Tonnage as PSIX records it45965 - Convention (Subpart B), Gross Ton 68071 - Displacement, Ton 13790 - Convention (Subpart B), Net Ton 49999 - Dead Weight, Ton
This hull's Official Number is not in the NVDC file dated 10 August 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.
Vessel history report
A report is not offered for this hull. Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. What a sparse-record report looks like.
Inspection history · 9
30 April 2026PSC B · COC-GAS Renew
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 8355056
23 May 2025COC-GAS Annual · PSC B
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 8142120
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Cargo transfer - Tankers
Issued 26 September 2018Resolved
Pressure relief valves should be set and sealed by a competent person/authority acceptance to administration. STBD #1 tank missing the proper seal on the wire that covers the setting adjustment. Provide documents and setting verification of the #1 STBD MARV setting and place proper seal. Verify proper seals on the rest of the MARVs.
Condition: Placed in Improper Service
Action required: 15 - Rectify deficiencies by next port
Due 27 September 2018
Resolved 27 September 2018
Resolution: Class verified proper settings of all cargo relief valves.
Fire Fighting › Automatic Sprinkler System › Piping
Issued 3 October 2016Resolved
Piping for deck spray system failed in two places during system test.
Condition: Improper/Lack of Maintenance
Action required: 701 - Prior to carriage of passengers/cargo
Due 10 October 2016
Resolved 5 October 2016
Resolution: Received report from NKK detailing repairs to the water spray system and testing of same by Attending class surveyor.