GO TRAVELER is a 2005 offshore supply vessel. The Coast Guard has recorded 20 inspections since 2016, most recently in June 2026, along with 34 deficiencies.

Records from 2016 to 2026. Most recent: inspection, 29 June 2026.

Built
2005
Last inspected
29 June 2026
Documentation
Valid · documentation file of 10 August 2026
Controls
None recorded without a removal date

Coast Guard record current through 23 August 2026, retrieved 5 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Offshore class in Maury's sources begin in 2016.

Inspection record

Last inspected 29 June 2026
…with no type recorded1
Operational controls None recorded without a removal date
Years with a record 10 calendar years (2016–2026)
Every line above is a count of records the US Coast Guard wrote, or a date it recorded. A blank resolution means none was recorded in this data; it does not establish that a deficiency is outstanding. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Identity

9370965
WDN3308
773007
Flag
UNITED STATES
Maury page id
psix-773007

Documentation record

Registered dimensions (L × B × D)149.2 ft × 36.0 ft × 12.0 ft
Registered tonnagegross 80 / net 54
ITC dimensions (L × B × D)149.2 ft × 36.0 ft × 12.0 ft
ITC tonnagegross 498 / net 149
BuilderMASTER BOAT BUILDERS INC · CODEN, AL, UNITED STATES · built 2005
Hull materialSteel
PropulsionDiesel Reduction
Hull shapeUNSPECIFIED
Hull configurationUNSPECIFIED
Hailing portNEW ORLEANS, LA
Trade endorsementsCoastwise, unrestricted, Registry
DocumentationValid · issued 9 April 2026 · expires 31 May 2027
Service, as the file records itOffshore Supply Vessel
Hull formpowered (Maury's inference from propulsion, hull shape, material and length, rule hf-1; not a recorded fact)
Tonnage as PSIX records it498 - Convention (Subpart B), Gross Ton
80 - Regulatory (Subpart C or D), Gross Ton
149 - Convention (Subpart B), Net Ton
54 - Regulatory (Subpart C or D), Net Ton
Every line above is a field of the National Vessel Documentation Center's file as served by NOAA Fisheries, dated 10 August 2026, matched to this hull on its Official Number. Registered and ITC measurements are two systems and are never combined. One snapshot is held so far; documentation history begins with the next.
Vessel history report

A report is not offered for this hull. Its record holds only 2 of the seven kinds of material a report is built from: inspections, deficiencies, operational controls, tow-unit appearances, casualty records, dimensions and documentation. That is a statement about the record, not about the vessel. What a sparse-record report looks like.

Inspection history · 20

29 June 2026 Damage Survey · Deficiency Check · Vessel Attendance · Administrative Inspection
Physical examination · Marine Safety Unit Morgan City · USCG Heartland District (CGD-H) · Activity 8418904
16 December 2025 Deficiency Check · COI Inspection · MTSA Verification
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 8276340
13 February 2025 Annual Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 8079457
14 January 2025 Internal Structural Exam · Drydock Exam · Cargo Tank Internal
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 8063223
23 January 2024 Administrative Inspection · Annual Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7853805
23 June 2023 Type not recorded
No type recorded · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7721903
6 December 2022 Administrative Inspection · Annual Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7602296
31 March 2022 Hull Examination · Internal Structural Exam · Drydock Exam
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7421556
21 March 2022 Administrative Inspection
Administrative · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7415857
5 January 2022 Annual Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7375844
16 December 2020 MARPOL Annex V Examination · COI Inspection · MARPOL Annex IV Survey · MARPOL Annex VI Survey · MARPOL Annex I Examination
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7112489
27 October 2020 Deficiency Check · Cargo Tank Internal · Internal Structural Exam · Administrative Inspection · Drydock Exam
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 7084788
15 April 2020 Drydock Extension · Administrative Inspection
Administrative · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6939352
2 July 2019 MARPOL Annex VI Survey · MTSA/ISPS Verification · MARPOL Annex V Examination · MARPOL Annex IV Survey · Annual Inspection · MARPOL Annex I Examination
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6733572
25 June 2018 Annual Inspection · MARPOL Annex I Examination
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 6442364
17 July 2017 In-Service Inspection · Administrative Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 6212232
10 July 2017 Administrative Inspection · Annual Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 6203928
21 June 2017 In-Service Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 6204880
24 May 2017 Internal Structural Exam · Administrative Inspection · Hull Examination
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 6154638
7 November 2016 Administrative Inspection · Annual Inspection
Physical examination · Marine Safety Unit Houma · USCG Heartland District (CGD-H) · Activity 6037319

Deficiency record · 34

07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 16 December 2025 Resolved
A vessel may install fire extinguishing equipment beyond that required and must be designed, installed, and maintained. Vessel had two heat detectors over the port and stbd MDEs that were not properly affixed and one of those had wiring issues.
Condition: Improper/Lack of Maintenance
Action required: 17 - Rectify deficiencies prior to departure
Resolved 17 December 2025
Resolution: Vessel submitted tech report stating that items was corrected.
11 - Life Saving Appliances › N/A - No Subsystem › Lifebuoys incl. provision and disposition
Issued 16 December 2025 Resolved
Each OSV on an oceans route must must carry at least one-half the total number of lifebuoys fitted with a self-igniting light approved under approval series 161.010. AND Each ring life buoy must be marked with Type I or II retro-reflective material approved under subpart 164.018 of this chapter. Port ring lifebouy on the main deck dod not have functioning light and reflective tape was worn.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 16 December 2025
Resolution: Vessel submitted invoice for new light and corrected refelctive taping.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 16 December 2025 Resolved
No ship may carry a cargo or bulk liquid hazardous material or NLS residue unless the bulk liquid HAZMAT is listed on the COI and the vsl meets the requirements to carry. Vessel did not meet the requirements of the IBC code, amended A.673, and CG-ENG Policy Letter 03-12,CH1 (US Interpretation of updated A.673 requirements) including Vapor detection, vent height requirements, vent pressure requirements, etc.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 January 2026
Resolved 2 April 2026
Resolution: Verified all items identified by gap analysis to enclude decontamination shower and eyewash station, additional PPE, CRB, USCG approved P & A Manual, and toxic/flammable vapor detection
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 16 December 2025 Resolved
Vessel shall be in a safe and seaworthy condition including pollution prevention and fire hazards. Excessive oil was observed in the bow thruster bilge. Remove and properly dispose of oil.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 January 2026
Resolved 12 January 2026
Resolution: Vessel rep sent pictures of bilge cleaned of oil.
09 - Working and Living Conditions › 092 - Working Conditions › Guards - fencing around dangerous machinery parts
Issued 16 December 2025 Resolved
Gears, couplings, flywheels, and all rotating machinery capable of injuring personnel must be provided with adequate covers or guards. Guard over bow thruster shaft was not held in place.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 January 2026
Resolved 12 January 2026
Resolution: Vessel rep sent picture of grating with cover secured.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Operation of machinery
Issued 16 December 2025 Resolved
Vessel shall be in a safe and seaworthy condition including pollution prevention and fire hazards. Oil leaks were identified in the stbd MDE and the port MDE fuel oil return.
Action required: 10 - Deficiency Rectified
Resolved 16 December 2025
Resolution: Vessel tightened fittings to prevent leakage.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Other (machinery)
Issued 16 December 2025 Resolved
Oil piping drains, strainers, and other equipment subject to normal oil leakage must be fitted with drip pans or other means to prevent oil draining into the bilge. Stbd generator was missing a drip pan.
Action required: 50 - Rectify deficiencies w/in 30 days
Due 16 January 2026
Resolved 14 January 2026
Resolution: Recevied email showing a drip pan underneath the RACOR.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 16 December 2025 Resolved
Each cable and wire must be supported so as to avoid chafing or other damage. Wire to light over Port MDE is not properly affixed.
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 17 December 2025
Resolution: Wiring corrected by Third Party Technition
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 16 December 2025 Resolved
A vessel of less than 100 gross tons must have adequate emergency lighting fitted along the line of escape to the main deck from accommodations and working (machinery) spaces below the main deck. Emergency lighting did not provide ample illumination for emergency response actions.
Action required: 10 - Deficiency Rectified
Resolved 16 December 2025
Resolution: Crew cleaned light covers.
01 - Certificates & Documentation › 013 - Documents › Oil record book
Issued 16 December 2025 Resolved
Entries shall be made in the Oil Record Book on each occasion whenever any machinery space oil transfer operations take place. Oil Record Book did not properly account for all movements of oil onto, throughout, and off the vsl. Proper documentation of oil on board is important to track disposition of oil.
Action required: 10 - Deficiency Rectified
Resolved 16 December 2025
Resolution: Provided training to Crew.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Machinery space openings
Issued 13 February 2025 Resolved
Means for securing these doors weathertight shall consists of gaskets and clamping devices or other equivalent means. MI saw daylight through where the ER Escape Hatch did not seal properly with the gasket.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 14 February 2025
Resolution: Vessel rep emailed pictures of repairs to the satisfaction of the MI.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Manholes/flush scuttles
Issued 13 February 2025 Resolved
A Class 1 door may be installed at any place if (3) The vessel's pilothouse contains a visual indicator showing whether the door is open or closed. The arm of the indicator was not long enough to make contact to signal the pilothouse.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 14 February 2025
Resolution: Vessel rep emailed pictures of repairs to the satisfaction of the MI.
06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 13 February 2025 Resolved
Hazardous location equipment must be approved as suitable for use in the specific hazardous atmosphere. Vessel had wastage that allowed ventilation and vapors in the methanol pump cabinet/area. 705- Prior to carriage of methanol.
Action required: 705 - Other - as specified
Resolved 14 February 2025
Resolution: Rewelded affected area of methanol pump cabinet.
14 - Pollution Prevention › 141 - MARPOL Annex I › Oil filtering equipment
Issued 13 February 2025 Resolved
Ship staff training must include familiarization in the operation and maintenance of the equipment. Routine maintenance of the oily water separating equipment and the bilge alarm must be clearly defined by the manufacturer in associated operating and maintenance manuals. All routine and repair maintenance must be recorded. Vessel crew did not know how to test OWS, was not testing OWS monthly, nor logging testing for annual inspection.
Action required: 10 - Deficiency Rectified
Resolved 13 February 2025
Resolution: Vessel locking out and tagging out equipment. Vessel has ability to retain oily waste.
01 - Certificates & Documentation › 013 - Documents › Oil record book
Issued 13 February 2025 Resolved
Entries shall be made in the ORB on each occasion IAW ORB instructions and 33CFR151.25. Vessel had seperate ORB for receiving and transfers & was not logging entries properly. Training provided to Master and Mate.
Action required: 10 - Deficiency Rectified
Resolved 13 February 2025
Resolution: Training provided to Master and Mate.
07 - Fire Safety › N/A - No Subsystem › Fire detection and alarm system
Issued 13 February 2025 Resolved
Equipment install must be installed, tested, and maintained IAW appropriate industry standards and manufacturer guidance. Vessel had three smoke detectors that were not operational.
Action required: 10 - Deficiency Rectified
Resolved 13 February 2025
Resolution: Replaced defective smoke detector and installed new batteries in others.
04 - Emergency Systems › N/A - No Subsystem › Fire drills
Issued 13 February 2025 Resolved
Vessel shall have fire and abandon ship drills on alternating weeks. Vessel modified the schedule on 1FEB2025 to conduct alternating weeks; however, did not conduct alternating drills prior as evidence in the logbook prior to NOV2024.
Action required: 10 - Deficiency Rectified
Resolved 13 February 2025
Resolution: Vessel has corrected schedule to complete alternating weeks.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 23 January 2024 Resolved
Each vessel with watertight doors in bulkheads must be made watertight. Engine room escape watertight door was loose.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 February 2024
Resolved 25 January 2024
03 - Water/Weathertight Conditions › N/A - No Subsystem › Covers (hatchway-, portable-, tarpaulins, etc.)
Issued 23 January 2024 Resolved
Each hatch exposed to the weather must be watertight. Engine room escape hatch had a pinhole.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 February 2024
Resolved 25 January 2024
11 - Life Saving Appliances › N/A - No Subsystem › Inflatable liferafts
Issued 23 January 2024 Resolved
Lifesaving appliances and arrangements are subject to tests and inspections during OSV boardings to ensure that the applications and arrangements comply with applicable requirements, are in satisfactory condition and remain fit for service. Port inflatable life raft hydrostatic release was improperly arranged to the painter line.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 24 January 2024
Resolved 24 January 2024
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 23 January 2024 Resolved
Lifesaving appliances and arrangements are subject to tests and inspections during OSV boardings to ensure that the applications and arrangements comply with applicable requirements, are in satisfactory condition and remain fit for service. Stbd aft life ring was blocked by materials.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 January 2024
Resolved 25 January 2024
05 - Radio Communications › N/A - No Subsystem › Other (radio communication)
Issued 23 January 2024 Resolved
Each vessel that relies on electricity to power any vital system must be arranged so that the loads can be energized from at least two sources of electricity. VHF radio was inoperable while operating on emergency power.
Condition: Improper Installation
Action required: 10 - Deficiency Rectified
Due 24 January 2024
Resolved 24 January 2024
99 - Other › N/A - No Subsystem › Other (Safety in general)
Issued 23 January 2024 Resolved
Each area enclosed by required coaming must have a mechanical means of closing each drain and scupper in the enclosed deck area. Containment on the stbd fuel oil manifold was improperly plugged.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 February 2024
Resolved 26 January 2024
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 23 January 2024 Resolved
Protect crew members, offshore workers and the vessel from electrical hazards including fire caused by or originating in electrical equipment and electrical shock. There was loose wiring under aft helm console.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 February 2024
Resolved 25 January 2024
11 - Life Saving Appliances › N/A - No Subsystem › Other (life saving)
Issued 23 January 2024 Resolved
A rescue boat is not required for a vessel operating on the continental shelf of the U.S. Rescue platform ladder was not properly affixed to the vessel.
Condition: Improper Installation
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 February 2024
Resolved 26 January 2024
07 - Fire Safety › N/A - No Subsystem › Other (fire safety)
Issued 23 January 2024 Resolved
For each 79,500 L or part thereof of any Class 3 (flammable) or combustible liquid being transported on board a vessel in a portable tank, rail tank car, or a motor vehicle cargo tank, there must be provided at least one B-V semiportable foam (152 L/40 gallon capacity), dry chemical or equivalent fire extinguisher, a fire hose fitted with an approved portable mechanical foam nozzle with pick-up tube and two (5 gallon) cans of foam liquid concentrate. Pick up tube for mechanical foam nozzle was inoperable.
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Due 24 January 2024
Resolved 24 January 2024
01 - Certificates & Documentation › 011 - Ships Certificates › Certificate of Inspection (COI)
Issued 23 January 2024 Resolved
The Certificate of Inspection must be framed under glass or other suitable transparent material and posted in a conspicuous place aboard the OSV so that each page is visible. The original COI was not onboard.
Condition: Improper/Lack of Maintenance
Action required: 50 - Rectify deficiencies w/in 30 days
Due 24 February 2024
Resolved 26 January 2024
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 6 December 2022 Resolved
A Class I door may be installed at any place if vessels pilothouse contains a visual indicator. Aft engine room door indicator arm is broken.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 7 December 2022
Resolution: Received photographic evidence from vessel rep of repaired aft engine room watertightdoor indicator arm.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 6 December 2022 Resolved
Each connection ot a battery terminal must be made with a permanent connector. Battery charge connection is made with temporary spring clips.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 December 2022
Resolved 7 December 2022
Resolution: Received photographic evidence of permanent connections to battery terminal.
09 - Working and Living Conditions › 092 - Working Conditions › Warning notices
Issued 6 December 2022 Resolved
Each space entrance storing or protected by CO2 systems must be marked. CO2 bottle storage room and engine room were not marked.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 20 December 2022
Resolved 7 December 2022
Resolution: Vessel rep stated new CO2 stickers have been ordered
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 5 January 2022 Resolved
The inspection for certification shall include a verification of the vessel's watertight integrity; watertight door on the 01 deck had dry-rotted gasket.
Action required: 10 - Deficiency Rectified
Resolved 5 January 2022
Resolution: Gasket was replaced prior to the conclusion of the inspection.
14 - Pollution Prevention › 146 - MARPOL Annex VI › Other (MARPOL Annex VI)
Issued 5 January 2022 Resolved
Self propelled vessels of 400 gross tonnage and above, engaged on international voyages, must have a Ship Energy Efficiency Management Plan (SEEMP) onboard; The SEEMP was not able to be located by the master or crew. MARPOL VI/22.1
Action required: 702 - Prior to embarking on international voyage
Resolved 6 January 2022
Resolution: Vessel rep sent photo of shipboard SEEMP.
13 - Propulsion and Auxiliary Machinery › N/A - No Subsystem › Gauges, thermometers, etc
Issued 16 December 2020 Resolved
Pressure-indicating gauges shall be compatible with the pressure to be indicated. The upper range can't be less than 1.2 times nor more than 2 times the pressure at which the relieving device is set to function. 46 CFR 54.15-5(f)
Action required: 16 - Rectify deficiencies w/in 14 days
Due 16 December 2020
Resolved 16 December 2020
Resolution: Vessel provided photographic evidence showing new pressure gauges.
14 - Pollution Prevention › 141 - MARPOL Annex I › Other (MARPOL Annex I)
Issued 16 December 2020 Resolved
Under each loading manifold and each transfer connection point requires a fixed container with a means of drainage and mechanical means of closing each drain. Vessel was unable to mechanically close each drainage opening on the fixed containers on the aft deck.
Action required: 16 - Rectify deficiencies w/in 14 days
Due 16 December 2020
Resolved 16 December 2020
Resolution: Vessel provided photographic evidence that all fixed containers had mechanical closers.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.