were identified as having washed out weld, which must be gouged and filled, to the satisfaction of the attending Marine Inspector.
Action required: 17 - Rectify deficiencies prior to departure
Due 15 November 2024
Resolved 15 November 2024
Resolution: All areas were satisfactorily addressed, and the deficiency is cleared.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 11 August 2023
Resolved
A towing vessel 79 feet or more in length must carry four lifebuoys that are at least 24" in diameter. One of the vessels life buoys was deteriorated and in need of replacement.
46CFR141.360(a)(3)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 25 August 2023
Resolved 30 August 2023
Resolution: Vessel replaced the bad lifering.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 11 August 2023
Resolved
At least two lifebuoys on a towing vessel greater than 26 feet must be fitted with a floating electric water light. The lights attached were not working due to expired batteries.
46CFR141.460(c)(2)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 August 2023
Resolved 30 August 2023
Resolution: Vessel replaced the ring-lights
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 11 August 2023
Resolved
Electrical systems and equipment must function properly and minimize system failures and fire and shock hazards. Several dead ended wires were identified throughout the vessel that must be properly secured.
46CFR143.400(a)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 14 August 2023
Resolved 30 August 2023
Resolution: Vessel removed the dead-end wires.
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 11 August 2023
Resolved
Each liferaft must have a painter system providing a connection between the vessel and the liferaft, and each liferaft must be arranged for float-free launching. The liferaft's painter was not properly secured to the vessels float free arraignment.
46CFR141.310
46CFR199.130(6) & (7)
Action required: 10 - Deficiency Rectified
Due 11 August 2023
Resolved 11 August 2023
Resolution: Vessel operator properly conected the liferaft to the weak link.
01 - Certificates & Documentation › 013 - Documents › Log-books/compulsory entries
Issued 11 August 2023
Resolved
The following list of items must be recorded in the TVR (logbook)
(1) Personnel records, in accordance with § 140.400;
(2) Safety orientation, in accordance with § 140.410; (3) Record of drills and instruction, in accordance with § 140.420;
(4) Examinations and tests, in accordance with § 140.615;
(5) Operative navigational safety equipment, in accordance with § 140.620;
(6) Navigation assessment, in accordance with § 140.635; (7) Navigation safety training, in accordance with § 140.645;
(8) Oil residue discharges and disposals, in accordance with § 140.655;
(9) Record of inspection of towing gear, in accordance with § 140.820; and
(10) Fire-detection and fixed fire-extinguishing, in accordance with § 142.240.
Vessel was not recording items properly in the TVR. Conducted some training with the vessel operator to start properly recording the items needed.
46CFR140.915(a)
Action required: 10 - Deficiency Rectified
Due 11 August 2023
Resolved 11 August 2023
Resolution: Conducted some training with the vessel operator on what needs to be logged in the TVR, and it needs to be done going forward.
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 1 February 2022
Resolved
Towing vessels must undergo an annual inspection within 3 months before or after the COI anniversary date. The vessel's anniversary date is 14Jul and the vessel did not conduct an annual inspection before 14Oct2021. The vessel's COI has been revoked and the vessel must conduct a COI renewal inspection prior to operating commercially in the spring of 2022.
Action required: 705 - Other - as specified
Due 15 April 2022
Resolved 9 May 2022
Resolution: Completed COI
11 - Life Saving Appliances › N/A - No Subsystem › Distress flares
Issued 29 April 2020
Resolved
Distress flares expired. 46CFR141.370
Action required: 17 - Rectify deficiencies prior to departure
Due 29 April 2020
Resolved 14 July 2020
Resolution: Verified new flares on board.
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 29 April 2020
Resolved
First aid contents expired. 46CFR140.435
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2020
Resolved 14 July 2020
Resolution: Verified new first aid kit.
10 - Safety of Navigation › N/A - No Subsystem › Lights, shapes, sound-signals
Issued 29 April 2020
Resolved
Fix or replace in-operable nav. lights IAW 33CFR084.
46CFR140.72
Action required: 17 - Rectify deficiencies prior to departure
Due 29 April 2020
Resolved 14 July 2020
Resolution: Verified proper operation of nav lights.
08 - Alarms › N/A - No Subsystem › Other (alarms)
Issued 29 April 2020
Resolved
Fix or replace bilge floats or alarms in engine room, steering compartment, and fwd berthing. 46CFR143.230(a)(5)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2020
Resolved 14 July 2020
Resolution: Witnessed operation of bilge alarms.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 29 April 2020
Resolved
Open control and start air UPV's for internal innspection and replace all safety relief valves. 46CFR143.300
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2020
Resolved 14 July 2020
Resolution: Internal inspection of UPV's conducted.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 29 April 2020
Resolved
Stencil name of vessel on lifejackets and designate stowage location. 46CFR141.340
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2020
Resolved 14 July 2020
Resolution: Verified life jackets have been stenciled and have designated stowage location.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 29 April 2020
Resolved
Provide required amount of liferings (04 total) and correct attachments. 02 with lights, 01 with line, 01 other. 46CFR141.360(a)(3), 46CFR141.360(c)(1)
Action required: 17 - Rectify deficiencies prior to departure
Due 29 April 2020
Resolved 14 July 2020
Resolution: Verifed proper arrangement of life rings.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 29 April 2020
Resolved
Label remote fuel shut off. 46CFR143.260(e)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2020
Resolved 14 July 2020
Resolution: Verified label.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 29 April 2020
Resolved
Remove dead end cables/wires or place ends in suitable enclosure. 46CFR143.400
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2020
Resolved 14 July 2020
Resolution: Dead end cables removed.
09 - Working and Living Conditions › 091 - Living Conditions › Lighting (Accommodation)
Issued 29 April 2020
Resolved
Fix in-operable lighting throughout vessel berthing areas & machinery spaces. 46CFR143.410(a)
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2020
Resolved 14 July 2020
Resolution: Verified lighting in operational.
11 - Life Saving Appliances › N/A - No Subsystem › Buoyant apparatus
Issued 29 April 2020
Resolved
Service IBA or replace with suitably sized skiff as allowed by 46CFR141.330. 46CFR141.305
Action required: 17 - Rectify deficiencies prior to departure
Due 29 April 2020
Resolved 14 July 2020
Resolution: Verified 6 man life raft on board.
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 29 April 2020
Resolved
Have EPIRB serviced or remove from vessel (not required).
46CFR141.380
Action required: 17 - Rectify deficiencies prior to departure
Due 29 April 2020
Resolved 14 July 2020
Resolution: EPIRB removed.
08 - Alarms › N/A - No Subsystem › General alarm
Issued 29 April 2020
Resolved
Fix or replace general alarm bells outside of port and stbd berthing areas and label (when alarm sounds go to your station), or prove alternate means of alerting crew with the use of P/A system. 46CFR143.235
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2020
Resolved 14 July 2020
Resolution: Verified operation of General Alarm.
08 - Alarms › N/A - No Subsystem › General alarm
Issued 29 April 2020
Resolved
Place red flashing light for general alarm in engine room so crew can be alerted visually over high noise levels. 46CFR143.235
Action required: 50 - Rectify deficiencies w/in 30 days
Due 29 May 2020
Resolved 14 July 2020
Resolution: Audible alarm afequate for noise level in engine room with machinery running.
10 - Safety of Navigation › N/A - No Subsystem › Automatic Identification System (AIS)
Issued 7 September 2018
Resolved
The vessel is currently broadcasting (1) Improper Call Sign, (2) Improper IMO Number,(3) Improper Beam and Length
Condition: Invalid
Action required: 705 - Other - as specified
Due 7 October 2018
Resolved 29 April 2020
Fire Fighting › Fire Pumps › Arrangement
Issued 26 May 2011
Resolved
Provide means to start fire pump outside of engine space
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 15 July 2011
Resolved 10 November 2011
Resolution: Remote switch installed as required
Fire Fighting › Fixed Gas Fire Extinguishing System › Tanks
Issued 26 May 2011
Resolved
Provide either a fixed extinguishing system for engine room or a semi portable type V extinguishing system.
Condition: Improper/Lack of Maintenance
Action required: 705 - Other - as specified
Due 15 July 2011
Resolved 11 November 2011
Resolution: Type V semi portable CO2 extinguishing system installed as required