Records from 2005 to 2022. Most recent: inspection, 7 February 2022.
Inspection history · 43
7 February 2022
PSC B
Physical examination · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 7390164
24 November 2020
PSC A
Physical examination · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 7101239
17 June 2020
PSC A
Physical examination · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 6975967
19 December 2019
CCSSC Examination · ISPS III Exam
Physical examination · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 6867652
24 July 2019
ISPS III Exam · NPV Safety Exam · Ballast Water Examination
Physical examination · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 6760835
6 March 2019
Deficiency Check · Administrative Inspection
Physical examination · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 6637042
28 February 2019
ISPS III Exam · Ballast Water Examination · NPV Safety Exam
Physical examination · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 6632332
26 September 2018
Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6549304
21 September 2018
Ballast Water Examination · NPV Safety Exam · ISPS III Exam
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6545153
11 September 2018
Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6538569
10 September 2018
Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6536734
28 August 2018
Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6525105
27 August 2018
Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6524050
22 August 2018
Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6519629
21 August 2018
Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6518480
16 August 2018
Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6513555
15 August 2018
Type not recorded
No type recorded · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6512574
13 July 2018
Deficiency Check
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6470193
4 July 2018
Administrative Inspection
Administrative · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6466272
14 June 2018
Deficiency Check · Ballast Water Examination · PII Safety Exam · ISPS II Exam
Physical examination · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6443082
12 June 2018
Administrative Inspection
Administrative · Sector San Juan · USCG Southeast District (CGD-SE) · Activity 6442556
30 January 2018
ISPS II Exam · Ballast Water Examination · Administrative Inspection · PII Safety Exam
Physical examination · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 6346315
22 September 2017
Administrative Inspection · Deficiency Check
Physical examination · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 6272850
1 September 2017
Administrative Inspection
Administrative · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6256952
24 July 2017
ACP Periodic Oversight · Periodic Inspection · Administrative Inspection
Physical examination · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 6219355
23 July 2017
Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 6223738
2 July 2017
Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 6199709
2 July 2017
Damage Survey
Physical examination · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 6214367
24 May 2017
ISM SMC Audit · In-Service Inspection · Administrative Inspection · Examination of Repairs · Damage Survey · Internal Structural Exam
Physical examination · Sector St Petersburg · USCG Southeast District (CGD-SE) · Activity 6154091
18 May 2017
Damage Survey
Physical examination · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 6149637
18 May 2017
Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 6212852
9 May 2017
Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 6142317
24 March 2017
Administrative Inspection
Administrative · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 6112377
22 September 2016
Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 6006458
17 August 2016
MTSA/ISPS Verification · ACP Annual Oversight · Damage Survey
Physical examination · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 5975549
11 August 2016
ISM Oversight
Administrative · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 5969729
9 August 2016
Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 5967003
14 July 2016
Deficiency Check · Administrative Inspection
Physical examination · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 5940211
28 June 2016
COE-Dockside
Physical examination · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 5921431
24 June 2016
Type not recorded
No type recorded · Sector Jacksonville · USCG Southeast District (CGD-SE) · Activity 5917534
7 March 2016
Administrative Inspection · Deficiency Check
Physical examination · Sector Charleston · USCG Southeast District (CGD-SE) · Activity 5830940
9 February 2016
Administrative Inspection
Administrative · Activities Europe · Activity 5811864
5 January 2016
In-Service Inspection
Physical examination · Sector North Carolina · USCG East District (CGD-E) · Activity 5791555
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 28 February 2019
Resolved
Doors fitted in boundary bulkheads of machinery spaces shall be reasonably gastight and self-closing. Multiple A class doors are missing gaskets and 01 door is unable to self close - 74 SOLAS (1997) II-2/47.1 - 16AC
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 March 2019
Resolved 6 March 2019
Resolution: MSD ST Thomas received ABS class survey report attesting to the proper repair of the A-class fire doors gaskets and self-closure. Deficiency Cleared.
05 - Radio Communications › N/A - No Subsystem › Operation/maintenance
Issued 28 February 2019
Resolved
A record shall be kept to the satisfaction of the administration and as required by radio regulations of all incidents. GMDSS Radio log is missing entries - 74 SOLAS(2014) IV/17 - 16BC
Action required: 16 - Rectify deficiencies w/in 14 days
Due 14 March 2019
Resolved 6 March 2019
Resolution: MSD ST Thomas received Vanuatu Flag State survey report stating corrective action has been verified onboard; with a new GMDSS log book placed on board and deck officers familiarization with the procedures. Deficiency Cleared.
07 - Fire Safety › N/A - No Subsystem › Evaluation of crew performance (fire drills)
Issued 21 September 2018
Resolved
Drills shall, as far a practicable, be conducted as if there were an actual emergency. The crew failed the first fire drill in the emergency generator room due to not closing the fuel shut off valve, one fireman did not have a flash hood, and the other fireman entered the space without an SCBA.
Action required: 10 - Deficiency Rectified
Due 21 September 2018
Resolved 21 September 2018
Resolution: The crew were provided feedback and the second drill was satisfactory.
07 - Fire Safety › N/A - No Subsystem › Fire doors/openings in fire-resisting divisions
Issued 21 September 2018
Resolved
Doors required to be self-closing shall not be fitted with hold-back hooks. The door to the emergency fire pump space was held back and the escape hatch in the engine room was held open by a fan.
Action required: 10 - Deficiency Rectified
Due 21 September 2018
Resolved 21 September 2018
Resolution: The hold back and fan were removed.
01 - Certificates & Documentation › 011 - Ships Certificates › Load Lines (including Exemption)
Issued 14 June 2018
Resolved
The ring, lines and letters shall be painted in a white or yellow on a dark background. The deck line was painted the same color as the hull. ILLC Ch I Reg 8
Action required: 10 - Deficiency Rectified
Resolved 14 June 2018
Resolution: The deck line was painted a contrasting color.
10 - Safety of Navigation › N/A - No Subsystem › Signalling lamp
Issued 14 June 2018
Resolved
All ships 150 gross tonnage and upwards shall be fitted with a daylight signaling lamp not solely dependent upon the ship's power. The daylight signaling lamp did not have a source of power separate from the ship's power. SOLAS (2014) V/19.2.2.2
Action required: 16 - Rectify deficiencies w/in 14 days
Due 28 June 2018
Resolved 13 July 2018
Resolution: Provided adequate independent power source for the dayight signaling lamp to the satisfaction of the Coast Guard.
Construction/Loadline › Hull › Transverse Frame
Issued 2 June 2017
Resolved
Found cargo bay transverse bulkhead 26 combing stiffiner plate wasted and holed. Make repairs to the satisfaction of the attending Coast Guard Marine Inspector.
Action required: 17 - Rectify deficiencies prior to departure
Due 2 June 2017
Resolved 11 June 2017
Resolution: Final repair witnessed and cleared by ABS.
Documentation › Safety/Response Plans/Programs › Fire Control Plans
Issued 2 June 2017
Resolved
Found Fire Control Plan inaccurately exhibited the vessels fire boundaries. Provide amended and approved plan.
Action required: 705 - Other - as specified
Due 6 October 2017
Resolved 7 October 2017
Resolution: Attended vessel with ABS Surveyor. Verified change to Fire Control Plan. Plans sent to ABS Houston for full approval. Def cleared. ABS Statutory Condition 1306 still outstanding.
Construction/Loadline › Hull › Hull Plating
Issued 2 June 2017
Resolved
Make permanent repairs to the Bow Thruster tube. (at next dry-dock but NLT 01FEB18)
Action required: 705 - Other - as specified
Due 1 February 2018
Resolved 20 June 2018
Resolution: PSC Team observed proper documentation attesting to the repairs of the Bow Thruster tube.
Fire Fighting › Structural Fire Protection - General › Hull Construction
Issued 2 June 2017
Resolved
Found fire stop (Roxtec) with incompatible components (red, blue modules). Repair/replace modules with comparable components at next dry-dock.
Action required: 705 - Other - as specified
Due 1 February 2018
Resolved 8 June 2017
Resolution: Proper (red) modules installed.
Operations/Management › Ballast Water Managment › Ballast Exchange
Issued 2 June 2017
Resolved
Vessel is prohibited from discharging untreated ballast water until vessel complies with Ballast Water regulations. (at next dry-dock)
Action required: 705 - Other - as specified
Due 1 February 2018
Resolved 7 June 2017
Resolution: Vessel received an extension from OES to expire 01AUG20.
Operations/Management › Vessel Safety Management › External Certification/Verification/Control
Issued 31 May 2017
Resolved
Conduct external Recognized Organization audit to determine validity of Safety Management Certificate.
Action required: 17 - Rectify deficiencies prior to departure
Due 31 May 2017
Resolved 5 June 2017
Resolution: External audit was conducted by Class NKK on 02JUN17 with non-conformities.
Construction/Loadline › Structures › Deck Plating
Issued 26 May 2017
Resolved
Gauge wasted deck are under the engine room ladder.
Action required: 705 - Other - as specified
Due 2 June 2017
Resolved 31 May 2017
Resolution: Area gauged satisfactory.
Electrical › Electrical Distribution System (service) › Panelboard
Issued 26 May 2017
Resolved
ECR- VFD Electrical panel for the cargo blowers behind main switchboard found zip-tide in the open position due to overheating. Make repairs and properly secure panel door.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2017
Resolved 1 June 2017
Resolution: Electric cooling fan installed on the VFD box.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Remote Pulls
Issued 26 May 2017
Resolved
Found fire pull station mounted on Co2 remote control box with electrical junction box exposed to the armored hose on the delay bottle. Box is not weather tight where pipe passes though Remote control box thereby creating a shock hazard.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2017
Resolved 5 June 2017
Resolution: New fire detection system pull station with WT box installed. Junction box in Remote station changed to a weather tight box.
Deck/Cargo › Holds/Tanks › Hatch
Issued 26 May 2017
Resolved
Holes found in #1 STBD cargo hatch. Gauge and make repairs to wasted area.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2017
Resolved 31 May 2017
Resolution: STBD Cargo Hatch holes, gauged, cropped and renewed area on hatch.
Fire Fighting › Fire Main › Condition
Issued 26 May 2017
Resolved
Multiple suspect areas were found on the backside of the Fire Main where mounted exterior of house on multiple decks. Conduct a satisfactory hydrostatic pressure test to the Fire Main to the satisfaction of the attending Marine Inspector.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2017
Resolved 9 June 2017
Resolution: Hyro tested SAT.
Fire Fighting › Fixed CO2 Fire Extinguishing System › Tanks
Issued 26 May 2017
Resolved
Found safety caps missing on approximately 48 Co2 bottles. Install/replace caps.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2017
Resolved 1 June 2017
Resolution: 48 safety caps installed ion the Co2 bottles.
Fire Fighting › Remote Fuel Shutoff › General
Issued 26 May 2017
Resolved
Safety glass missing on emergency shut-off port side at A/C room.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2017
Resolved 1 June 2017
Resolution: New safety glass and box installed for A/C room shut-off.
Communications › Alarms/Indicators › Bilge Alarm
Issued 26 May 2017
Resolved
Bilge alarm float (FR 112) in forward port side cargo hold, mounting bracket wasted and float sensor hanging by electric cable. Repair to satisfaction of the CG Marine Inspector.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2017
Resolved 31 May 2017
Resolution: Remounted.
Construction/Loadline › Structures › Transverse Bulkhead
Issued 26 May 2017
Resolved
Lower FWD STBD Cargo hold bulkhead found with wasted (FR 112 area), provide gauge reading for cargo hold/cofferdam bulkhead, make repairs if below allowable tolerance.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2017
Resolved 31 May 2017
Resolution: Gauged satisfactory.
Deck/Cargo › Ballast › Piping
Issued 26 May 2017
Resolved
STBD Engine Room Ballast Pipe suction/fill 90 degree elbow found excessive wastage. Provide gauge reading and make repairs if below allowable tolerance.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2017
Resolved 31 May 2017
Resolution: Gauged satifactory.
Fire Fighting › Fixed Fire Detection System › Heat Detectors
Issued 26 May 2017
Resolved
Fire detection system thermal sensors #7,8,9,10,17 & 18 where not properly installed and threaded into the A-0 bulkhead in the pipe tunnel to the overhead cargo bay. Properly install and test fire detections system to the satisfaction of the CG Marine Inspector.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2017
Resolved 2 June 2017
Resolution: Repaired/Replaced. SoTec of Jasxsonville provided report attesting "system checked ok" after repairs.
Fire Fighting › Structural - A Class Divisions › Corridors
Issued 26 May 2017
Resolved
Properly install fire stop around armor jacketed wire in STBD side overhead of the pipe tunnel in area of frame 80.
Action required: 17 - Rectify deficiencies prior to departure
Due 26 May 2017
Resolved 5 June 2017
Resolution: Armor jacketed wire at frame 80 did not require fire stop as the wire leads into an adjacent cofferdam and not the cargo bay as originally suspected.
Engineering › Fuel Oil Service System › Piping
Issued 25 May 2017
Resolved
Found 3 diesel fuel leaks port side 2nd deck engine room.
Action required: 17 - Rectify deficiencies prior to departure
Due 25 May 2017
Resolved 31 May 2017
Resolution: Fittings, and flanges tighted. Leaks secured.
Fire Fighting › Structural Fire Protection - General › Structural Bulkhead Construction
Issued 25 May 2017
Resolved
Multiple fire fire doors would not self-close and latch, some latches removed.
Action required: 17 - Rectify deficiencies prior to departure
Due 25 May 2017
Resolved 31 May 2017
Resolution: Adjusted and Repaired.
Operations/Management › Vessel Safety Management › Maintenance of Ship/Equipment
Issued 25 May 2017
Resolved
Both forward and aft cranes have excessive hydraulic leaks with saturated absorbent pads laying on deck and framing up through the vertical tunnel, creating a fire hazard.
Action required: 17 - Rectify deficiencies prior to departure
Due 25 May 2017
Resolved 31 May 2017
Resolution: Fire hazard of the standing hydraulic oil leaks under both fore and aft cranes cleaned, hydraulic lines tightened.
Operations/Management › Vessel Safety Management › Maintenance of Ship/Equipment
Issued 25 May 2017
Resolved
Hydraulic line leaking in pipe tunnel passageway amidship with saturated absorbent pads on deck, creating a fire hazard.
Action required: 17 - Rectify deficiencies prior to departure
Due 25 May 2017
Resolved 31 May 2017
Resolution: Hydraulic line leak in pipe tunnel found to be run-off on wire runs from crane. Cleaned and saturated lagging removed.
Fire Fighting › Fire Main › Condition
Issued 25 May 2017
Resolved
Fire Main pipe wasted and leaking onto electrical wire runs in pipe tunnel passageway near amidships.
Action required: 17 - Rectify deficiencies prior to departure
Due 25 May 2017
Resolved 9 June 2017
Resolution: 10 feet with drain installed and hydrostatically tested.
Construction/Loadline › Structures › Deck Plating
Issued 25 May 2017
Resolved
Lower Provision Room (2 areas) steel overhead wasted through to deck above inboard. Steel deck drain in overhead holed with soft patch.
Action required: 17 - Rectify deficiencies prior to departure
Due 25 May 2017
Resolved 9 June 2017
Resolution: Doublers installed SAT, ABS issued Condition of Class to make permanent repairs at next DD.
Construction/Loadline › Structures › Deck Plating
Issued 25 May 2017
Resolved
Pipe tunnel/passageway overhead wasted through to cargo deck with Red Hand patch covering holed area.
Action required: 17 - Rectify deficiencies prior to departure
Due 25 May 2017
Resolved 31 May 2017
Resolution: Patch removed and steal inserted.
Engineering › Sea-water System (primary cooling) › Valve
Issued 25 May 2017
Resolved
Mechanical Seal failed in (raw water) pump and could not be replaced due to suction and discharge valves could not be operated properly.
Action required: 17 - Rectify deficiencies prior to departure
Due 25 May 2017
Resolved 5 June 2017
Resolution: Raw water pump has been reinstalled with new isolation (butterfly) valves installed.
Engineering › Sea-water System (primary cooling) › Piping
Issued 25 May 2017
Resolved
STBD stern tube raw water supply pipe is holed and leaking onto electrical controller box.
Action required: 17 - Rectify deficiencies prior to departure
Due 25 May 2017
Resolved 5 June 2017
Resolution: Repair complete.
Engineering › Bilge Water Management System › Valve
Issued 25 May 2017
Resolved
Valve on bilge system system in thruster room is missing valve handle.
Action required: 17 - Rectify deficiencies prior to departure
Due 25 May 2017
Resolved 1 June 2017
Resolution: Valve handle replaced on bilge system in the thruster room.
Pollution Prevention/Response › Prevention Equipment › Fixed Containment
Issued 25 May 2017
Resolved
Bunker station port/aft missing threaded containment plug.
Action required: 705 - Other - as specified
Due 8 June 2017
Resolved 31 May 2017
Resolution: Plug replaced.
Construction/Loadline › Hull › Bottom Plating
Issued 24 May 2017
Resolved
Make repairs to the wastage/damage bottom shell iwo FR 121 to 122 and any other identified by class or Coast Guard, to the satisfaction of the attending Coast Guard Marine Inspector.
Action required: 17 - Rectify deficiencies prior to departure
Due 24 May 2017
Resolved 5 June 2017
Resolution: Hull repair was satisfactory and made watertight to include the bow thruster tube. The tube will be required permanent repair at next dry-dock but no later than 01FEB2018.
Fire Fighting › Fire Pumps › Pressure
Issued 24 May 2017
Resolved
Make repairs to the vessels Fire Pump and prove proper operation to the satisfaction of the attending Coast Guard Marine Inspector.
Action required: 17 - Rectify deficiencies prior to departure
Due 24 May 2017
Resolved 9 June 2017
Resolution: Rebuilt FP installed and satisfactorily tested.
Electrical › Electric Supply System (service) › Cable
Issued 19 August 2016
Resolved
ROX-Blox for wire run going to steering gear room had a loose cable.
Action required: 705 - Other - as specified
Resolved 19 August 2016
Resolution: Shipyard electrician made repairs.
Fire Fighting › Miscellaneous Items › Waste Receptacles
Issued 19 August 2016
Resolved
There were plastic trash cans with oily rags in various locations in machinery spaces.
Action required: 705 - Other - as specified
Resolved 24 August 2016
Resolution: Vessel received metal, fire resistant waste receptacles and removed the plastic ones.
Fire Fighting › Structural - A Class Divisions › Corridors
Issued 19 August 2016
Resolved
There was some missing SFP in the walkway tunnel adjacent to accomodations.
Action required: 705 - Other - as specified
Resolved 25 August 2016
Resolution: SFP was replaced.
Fire Fighting › International Shore Connection › Gasket
Issued 19 August 2016
Resolved
Shore connection was missing a gasket.
Action required: 705 - Other - as specified
Resolved 19 August 2016
Resolution: A new gasket was made and placed with the shore connection.
Engineering › Fuel Oil Service System › Valve
Issued 19 August 2016
Resolved
E-gen fuel valve emergency pull did not work.
Action required: 705 - Other - as specified
Resolved 19 August 2016
Resolution: Crew adjusted the cable and tested valve pull, sat.
Electrical › Electrical Distribution System (emergency) › Cable
Issued 19 August 2016
Resolved
GMDSS battery terminals were corroded and loose.
Action required: 705 - Other - as specified
Resolved 19 August 2016
Resolution: Crew cleaned and tightened battery terminals.
Electrical › Electrical Distribution System (service) › Cable
Issued 19 August 2016
Resolved
A dead end cable was found on top of the pilot house.
Action required: 705 - Other - as specified
Resolved 19 August 2016
Resolution: Dead end cable was removed and the stuffing tube was packed.
Operations/Management › Vessel Safety Management › Master's Responsiblity/Authority
Issued 11 August 2016
Resolved
[withheld — contains personal information; the deficiency system, dates, and resolution status are shown above]
Condition: Damaged By Earlier Event
Action required: 17 - Rectify deficiencies prior to departure
Due 11 August 2016
Resolved 26 August 2016
Resolution: Class attended vessel to witness repairs
Documentation › Certificates/Documents › Safety Management Certificate (ISM)
Issued 11 August 2016
Resolved
Based on objective evidence found on an ISM oversight of the vessel's SMS on Aug 11, 2016 DOC SMM-SAF-04, AP-1 (immediate incident notification) vessel must conduct an external ISM SMS Audit prior to departing Jacksonville COTP. ISM Code 2.2, 5 & 9.1
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Resolved 25 August 2016
Resolution: NKK conducted audit.
Operations/Management › Casualty Reporting/Post-Casualty Actions › Notice of Marine Casualty
Issued 21 February 2016
Resolved
Vessel was hit by a barge on 09 AUG 2015 at 1342 hours and was damaged in way of the starboard side aft hull around frame 30. The hull was breached and the #12 ballast tank discharged water as a result
Condition: Damaged By Earlier Event
Action required: 705 - Other - as specified
Due 21 February 2016
Resolved 21 February 2016
Resolution: ABS attended vessel in Ft. Lauderdale, FL and witness the successful hull repair.
Operations/Management › Lifesaving › Op Readiness/Maintenance/Inspection
Issued 9 February 2016
Resolved
Vessel Owner/Operator shall complete an external ISM Audit by a recognized organization and witnessed by attending Coast Guard Marine Inspector at Piraeus, Greece.
Condition: Invalid
Action required: 17 - Rectify deficiencies prior to departure
Due 18 February 2016
Resolved 14 July 2016
Resolution: Cleared from previous activity actions. See Activity #5811864.
Communications › Alarms/Indicators › Fire Alarm
Issued 5 January 2016
Resolved
There are seven fire detectors in the cargo hold, one detector is not operational. Repair or replace as necessary and prove proper operation to the satisfaction of class.
Action required: 705 - Other - as specified
Due 5 February 2016
Resolved 17 February 2016
Resolution: Technicians replaced fire detector in Cargo Hold and class randomly tested fixed detection system sat.
Fire Fighting › Fire Pumps › Power Source
Issued 5 January 2016
Resolved
The motor for the main fire pump is inoperative. Make repairs or replace as necessary and prove proper operation to the satisfaction of a class surveyor.
Action required: 705 - Other - as specified
Due 5 February 2016
Resolved 5 February 2016
Resolution: Class report provided attesting to proper operation of the main fire pump.