Inspection history · 5
27 December 2022
Administrative Inspection
Administrative · Commandant (CG-CVC) · Activity 7613823
29 March 2022
PSC B
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7420600
27 February 2022
Deficiency Check
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7402696
3 February 2022
PSC B · Deficiency Check · Administrative Inspection
Physical examination · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 7390227
13 January 2022
Administrative Inspection
Administrative · Commandant (CG-CVC) · Activity 7380042
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 3 February 2022
Resolved
In cargo ships, if a fire in any one compartment could put all the pumps out of action, there shall be alternative means consisting of an emergency fire pump. PSCO bserved inoperable fire pump.
74 SOLAS 20 II-2/2.2.3.2
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 February 2022
Resolution: Vessel provided class report attesting to repair of emergency fire pump
07 - Fire Safety › N/A - No Subsystem › Operation of Fire protection systems
Issued 3 February 2022
Resolved
Fire-fighting systems and appliances shall be kept in good working order and readily available for immediate use. (01) the CO2 release cabinet to ER on the main deck was found with disconnected lines rendering the remote station inoperable. (02) The CO2 blow through line was found with isolation valve in the open position creating an unintended release into the local space.
74 SOLAS (20) 14.2.1.2
Condition: Improper Installation
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 February 2022
Resolution: Vessel provided class report attesting to rectification of deficiency
14 - Pollution Prevention › 141 - MARPOL Annex I › Oil filtering equipment
Issued 3 February 2022
Resolved
Oil filtering equipment referred to in paragraph 1 of this regulation shall be of a design approved by the administration and shall be such as will ensure that any oily mixture discharged into the sea after passing through the system has an oil content not exceeding 15ppm. In considering the design of such equipment, the adminstration shall have regard to the specification recommended by the organization. PSCO observed inoperable ows.
Marpol Annex I/16
Condition: Placed in Improper Service
Action required: 17 - Rectify deficiencies prior to departure
Resolved 4 February 2022
Resolution: Vessel provided class report attesting to rectification of deficiency. OWS now operable.
14 - Pollution Prevention › 148 - Ballast Water › Ballast Water Management System (BMWS)
Issued 3 February 2022
Resolved
Following the installation, the master, owner, operator, agent, or persons in charge of the vessel subject to this subpart must properly maintain the BWMS in accordance with all manufacture specfication. PSCO observed BWMS in commision but not installled, going past installation date.
33 CFR 151.2025(a)(i)
Condition: Placed in Improper Service
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 30 March 2022
Resolution: Vessel commisoned BWS and submitted Class report attesting to system meeting all applicable regulations.