VICTORIOUS

VICTORIOUS is a 2005 tank ship. The Coast Guard has recorded 25 inspections since 2005, most recently in October 2019, along with 11 deficiencies and 8 operational controls.

Records from 2005 to 2019. Most recent: inspection, 12 October 2019.

Built
2005
Last inspected
12 October 2019
Documentation
Not in the documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

9290919 View on MarineTraffic leaves Maury; a third-party site, nothing from it is stored here
V7A2490
741538
Flag
BAHAMAS, THE
—
Maury page id
psix-741538

Inspections, by type

…with no type recorded12
Years with a record 9 calendar years (2005–2019)
The 25 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

This record may be incomplete: the most recent inspection recorded for this vessel was 7 years ago. Maury shows what the Coast Guard recorded, not whether the vessel has been inspected since, is still in service, or what condition it is in. Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Tank Ship class in Maury's sources begin in 1980.

Documentation record

Tonnage as PSIX records it30020 - Convention (Subpart B), Gross Ton
12196 - Convention (Subpart B), Net Ton
57625 - Displacement, Metric Ton
47119 - Dead Weight, Metric Ton
This hull's Official Number is not in the NVDC file dated 10 September 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.

Radio station licence

No FCC ship-station licence is recorded against this Official Number in the file of 6 September 2026. That is a fact about the licence file, not about the radio.

Inspection history · 25

12 October 2019 Ballast Water Examination · COE-Administrative · ISPS II Exam · COC-CHEM & TVE Renew
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 6828495
30 September 2019 Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 6824894
30 September 2019 Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 6824911
18 March 2019 Type not recorded
No type recorded · Sector New York · USCG Northeast District (CGD-NE) · Activity 6644569
13 October 2018 Ballast Water Examination · COC-CHEM & TVE Renew · ISPS II Exam
Physical examination · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 6556507
30 January 2012 Ballast Water Examination · COC-CHEM Annual · ISPS II Exam
Physical examination · Marine Safety Unit Texas City · USCG Heartland District (CGD-H) · Activity 4231387
6 October 2010 COC-CHEM Renew · ISPS II Exam · PII Safety Exam · Ballast Water Examination
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 3864729
5 October 2010 Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 3861073
27 February 2009 COE-Administrative
Administrative · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 3425279
15 February 2009 COE-Dockside
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 3416040
24 November 2008 Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 3368322
18 November 2008 Type not recorded
No type recorded · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 3365367
10 November 2008 ISPS II Exam · COC-CHEM Annual · Ballast Water Examination
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 3360657
28 March 2007 MARPOL Annex V Examination · Ballast Water Examination · STCW 95 Exam · COC-CHEM Renew · ISPS II Exam · MARPOL Annex I Examination · ILO-147 Exam
Physical examination · Sector Northern New England · USCG Northeast District (CGD-NE) · Activity 2897065
23 October 2006 Type not recorded
No type recorded · Sector Northern New England · USCG Northeast District (CGD-NE) · Activity 2806149
21 October 2006 Type not recorded
No type recorded · Sector Northern New England · USCG Northeast District (CGD-NE) · Activity 2807789
11 June 2006 Type not recorded
No type recorded · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 2676144
7 June 2006 In-Service Inspection
Physical examination · Marine Safety Unit Port Arthur · USCG Heartland District (CGD-H) · Activity 2673368
30 March 2006 ISPS II Exam · COC-CHEM Annual · Ballast Water Examination
Physical examination · Sector Houston/Galveston · USCG Heartland District (CGD-H) · Activity 2612894
6 January 2006 Random ISPS/MTSA/PSC · Ballast Water Examination
Physical examination · Sector Delaware Bay · USCG East District (CGD-E) · Activity 2561910
16 September 2005 Type not recorded
No type recorded · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 2494008
16 September 2005 Type not recorded
No type recorded · Sector Corpus Christi · USCG Heartland District (CGD-H) · Activity 2502122
21 April 2005 Deficiency Check
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 2339415
28 March 2005 MARPOL Annex I Examination · COC-CHEM Renew · ISPS II Exam · Ballast Water Examination
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 2321921
26 March 2005 Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 2320128

Deficiency record · 11

Deck/Cargo › Inert Gas System › Deck Distribution System
Issued 6 October 2010 Resolved
As currently constructed the ventilation system in the engine room around the O2 censoring equipment to the inert gas generator is not operating as appropriate for the purpose of that machinery space. Temporary ventilation piping has been installed to prevent O2 sensor failure. cite: SOLAS 74/2004 cons. II-I, Reg 35
Action required: 705 - Other - as specified
Resolved 10 October 2010
Resolution: Recieved class report. Temporary piping installed for ventilation has been removed. O2 sensing equipment for inert gas generator was tested sat.
Pollution Prevention/Response › Prevention Equipment › Incinerator, Shipboard
Issued 6 October 2010 Resolved
Ignition sources shall be restricted. The fire bricks inside the incinerator have collapsed and no longer protect the incinerator casing creating a significant fire hazard. cite: SOLAS 74/2004 cons. II-I Reg 4.1.4
Action required: 705 - Other - as specified
Resolved 10 October 2010
Resolution: Recieved class report. Fire bricks inside of incinerator were repaired in accordance with manufacturer recommendation and found sat.
Engineering › Fuel Oil Service System › Piping
Issued 6 October 2010 Resolved
The machinery and associated piping shall be of a design and construction adequate for the service for which they are intended. The fuel oil leakage piping on main engine has an additional line installed which is not indicated on approved fuel oil service system diagram. cite: SOLAS 74/2004 cons. II-I Reg 26.1
Action required: 705 - Other - as specified
Due 5 November 2010
Resolved 10 October 2010
Resolution: Recieved class report. Relevent piping removed from main engine fuel oil system and flanges blanked.
Documentation › Logs/Records › Oil Record Book
Issued 6 October 2010 Resolved
Each operation in the oil record book shall be fully recorded without delay, so that all entries in the book appropriate to that operation and completed. The max capacitity of the oily water separator is 5.0m3/hour. On July 19 2010 the Oil record book records start 1300 end 1600 and processed 18m3; On July 31 2010 started 1400 end 1700 and processed 17m3. This exceeds the maximum output of 5 m3/hr
Action required: 705 - Other - as specified
Due 5 November 2010
Resolved 10 October 2010
Resolution: Recieved Flag report. Attested to correction of oil record book and proper operation of ows.
Personnel › Manning/Qualifications › Minimum Safe Manning
Issued 18 November 2008 Resolved
The Captain of the Port Sector Houston Galveston has been notified of the marine casualty aboard your vessel with regards to the ships master. Prior to the vessels departed from the Port of Houston, submit to this office: Documentation attesting to the proper manning of the vessel.
Condition: Unknown
Action required: 17 - Rectify deficiencies prior to departure
Resolved 20 November 2008
Resolution: PSCO received documentation of proper manning, new master onboard. The vessel has been released from OPCON.
Deck/Cargo › Vapor Control Systems › Piping/Hoses
Issued 28 March 2005 Resolved
Install permanently fixed stud on all manifold Vapor Control Flanges. Adjustable studs are not acceptable.
Condition: Improper Installation
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 2 April 2005
Resolution: all sat.
Documentation › Certificates/Documents › IOPP Certificate
Issued 28 March 2005 Resolved
Flag or Class to indicate vessel type on Page 1 of the IOPP. Currently "Type of Ship" is not indicated.
Condition: Unknown
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 21 April 2005
Documentation › Certificates/Documents › IOPP Certificate
Issued 28 March 2005 Resolved
Provide attachment for Category C & D Oil- Like NLS cargoes as per IOPP Form B. Vsl shall not carry Oil-like NLS cargoes until attachement is on board. See Act 2321921 for details.
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 21 April 2005
Documentation › Manuals/Policy Documentation › Vessel Specific Watch Policy/Procedures
Issued 28 March 2005 Resolved
Provide current copies of 46 CFR 35, 150, and 150 as per 46CFR 153.905.
Condition: Unknown
Action required: 15 - Rectify deficiencies by next port
Resolved 2 April 2005
Resolution: copies of 46 CFR present, all sat.
Pollution Prevention/Response › Prevention Equipment › Oily Water Separator (15 ppm)
Issued 28 March 2005 Resolved
Remove the crossover connection at the OWS overboard discharge piping, after the 3-way valve that was installed in the shipyard during new construction. Piping arrangement differs from manufacturer's specifications. See Act 2321921 for details.
Condition: Improper Installation
Action required: 15 - Rectify deficiencies by next port
Resolved 2 April 2005
Resolution: piping removed, all sat
Accommodation/Occupational Safety › Occupational Safety › Portable Electric Equipment/Appliances
Issued 28 March 2005 Resolved
Both portable oxygen analysers inop due to dead batteries. Machines left on during last use.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 28 March 2005
Resolution: New batteries installed.