AZAMARA QUEST

AZAMARA QUEST is a passenger vessel (inspected). The Coast Guard has recorded 21 inspections since 2005, most recently in October 2025, along with 17 deficiencies and 3 operational controls.

Records from 2005 to 2025. Most recent: inspection, 2 October 2025.

Built
Not recorded
Last inspected
2 October 2025
Documentation
Not in the documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

9210218 View on MarineTraffic leaves Maury; a third-party site, nothing from it is stored here
800475
Flag
MALTA
—
Maury page id
psix-800475

Inspections, by type

…with no type recorded4
Years with a record 9 calendar years (2005–2025)
The 21 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Passenger Ship class in Maury's sources begin in 1977.

Documentation record

Tonnage as PSIX records it30277 - Convention (Subpart B), Gross Ton
11748 - Convention (Subpart B), Net Ton
3376 - Dead Weight, Ton
16146 - Displacement, Ton
This hull's Official Number is not in the NVDC file dated 10 September 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.

Radio station licence

No FCC ship-station licence is recorded against this Official Number in the file of 6 September 2026. That is a fact about the licence file, not about the radio.

Inspection history · 21

2 October 2025 COC-CVE Annual · PSC A
Physical examination · Sector Northern New England · USCG Northeast District (CGD-NE) · Activity 8244998
23 November 2021 COC-CVE Annual · PSC B
Physical examination · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 7350914
6 November 2021 Administrative Inspection
Administrative · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 7346503
1 November 2021 Type not recorded
No type recorded · USCG Southeast District (dp) · USCG Southeast District (CGD-SE) · Activity 7343506
21 May 2019 ISPS II Exam · COC-CVE Annual · Ballast Water Examination
Physical examination · Sector Western Alaska and U.S. Arctic · USCG Arctic District (CGD-A) · Activity 6668645
20 May 2019 Administrative Inspection
Administrative · Sector Western Alaska and U.S. Arctic · USCG Arctic District (CGD-A) · Activity 6822180
17 February 2018 Administrative Inspection
Administrative · Sector San Diego · USCG Southwest District (CGD-SW) · Activity 6356744
21 December 2017 Administrative Inspection
Administrative · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6327472
20 November 2017 Ballast Water Examination · ISPS II Exam · COC-CVE Annual
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6308337
21 March 2017 Ballast Water Examination · COC-CVE Quarterly · ISPS II Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 6108062
23 October 2016 In-Service Inspection · Administrative Inspection
Physical examination · Sector Mobile · USCG Heartland District (CGD-H) · Activity 6028295
22 October 2016 Type not recorded
No type recorded · Sector Key West · USCG Southeast District (CGD-SE) · Activity 6027574
22 October 2016 Type not recorded
No type recorded · Sector Key West · USCG Southeast District (CGD-SE) · Activity 6030692
17 October 2016 Administrative Inspection
Administrative · Sector Key West · USCG Southeast District (CGD-SE) · Activity 6023873
2 October 2016 ISPS II Exam · COC-CVE Initial · Ballast Water Examination · PII Safety Exam · Deficiency Check
Physical examination · Marine Safety Unit Belfast · USCG Northeast District (CGD-NE) · Activity 6004151
27 March 2014 Deficiency Check
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 4823774
19 March 2014 Administrative Inspection
Administrative · Marine Safety Unit Saint Thomas · USCG Southeast District (CGD-SE) · Activity 4818794
12 March 2014 Spot Check · ISPS III Exam · Ballast Water Examination
Physical examination · Sector New Orleans · USCG Heartland District (CGD-H) · Activity 4814642
21 October 2007 MARPOL Annex I Examination · COC-CVE Annual · ISPS II Exam
Physical examination · Sector Miami · USCG Southeast District (CGD-SE) · Activity 3083779
19 October 2007 Type not recorded
No type recorded · Sector Miami · USCG Southeast District (CGD-SE) · Activity 3082991
28 November 2005 COC-CVE Initial
Administrative · Activities Europe · Activity 2544531

Deficiency record · 17

03 - Water/Weathertight Conditions › N/A - No Subsystem › Ventilators, air pipes, casings
Issued 23 November 2021 Resolved
Where pipes, scuppers, electrical cables etc. are carried through watertight subdivision bulkheads, arrangements shall be made to ensure the watertight integrity of the bulkheads. PSCO's discovered 04 electrical penetrations leading into the steering gear room from a watertight deck on the aft mooring deck that were not watertight. 74 SOLAS 04 consolidated Ch II-1/15
Condition: Improper/Lack of Maintenance
Action required: 10 - Deficiency Rectified
Resolved 23 November 2021
Resolution: Vessel refitted the watertight penetration with approved material to bring into appropriate service. Refit was approved by classification society.
Fire Fighting › Structural - A Class Divisions › Doors
Issued 20 November 2017 Resolved
74SOLAS (2001) II-2/3.3 - A Class divisions shall be so constructed as to be capable of preventing the passage of smoke and flame to the end of the one hour standard hour test. Emergency generator space door is of B Class division.
Condition: Improper Installation
Action required: 705 - Other - as specified
Due 20 January 2018
Resolved 10 January 2018
Resolution: Received class report refrencing SOLAS CH II-2/9.4.1.1.6 which states doors which open to open decks not leading to lifesaving appliances need not be A class doors.
Fire Fighting › Fixed Pressure Water-Spraying Fire Extinguishing System › Location
Issued 20 November 2017 Resolved
74SOLAS (2001) II-2/18.9; MSC/Circ. 800 - Where deep-fat cooking equipment is installed all new installations shall be fitted with an automatic or manual fixed fire extinguishing system. Deep frying equipment in main galley, crew galley, and speciality galley do not have fixed fire fighting installation IAW MSC/Circ. 800.
Condition: Design Flaw
Action required: 705 - Other - as specified
Due 20 January 2018
Resolved 10 January 2018
Resolution: Received class report and confirmed at unit that due to the age of the vessel fixed fire fighting not required to be installed at the deep fat fryer.
Operations/Management › Drills/Instruction › Making Voice Radio Distress Call
Issued 20 November 2017 Resolved
74SOLAS (2014) - At least one person qualified for distress and safety radiocommunication shall be assigned to perform only radiocommunication duties during distress incidents. During emergency drill vessel radiocommunication officer performed other duties and functions apart from radiocommunication.
Action required: 705 - Other - as specified
Due 20 November 2017
Resolved 20 November 2017
Fire Fighting › Structural - A Class Divisions › Corridors
Issued 2 October 2016 Resolved
Main Vertical Zones shall be sub-divided by A-60 Class divisions. The bulkhead of Electrical Room #409 is missing a section. Install insulation on the bulkhead. 74 SOLAS (01 Cons.) II-2/24.1.1 50a/50c
Action required: 705 - Other - as specified
Due 2 November 2016
Resolved 3 October 2016
Resolution: Vessel attended by Sector Northern New England. Insulation has been installed.
Fire Fighting › Automatic Sprinkler System › Sprinkler Grouping
Issued 2 October 2016 Resolved
Fixed Sprinkler extinguishing systems shall be adaquately spaced to provide equal coverage of the space. The Flamable Lube Oil storage space (CAT 14) port side does not provide adaquate coverage along the outboard port side. 74 SOLAS (01 Cons.) II-2/12.3 50a/c
Action required: 705 - Other - as specified
Due 2 November 2016
Resolved 3 October 2016
Resolution: Vessel attended by Sector Northern New England. Two sprinkler heads were added to provide adequate coverage.
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 2 October 2016 Resolved
Fire protection systems shall be kept in good working order. Various fire doors were not working or closing properly. 74 SOLAS (2014) II-2/14.2.1.1 10c
Action required: 705 - Other - as specified
Due 2 October 2016
Resolved 2 October 2016
Resolution: Fire door operation was prooved to satisfaction of attending PSCO.
Operations/Management › Navigation Safety › Arrival/Departure Tests
Issued 19 March 2014 Resolved
No more than 12 hours before entering the US, or departing a port, the operation of the emergency power supply and the steering gear operation from the alternative power supply shall be checked. Vessel did not conduct pre-arrival checks in accordance with the regulations. Steering gear was not test under emergency power source.
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Due 27 March 2014
Resolved 27 March 2014
Resolution: Ship provided operational test procedures IRT testing steering gear under emergency power.
Operations/Management › Navigation Safety › Arrival/Departure Tests
Issued 12 March 2014 Resolved
2099-Other -No more than 12 hours before entering the US or departing a port the operation of the emergency power supply and the steering gear operation from the alternative power supply shall be checked . C/E stated the vessel does not test operation of steering gear from the alternative power supply or the emergency power supply prior to arrival or departure from any port.SOLAS 74A V/26
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Due 12 March 2014
Resolved 19 March 2014
Resolution: Received scanned copy of AZAMARA QUEST deck log reflecting that the vessel conducted pre-arrival in accordance with the regulations prior to their arrival Port of St John.
Fire Fighting › International Shore Connection › Connection
Issued 12 March 2014 Resolved
0730-Appliances- Ships of 500 gross tonnage and upwards shall be provided with at least one international shore connection complying with the Fire Safety Systems Code. The vessel permanently attached their connections to the fire main vice having them portable with gaskets and bolts.SOLAS 74 A II-2/10
Action required: 705 - Other - as specified
Due 28 March 2014
Resolved 27 March 2014
Resolution: Ship provided portable international shore connection both port and starboard side of ship.
Fire Fighting › Structural - A Class Divisions › Fire Doors
Issued 12 March 2014 Resolved
0710-SOLAS 74A II-2/14- structural fire protection, including fire-resisting divisions, and protection of openings and penetrations in these divisions shall be kept in good order so as to ensure their required performance if a fire occurs. FSDs 3903 and 719 would not close without assistance.
Action required: 705 - Other - as specified
Due 12 March 2014
Resolved 12 March 2014
Resolution: FSDs repaired and verified as operational prior to the completion of the exam.
Construction/Loadline › Markings › Draft Marks/Indicating System
Issued 21 October 2007 Resolved
Deck mark IAW LL regs not visible, no contrasting colors
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 October 2007
Resolution: Resolved
Operations/Management › Vessel Safety Management › Plans for Shipboard Operations
Issued 21 October 2007 Resolved
"Blue Moon" signage on WTDs; what is ship's policy for operating notifying Bridge during operation of WTD
Due 4 November 2007
Resolved 22 October 2007
Resolution: Resolved
Electrical › Electrical Distribution System (service) › Distribution Panel Bus
Issued 21 October 2007 Resolved
Electrical panel door missing. Wires are exposed.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 October 2007
Resolution: Panel replaced.
Pollution Prevention/Response › Prevention Equipment › Garbage Grinder/Comminuter
Issued 21 October 2007 Resolved
House cleaning in Garbage Room, deck 3; open paint cans & garbage needs to be stowed/removed.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 October 2007
Resolution: Resolved
Fire Fighting › Fixed Fire Detection System › Smoke Detectors
Issued 21 October 2007 Resolved
Smoke detector cabin #6056 is inoperative and must be replaced/fixed.
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 October 2007
Resolution: Resolved..
Operations/Management › Vessel Safety Management › Maintenance of Ship/Equipment
Issued 29 November 2005 Resolved
Complete all remaining items from overseas ICVE final worklist issued on November 29, 2005 prior to issuance of USCG Certificate of Compliance letter.
Action required: 15 - Rectify deficiencies by next port
Due 31 December 2005
Resolved 31 December 2005
Resolution: Conducted ICVE COC exam and ISPS II exam. Cleared remaining 08 wordlist items from ACTEUR dated Nov 29 2005. No wordlist items remain. All items examined this date satisfactory.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.