CQ PRINCESS
Passenger (Inspected) · Passenger Ship class · Built 2000s · USCG Heartland District (CGD-H) · Other hulls named CQ PRINCESS
CQ PRINCESS is a 2004 passenger vessel (inspected). The Coast Guard has recorded 24 inspections since 2003, most recently in September 2025, along with 29 deficiencies and 1 casualty investigation in 2011.
Records from 2003 to 2025. Most recent: inspection, 30 September 2025.
- Built
- 2004
- Last inspected
- 30 September 2025
- Documentation
- Valid · documentation file of 10 September 2026
- Deficiencies
- 29 recorded · 0 without a recorded resolution
- Controls
- None recorded without a removal date
- Casualties
- 1 investigation · 2011
Identity
1161352
WDI6746
710990
Flag
UNITED STATES
367721790 (licence lapsed)
Maury page id
psix-710990
Inspections, by type
…with no type recorded1
Years with a record
18 calendar years (2003–2025)
The 24 inspections in the strip above, split by the kind of activity the US
Coast Guard recorded. Years with a record are calendar years in which a record exists, not
years in service. What Maury does not do.
Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.
Documentation record
Registered dimensions (L × B × D)82.2 ft × 20.0 ft × 6.0 ft
Registered tonnagegross 73 / net 49
ITC dimensions (L × B × D)82.2 ft × 20.0 ft × 6.0 ft
ITC tonnagegross 178 / net 63
BuilderMID CITY STEEL FABRICATING INC · LA CROSSE, WI, UNITED STATES · built 2004
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeNot recorded
Hull configurationNot recorded
Hailing portLOUISVILLE, KY
Trade endorsementsCoastwise, unrestricted
DocumentationValid · issued 11 December 2025 · expires 31 December 2026
Service, as the file records itPassenger (Inspected)
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it178 - Convention (Subpart B), Gross Ton
73 - Regulatory (Subpart C or D), Gross Ton
63 - Convention (Subpart B), Net Ton
49 - Regulatory (Subpart C or D), Net Ton
73 - Regulatory (Subpart C or D), Gross Ton
63 - Convention (Subpart B), Net Ton
49 - Regulatory (Subpart C or D), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 September 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Radio station licence
WDI6746MMSI 367721790 · expired · compulsorily equipped · granted 18 March 2016, cancelled 23 May 2026
FCC Universal Licensing System ship-station file of 6 September 2026, matched to this hull on its
US Official Number. Status and dates are the file’s own. The licensee is not read from the file and is not shown.
A lapsed licence’s MMSI is still the number the vessel transmitted under while it was valid.
Inspection history · 24
30 September 2025
Annual Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 8236557
6 September 2024
Annual Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 7961314
11 July 2023
COI Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 7721445
26 April 2023
Deficiency Check · Hull Examination · Internal Structural Exam
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 7676174
25 October 2022
Annual Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 7566209
20 October 2021
Annual Inspection · Deficiency Check
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 7336406
13 October 2020
Annual Inspection · Deficiency Check
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 7059155
3 September 2019
Deficiency Check · Administrative Inspection · Annual Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 6802741
18 July 2018
COI Inspection · Hull Examination · Examination of Repairs · Administrative Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 6483491
30 April 2018
Administrative Inspection · Drydock Extension
Administrative · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 6474223
29 November 2017
DAPI Audit
Administrative · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 6315406
3 October 2017
Annual Inspection · Administrative Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 6280929
13 September 2016
Annual Inspection · Administrative Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 5999136
1 September 2015
Annual Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 5232318
6 October 2014
Deficiency Check · Administrative Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 4999885
18 August 2014
Annual Inspection · Deficiency Check · Administrative Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 4958496
1 December 2011
Administrative Inspection
Administrative · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 4196932
27 September 2011
Administrative Inspection
Administrative · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 4162977
28 February 2011
Type not recorded
No type recorded · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 3954114
15 September 2010
Annual Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 3849748
19 August 2008
Annual Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 3303108
21 September 2005
Annual Inspection
Physical examination · Sector Ohio Valley · USCG Heartland District (CGD-H) · Activity 2498064
30 December 2004
Administrative Inspection
Administrative · MSO LOUISVILLE · USCG Heartland District (CGD-H) · Activity 2267788
1 October 2003
Construction Oversight · Hull Examination · COI Inspection
Physical examination · MSD ST. PAUL · USCG Heartland District (CGD-H) · Activity 2167438
Deficiency record · 29
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 30 September 2025
Resolved
Found worn child PFD donning placard, replace placard.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 20 October 2021
Resolved
Fixed fire extinguishing system shall be inspected annually. Vessels CO2 system has not been inspected since 2019. Ensure system is inspected and fully operational prior to getting underway with passengers.
07 - Fire Safety › N/A - No Subsystem › Maintenance of Fire protection systems
Issued 20 October 2021
Resolved
Portable extinguishers must be inspected and maintained in accordance with NFPA 10, which requires both an annual inspection by a certified technician and monthly checks by the owner/operator. These monthly checks are not being performed/ Develop a system to conduct and log these monthly checks.
05 - Radio Communications › N/A - No Subsystem › VHF radio installation
Issued 20 October 2021
Resolved
Vessels must comply with 47 CFR Part 80. All equipped radios must be operable onboard. Repair or replace the inoperable radio in pilothouse.
11 - Life Saving Appliances › N/A - No Subsystem › Maintenance of Life Saving Appliances
Issued 13 October 2020
Resolved
Vessel must carry at least one floating waterlight attached to the Ring Life Buoy, Waterlight had substantial crack in it causing it to no-longer meet required specifications for structural integrity. Replace Waterlight with approved equipment.
11 - Life Saving Appliances › N/A - No Subsystem › On board training and instructions
Issued 13 October 2020
Resolved
Vessel must have lifejacket donning instruction placard posted in a conspicuous location,current placard is worn beyond legibility. Replace donning placard.
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 13 October 2020
Resolved
Marine employers must establish random drug testing program for all crewmembers who perform duties and functions, required by the Vessel's Certification of Inspection, employer was unable to provide proof of one (01) crewmember's enrollment in random drug-testing pool. Provide evidence of crewmember's status in candidate pool.
09 - Working and Living Conditions › 091 - Living Conditions › Medical Equipment
Issued 13 October 2020
Resolved
Vessel must maintain a first aid kit as required in provided citation, kit had expired items. Restock kit.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 13 October 2020
Resolved
Use of twist-on type electrical connectors may be used within an enclosure and the insulated cap must be secured to prevent loosening due to vibration, electrical connectors for water tank did not have means of securing wire nuts (i.e. electrical tape). Install in accordance with provided citation.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 19 September 2019
Resolved
Relocate the fire extinguisher in the concession stand so it is at the ext and the extiguisher in the change room so they are readily accessible.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 3 September 2019
Resolved
Correct wiring in A/C space to meet standard for twist-on type wire nuts or use other approved commection type.
11 - Life Saving Appliances › N/A - No Subsystem › Lifejackets incl. provision and disposition
Issued 3 September 2019
Resolved
relocate placard for life jacket donning instructions for both life jacket storage boxes to a conspicuous place visible to crew and passengers.
02 - Structural Conditions › N/A - No Subsystem › Electrical installations in general
Issued 3 September 2019
Resolved
Correct TV power wiring in A/C space to meet standards for cable and wire for power and lighting circuits.
09 - Working and Living Conditions › 092 - Working Conditions › Machinery
Issued 3 September 2019
Resolved
Install guards around propeller shafts in engine room.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Machinery space openings
Issued 3 September 2019
Resolved
Install capture device for rudder room hatch cover to prevent loss of hatch cover.
09 - Working and Living Conditions › 091 - Living Conditions › Access/structure
Issued 3 September 2019
Resolved
Replace faded sign on upper deck notifying passengers of 53 person limit for upper deck.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 3 September 2019
Resolved
The current lable for the fuel shutoff valve is hidden in the A/C closet which does not meet the intent of the regulations. The fuel shutoff station needs to be clearly marked for emergency situations which may require assistance from non-crewmembers.
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 3 September 2019
Resolved
The bilges and other spaces should have no excessive accumulation of oil, trash, deris, or other matter what might create a fire hazard, clog bilge pumping systems, or block emergency escape. The vissel is being utilized for storage of furniture, multiple 5 quart oil jugs next to the main engines, and various other maintenance supplies throughout the voids and engineering spaces. Crew stated the vessel was utilized to store these items so they wouldn't have to move it from the shed during flooding events.
02 - Structural Conditions › N/A - No Subsystem › Beams, frames, floors-op. damage
Issued 18 July 2018
Resolved
During ISE the Marine Inspector identified 6 buckled transverse frames in the void that is immediately aft of the collision bulkhead. Whenever damage or deterioration to the hull plating or structural members that may affect the seaworthiness of a vessel is discovered the cognizant OCMI may take vessel out of service to effect permanent repairs. Vessel owner shall provide the marine inspector with a written repair proposal to conduct permanent repairs for the six buckled frames. Conduct repairs after repair proposal has been approved to the satisfaction of the attending Coast Guard Marine Inspector.
Lifesaving › Hand Flares › Approval
Issued 3 October 2017
Resolved
Vessel did not have Coast Guard approved distress signals. Vessel shall provide proper distress signals prior to getting underway.
Electrical › Electrical Distribution System (service) › Outlet Box
Issued 13 September 2016
Resolved
Install missing plug cover starboard side steering room.
Navigation › Piloting/Steering › Coast Guard Light List
Issued 19 August 2014
Resolved
Found no Coast Guard Light List on board. supply current Light list
Lifesaving › Lifejacket/PFD (General) › Storage
Issued 19 August 2014
Resolved
Found child PFD storage area without donning placard. Provide appropriate placard.
Documentation › Manifests/Lists › Emergency Checkoff List
Issued 18 August 2014
Resolved
Found passenger count not kept on shore side. Provide satisfactory plan to USCG inspector.
Personnel › Training › Fire Fighting Basic
Issued 18 August 2014
Resolved
Crew training has not been recorded in log book. Provide log book with crew training to include name, date, and description of training.
Operations/Management › Lifesaving › Op Readiness/Maintenance/Inspection
Issued 18 August 2014
Resolved
Vessel drills has not been recorded in log book. Provide log book with abandon ship, man overboard, and fire drills to included; date of drill and description of drill.
Engineering › Bilge Water Management System › Valve
Issued 18 August 2014
Resolved
Found engine room bilge suction check valve seized closed. Correct for future use.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Servicing
Issued 21 September 2005
Resolved
Annual servicing not completed. Provide proper documentation of annual service.....
Fire Fighting › Portable CO2 Fire Extinguisher › Service
Issued 21 September 2005
Resolved
Annual servicing not completed. Provide proper documentation of annual service.....
Casualty record · 1
28 February 2011Routine · role: Involved in a Marine Casualty · activity 3954114
Each line is an incident investigation the Coast Guard recorded with this hull among the vessels involved, with the date and the classification the Coast Guard gave it, and the bridge, lock or dam the investigation names where it names one. Involvement is not fault. The investigation narrative is not published. Source: IIR, through 2026.
Ownership record
The Coast Guard's documentation record for this hull -- the Abstract of Title,
with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National
Vessel Documentation Center, files it here with its date, and every reader of this page gets it.