CARNIVAL MIRACLE

Built
2004
Last inspected
24 July 2026
Documentation
No record in the NVDC file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 2016.

Inspection record

Last inspected 24 July 2026
…with no type recorded20
Operational controls None recorded without a removal date
Years with a record 11 calendar years (2016–2026)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

9237357
667935
Flag
PANAMA
Maury page id
psix-667935

Documentation record

Tonnage as PSIX records it85942 - Convention (Subpart B), Gross Ton
53626 - Convention (Subpart B), Net Ton
8409 - Dead Weight, Metric Ton
46416 - Displacement, Metric Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Professional
The full record for this vessel

Behind this panel: 66 inspections, each with its date, unit and type; 32 deficiencies with the resolution recorded against each; operational controls, none recorded without a removal date; no tow-unit appearances recorded; no other recorded names; no NVDC documentation record for this Official Number. Every line is a record the Coast Guard wrote; the counts above are the same counts as in the summary, and they are free.

Professional is $39 a month or $299 a year, or $19.99 a month locked for life at the founding rate, for the first 200 subscribers. It unlocks every detail section on every vessel page, fleet watch tied to your account, and ownership records on request. Already a subscriber? Sign in.

Maury does not score, rate or grade vessels, at any price.

Vessel history report
Every record for this hull, in one document — $299

Every recorded inspection, 1972 to 2026, in one chronology · every deficiency, with system, dates and resolution · operational controls imposed and removed · every name this hull has been recorded under · the vessels it was inspected alongside, and when · how its record compares with hulls of similar age and size, as a fact about the population and never a judgement about this vessel.

Read one first, in full: a forty-year chronology · a hull that changed operators four times · the sparse case, shown as an example, not for sale.

This report is in development and is not for sale yet. There is no date, and nothing is charged. Leave an email and we will tell you when it exists, once.

Inspection history · 66

24 July 2026 Administrative Inspection
Administrative · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 8445669
13 July 2026 Administrative Inspection
Administrative · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 8437007
15 June 2026 Deficiency Check · PSC B
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 8403080
11 June 2026 Administrative Inspection
Administrative · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 8403527
5 June 2026 Administrative Inspection
Administrative · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 8392796
15 May 2026 Administrative Inspection
Administrative · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 8376390
11 May 2026 PSC B
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 8371275
30 April 2026 Administrative Inspection
Administrative · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 8358950
22 April 2026 Administrative Inspection
Administrative · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 8356738
14 April 2026 Administrative Inspection
Administrative · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 8349723
14 March 2026 Deficiency Check
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 8326670
8 March 2026 PSC A · COC-CVE Annual
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 8319663
12 January 2026 Administrative Inspection
Administrative · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 8295341
22 November 2025 PSC B · COC-CVE Quarterly
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 8270992
29 March 2025 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 8101732
13 March 2025 PSC A · COC-CVE Annual
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8090442
3 March 2025 Deficiency Check
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8087545
27 December 2024 PSC B · COC-CVE Quarterly
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8051131
29 October 2024 Administrative Inspection
Administrative · Sector Key West · USCG Southeast District (CGD-SE) · Activity 8026288
28 June 2024 PSC A · COC-CVE Annual · Deficiency Check · Ballast Water Examination
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7941606
9 April 2024 Administrative Inspection
Administrative · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7893106
12 January 2024 COC-CVE Quarterly · PSC B
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7848282
8 January 2023 COC-CVE Quarterly · PSC B
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7618027
13 November 2022 Administrative Inspection
Administrative · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 7593559
28 October 2022 Type not recorded
No type recorded · Marine Safety Unit Portland OR · USCG Northwest District (CGD-NW) · Activity 7587482
20 September 2022 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7580022
13 September 2022 Administrative Inspection
Administrative · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 7562995
18 August 2022 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7538204
19 July 2022 COC-CVE Annual · Ballast Water Examination · PSC A
Physical examination · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7508944
17 May 2022 Type not recorded
No type recorded · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7568954
4 May 2022 Administrative Inspection · Deficiency Check
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7444088
20 February 2022 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7426121
23 January 2022 COC-CVE Quarterly · PSC B
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7384170
11 December 2021 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7592496
18 November 2021 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7431282
13 October 2021 Deficiency Check
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7331546
20 September 2021 Administrative Inspection
Administrative · Marine Safety Detachment Ketchikan · USCG Arctic District (CGD-A) · Activity 7316810
31 August 2021 Type not recorded
No type recorded · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 7302161
13 August 2021 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7336726
4 August 2021 Type not recorded
No type recorded · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 7283544
29 July 2021 Type not recorded
No type recorded · Sector Southeast Alaska · USCG Arctic District (CGD-A) · Activity 7282006
21 July 2021 PSC B · COC-CVE Annual
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7242816
4 April 2020 Administrative Inspection
Administrative · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6935652
14 February 2020 Deficiency Check · Administrative Inspection
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6909607
6 January 2020 COC-CVE Annual · ISPS III Exam · Ballast Water Examination
Physical examination · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6879645
2 October 2019 Type not recorded
No type recorded · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6830026
28 July 2019 ISPS III Exam · COC-CVE Quarterly · Ballast Water Examination
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6755322
13 January 2019 ISPS II Exam · Ballast Water Examination · COC-CVE Annual
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6606534
2 December 2018 Type not recorded
No type recorded · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6592848
18 November 2018 Bulk Liquid Transfer Monitor
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6582740
22 July 2018 Type not recorded
No type recorded · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6489203
8 July 2018 ISPS II Exam · Ballast Water Examination · COC-CVE Quarterly
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6467663
6 May 2018 In-Service Inspection
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6407964
17 March 2018 Type not recorded
No type recorded · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6385350
10 March 2018 Type not recorded
No type recorded · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6370247
13 January 2018 COC-CVE Annual · ISPS II Exam · Ballast Water Examination
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6346579
15 September 2017 Deficiency Check
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6267801
12 August 2017 ISPS II Exam · COC-CVE Quarterly · Ballast Water Examination
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6240776
12 February 2017 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6092645
4 February 2017 Ballast Water Examination · ISPS II Exam · COC-CVE Annual
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6076953
6 December 2016 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6053660
2 October 2016 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 6014830
10 September 2016 In-Service Inspection
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 5997053
8 September 2016 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 5995321
30 July 2016 ISPS II Exam · COC-CVE Quarterly
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 5959290
31 January 2016 COC-CVE Annual · ISPS II Exam · Ballast Water Examination
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 5801413

Deficiency record · 32

11 - Life Saving Appliances › N/A - No Subsystem › Operational readiness of lifesaving appliances
Issued 11 May 2026 Resolved
Before the ship leaves port and at all times during the voyage, all life-saving appliances shall be in working order and ready for immediate use. PSCO observed life boat #11 did not start.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Due 11 May 2026
Resolved 11 May 2026
Resolution: Lifeboat was capable of starting prior to inspectors departing vessel.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 11 May 2026 Resolved
Fire doors in main vertical zone bulkheads and stairway enclosures shall satisfy the following requirements: The doors shall be self-closing and be capable of closing against an angle of inclination of up to 35 degrees opposing closure. PSCO observed FSD 4.5.01 inop and in partially open position.
Condition: Placed in Improper Service
Action required: 50 - Rectify deficiencies w/in 30 days
Due 11 June 2026
Resolved 16 June 2026
Resolution: Attended vessel and cleared.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 11 May 2026 Resolved
Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this regulation, it shall be treated as a space within the relevant catergory having the most stringent boundary requirements. PSCO observed storage of combustible materials in technical spaces behind FSD 1.4.02 near cabin 4177 and 1156 and inside fire sation 6.4.1.
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Due 11 May 2026
Resolved 11 May 2026
Resolution: Crew removed materials from technical space
09 - Working and Living Conditions › 092 - Working Conditions › Other (accident prevention)
Issued 8 March 2026 Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons onboard. PSCO observed a contorted hand hold on the ladder leading to lifeboat #16. 74SOLAS(20) I/11(a)
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Due 22 March 2026
Resolved 14 March 2026
Resolution: Received class report attesting to satisfactory repair of hand hold.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 8 March 2026 Resolved
Where the contents and use of a space are such that there is a doubt as to its classification for the purpose of this regulation, it shall be treated as a space within the relevant category having the most stringent boundary requirements. PSCO observed improper storage of combustible materials in the Burger Joint Galley in the Atrium Smoke Extraction Remote Station and storage behind the lining on deck 7 main vertical zone 5 in the cable locker across cabin #7176. 74 SOLAS 01 II-2/26.2.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 March 2026
Resolution: Corrected during exam.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 8 March 2026 Resolved
Electrical installations shall be such that electrical services for safety will be ensured under various emergency conditions. PSCO observed emergency lighting junction boxes with failed gland installations on liferaft crane #8 and liferaft #20. 74 SOLAS 04 II-1/40.1.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 March 2026
Resolution: Corrected during exam.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 8 March 2026 Resolved
The construction of all doors and door frames in "A'' class divisions, with the means of securing them when closed, shall provide resistance to fire as well as to the passage of smoke and flame, as far as practicable, equivalent to that of the bulkheads in which the doors are situated. PSCO observed a double-leaf fire screen door bounding the starboard sea chest in the main vertical zone #3, at the tank top, adjacent to FSD 3.03 unable to close and latch completely. 74 SOLAS 01 II-2/30.2
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 March 2026
Resolution: Corrected during exam.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 8 March 2026 Resolved
All life-saving appliances and arrangements shall comply with the applicable requirements of the Code. PSCO observed a navigation light on lifeboat #3, starboard side,unable to energize. 74 SOLAS 20 III/34
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 March 2026
Resolution: Corrected during exam.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 8 March 2026 Resolved
All life-saving appliances and arrangements shall comply with the applicable requirements of the Code. PSCO observed a missing handle for the fuel shutoff on lifeboat #3 starboard side. 74 SOLAS 20 III/34
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 8 March 2026
Resolution: Corrected during exam.
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 13 March 2025 Resolved
Where "A" class divisions are penetrated for the passage of electric cables, pipes, trunks, ducts, etc., or for girders, beams or other structural members, arrangements shall be made to ensure that the fire resistance is not impaired. PSCO observed multiple cable penetrations altered on main vertical zone 5 electrical locker. 74 SOLAS 01 II-2/18.1.1 50ac
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 13 April 2025
Resolved 22 November 2025
Resolution: PSCO observed satisfactory repair.
07 - Fire Safety › N/A - No Subsystem › Means of escape
Issued 13 March 2025 Resolved
Doorways and corridors and intermediate landings included in the means of escape shall be sized in the same manner as stairways, shall not be less than 900mm in clear width, the minimum clear width shall be increased by 10mm for every one person provided for in excess of 90 persons. PSCO observed escape route door obstructed by multiple curtains on deck 10 starboard side in club O2. 74 SOLAS 01 II-2/28.1.5.3 10ac
Condition: Design Flaw
Action required: 10 - Deficiency Rectified
Resolved 13 March 2025
Resolution: Curtains were removed.
11 - Life Saving Appliances › N/A - No Subsystem › On board training and instructions
Issued 27 December 2024 Resolved
On-board training in the use of the ship's life-saving appliances, including survival craft equipment, and in the use of the ship's fire-extinguishing appliances shall be given as soon as possible but not later than two weeks after a crew member joins the ship. PSCO observed secondary coxswain on lifeboat 1 and coxswain and motorman on lifeboat 3 unfamiliar with starting and emergency steering procedures. 74 SOLAS 20 III/19.4.1
Action required: 10 - Deficiency Rectified
Due 10 January 2025
Resolved 27 December 2024
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 28 June 2024 Resolved
74 SOLAS 01 II-2/26.2.2 16a.c. Where the contents and use of a space are such that there is doubt as to its classification for the purpose of this regulation, it shall be treated as a space within the relevant category having the most stringent boundary requirements. PSCO observed storage of combustible materials including cardboard boxes, plastic bins, spare lights, etc. in category (10) A/C machinery space on deck 1 IVO F.S.D. 1.3.14 and in category (10) lift machinery space IVO F.S.D. 1.3.12.
Condition: Improper/Lack of Maintenance
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 29 June 2024
Resolution: Received class report from DNV attesting to the removal of combustible materials from the spaces identified.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 19 July 2022 Resolved
A door designed to reopen upon contacting an object in its path shall reopen not more than 1m from the point of contact. FSD 3.5.12 was tested locally and did not reopen upon contact. SOLAS 01 II-2/30.4.11
Action required: 10 - Deficiency Rectified
Due 19 July 2022
Resolved 19 July 2022
Resolution: Door was adjusted and repaired.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 19 July 2022 Resolved
Fire doors in main vertical zone bulkheads, galley boundaries and stiarway enclosures shall satisfy the following requirements: the approximate time of closure for hinged fire doors shall be no more than 40s and no less than 10s from the beginning of their movement with the ship in upright position. FSD 9.3.26, in a galley boundary, closed in less than 5s. SOLAS 01 II-2/30.4.2
Action required: 10 - Deficiency Rectified
Due 19 July 2022
Resolved 19 July 2022
Resolution: Door was adjusted.
09 - Working and Living Conditions › 091 - Living Conditions › Other (crew and accommodation)
Issued 19 July 2022 Resolved
The condition of the ship and its equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all respects will remain fit to proceed to sea without danger to the ship or persons on board. Black water drain pipe in vicinity of FSD A.5.01 had a duct tape patch covering a hole drilled in pipe by crew for maintenance. SOLAS 20 I/11(a)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 2 August 2022
Resolved 29 July 2022
Resolution: Repair completed to the satisfaction of class.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 19 July 2022 Resolved
Electrical installations shall be such that the safety of passengers, crew and ship from electrical hazards will be ensured. Light cover was missing in fire fighting station 6. SOLAS 04 II-1/40.1.3
Action required: 10 - Deficiency Rectified
Due 19 July 2022
Resolved 19 July 2022
Resolution: New cover installed on light.
11 - Life Saving Appliances › N/A - No Subsystem › Embarkation arrangement survival craft
Issued 19 July 2022 Resolved
During preparation and launching, the survival craft, its launching appliance and the area of the water into which is to be launched shall be adequately illuminated. 01 embarkation light on the port side was extinguished.
Action required: 10 - Deficiency Rectified
Due 19 July 2022
Resolved 19 July 2022
Resolution: Light was repaired and found functional.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 19 July 2022 Resolved
Any required fixed fire detection and fire alarm system with manually operated call points shall be capable of immediate operation at all times. One manual call point on A-Deck (#174-24) and one manual call point on Deck 2 (#220-25) did not activate upon testing. SOLAS 01 II-2/13.1.1
Action required: 10 - Deficiency Rectified
Due 19 July 2022
Resolved 19 July 2022
Resolution: Call points were repaired.
14 - Pollution Prevention › 141 - MARPOL Annex I › Control of discharge
Issued 13 October 2021 Resolved
Subject to the provisions of regulation 4 of this Annex and paragraphs 2,3, and 6 of this regulation, any discharge into the sea of oil or oily mixtures from ships shall be prohibited. Vessel reported five liters of oil missing from starboard fin stabilizer head tank. MARPOL 1/15.1
Action required: 10 - Deficiency Rectified
Due 26 October 2021
Resolved 4 May 2022
Resolution: Vessel has been issued a condition of class (AI-S-044) to rectify at next drydock (FEB, 2023), Special Note added to vessel profile.
11 - Life Saving Appliances › N/A - No Subsystem › Lifeboats
Issued 21 July 2021 Resolved
Passenger ships engaged on short international voyages shall carry: partially or totally enclosed lifeboats complying with the requirements of section 4.5 or 4.6 of the code of such aggregate capacity as will accommodate at least 30% of the total number of persons on board. PSCO discovered fracture on the rudder post on the #17 lifeboat.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 21 August 2021
Resolved 24 August 2021
Resolution: Vessel submitted satisfactory class report contesting that the rudder was replaced and tested out of the water.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 21 July 2021 Resolved
Fire drills should be planned in such a way that due consideration is given to regular practice in the various emergencies that may occur depending on the type of ships and the cargo. In the opinion of the PSCO, the fire drill lacked vital communication and effective boundary cooling. Vessel conducted subsequent fire drill in machinery space and was performed satisfactory..
Action required: 10 - Deficiency Rectified
Due 22 July 2021
Resolved 22 July 2021
Resolution: Vessel conducted subsequent fire drill in machinery space and was performed satisfactory.
04 - Emergency Systems › N/A - No Subsystem › Emergency source of power - Emergency generator
Issued 6 January 2020 Resolved
A SELF CONTAINED EMERGENCY SOURCE OF ELECTRICAL POWER SHALL BE PROVIDED. THE VESSELS EMERGENCY GENERATOR IS EQUIPPED WITH ELECTRICAL AND PNEUMATIC STARTING CAPABILITIES. THE PNEUMATIC STARTING WAS INOPERABLEWHEN TESTED AND TOOK SEVERAL HOURS TO REPAIR. SOLAS 2001 CONS. CH II-1 REG. 42.1.1
Action required: 10 - Deficiency Rectified
Resolved 6 January 2020
Resolution: WITNESSED SATISFACTORY REPAIR AND STARTING OF PNEUMATIC STARTING METHOD
10 - Safety of Navigation › N/A - No Subsystem › Record of drills and steering gear tests
Issued 6 January 2020 Resolved
NO PERSON MAY CAUSE A VESSEL TO ENTER INTO OR GET UNDERWAYON NAVIGABLE WATERS OF THE UNITED STATES UNLESS NO MORE THAN 12 HOURS BEFORE ENTERING OR GETTING UNDERWAY. TESTS AS REQUIRED BY 33 CFR 164.25 WERE NOT CONDUCTED PRIOR TO ENTERING U.S. WATERS. 33 CFR 164.25
Action required: 10 - Deficiency Rectified
Resolved 6 January 2020
Resolution: MASTER INFORMED OF REQUIREMENTS
04 - Emergency Systems › N/A - No Subsystem › Low level lighting in corridors
Issued 6 January 2020 Resolved
MEANS OF ESCAPE SHALL BE MARKED BY LIGHTING OR PHOTO ILLUMINESCENT STRIPS TO IDENTIFY ROUTESOF ESCAPE. LOW LOCATION LIGHTINGBEHIND ALCHEMY BAR AND DECK A BY MAIN LAUNDRY WAS FOUND DAMAGED. SOLAS 2004 CONS. CH. II-2 REG. 13.2.5.1
Action required: 10 - Deficiency Rectified
Due 6 January 2020
Resolved 6 January 2020
Resolution: Corrected on the Spot.
09 - Working and Living Conditions › 092 - Working Conditions › Obstruction/slipping, etc.
Issued 6 January 2020 Resolved
AT STAIRWAY ENCLOSURE PERIMETERS, ONLY LOCKER OF NON COMBUSTIBLE MATERIAL PROVIDING STORAGE FOR NON HAZARDOUS SAFETY EQUIOPMENT ARE PERMITTED. THE FOLLOWING STAIRWAY ENCLOSURES WERE FOUND WITH EXCESSIVE STORAGE: 1)E/R ESCAPE LADDER TO A DECK FWD, 2)E/R ESCAPE STAIRS TO I-95 STBD SIDE BY TENDER EMBARKATION STATIONS, 3)AT ELEVATOR STATION ON DECK 3AT MUSTER STATION CHIGH CHAIRSAND EMPORIUM STACKED, 4)EQUIPMENT STORED IN FRONT OF PIT ESCAPEAT STAGE. SOLAS 04 CONS. CH. II-2 REG. 3.1
Action required: 10 - Deficiency Rectified
Due 6 January 2020
Resolved 6 January 2020
Resolution: Corrected prior to departure from vessel.
07 - Fire Safety › N/A - No Subsystem › Fire prevention structural integrity
Issued 6 January 2020 Resolved
THE USE OF COMBUSTIBLE MATERIALS SHALL BE RESTRICTED TO LIMIT FIREGROWTH POTENTIAL. EXCESSIVE COMBUSTIBLE MATERIAL STORED BEHIND STAGE ON 2 DECKS. UNWASHED SHEETS FOUND PILED UP BEHIND WASHER MACHINESAND ON TOP OF CORROSIVE AND OXIDIZING MATERIAL. PYROTECHNICS WERE FOUND STORED OUTSIDE OF THE PROTECHNICS LOCKER. SOLAS 04 CONS. CH. II-2 REG. 3.1
Action required: 16 - Rectify deficiencies w/in 14 days
Due 21 January 2020
Resolved 14 February 2020
Resolution: See documents for Class Report
07 - Fire Safety › N/A - No Subsystem › Division - decks, bulkheads and penetrations
Issued 6 January 2020 Resolved
FIRE INTEGRITY OF DIVISIONS SHALL BE MAINTAINED AT CABLE TRANSITS AND PENETRATIONS. NUMEROUS CABLE TRANSITS AND PENATRATIONS HAVE BEEN REPACKED NOT PROVIDING INTEGRITY OF DIVISION. SOLAS 01 CONS. CH. II-2 REG. 3.3
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 February 2020
Resolved 14 February 2020
Resolution: See documents for Class Report
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 6 January 2020 Resolved
TERMINATIONS AND JOINTS IN ALL CONDUCTORS SHALL BE MADE TO RETAIN THE ORIGINALELECTRICAL, MECHANICAL,AND FLAME RETARDING PROPERTIES. DEAD END WIRES FOUND IN PYROTECHNICS STORAGE SPACE AND IN STORAGE BEHIND REDFROG BAR STAGE. SOLAS 01 CONS. CH. II-1 REG. 45.5.6
Action required: 50 - Rectify deficiencies w/in 30 days
Due 6 February 2020
Resolved 14 February 2020
Resolution: See documents for Class Report
04 - Emergency Systems › N/A - No Subsystem › Low level lighting in corridors
Issued 28 July 2019 Resolved
04104 IN ADDITION TO THE EMERGENCY LIGHTING REQUIRED, THE MEANS OF ESCAPE INCLUDING STAIRWAYS AND EXITS SHALL BE MARKED BY LIGHTING OR PHOTOLUMINESCENT STRIP INDICATORS. PSCO OBSERVED LOW LOCATION LIGHTING ON DECK 7 WAS NOT WORKING ON SOME AREAS (CABINS 7208-7299) PORT AND STBD PASSAGEWAYS. 74 SOLAS (2014) II-2 13.3.2.5.1 10C
Condition: Damaged By Earlier Event
Action required: 10 - Deficiency Rectified
Resolved 28 July 2019
Resolution: LOW LOCATION LIGHTING STRIP WAS FIXED PRIOR TO DEPARTURE.
04 - Emergency Systems › N/A - No Subsystem › Emergency source of power - Emergency generator
Issued 13 January 2019 Resolved
01-04114-The stored energy shall be maintained at all times as follows: compressed air starting systems may be maintained by the main or auxiliary valve or by an emergency air compressor. PSCO observed emergency air compressor leaking fuel at startup. 74SOLAS(04 CONS) CH II-1 / REG. 44.3.2 10C
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 13 January 2019
Resolution: Engineering department corrected deficiency shortly after and able to run emergency air compressor for emergency diesel generator without fuel leaking.
Electrical › Electrical Distribution System (service) › Shore Connection Box
Issued 16 September 2017 Resolved
The condition of the ship and it's equipment shall be maintained to conform with the provisions of the present regulations to ensure that the ship in all resepects will remain fit to proceed to sea without danger to the ship or persons on board. Vessel submitted report stating vessel experienced loss of power as well as a propulsion malfunction while en route to Sector LA-LB AOR. 74SOLAS(14)I/11
Action required: 17 - Rectify deficiencies prior to departure
Resolved 16 September 2017
Resolution: Class society (Lloyds) attended vessel, suspended Class Certificate with OPS notation until issue is resolved.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.