Records from 2022 to 2024. Most recent: inspection, 8 May 2024.
01 - Certificates & Documentation › 011 - Ships Certificates › Other (certificates)
Issued 19 July 2022
Resolved
All owners and operators of an existing towing vessel must have on board a valid COI prior to the specified phase-in period. This vessel has not scheduled an inspection or obtained a valid COI. The vessel shall be made available for a Coast Guard COI Inspection immediately and the vessel may no longer be permitted to operate.
Condition: Invalid
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 July 2022
Resolution: Issued completed initial certificate of inspection and temporary COI.
04 - Emergency Systems › N/A - No Subsystem › Emergency, lighting, batteries and switches
Issued 23 June 2022
Resolved
Emergency lighting must be provided for all internal crew work and living spaces. Multiple spaces on the vessel, to include the E/R and Galley, did not have emergency lighting. Provide emergency lighting for all crew work and living spaces.
Condition: Improper Installation
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 July 2022
Resolution: Verified installed emergency lighting installation in living spaces.
03 - Water/Weathertight Conditions › N/A - No Subsystem › Doors
Issued 23 June 2022
Resolved
Closure devices must be provided for deckhouse or or hull penetrations, which open to the exterior of the vessel. Four of the five deck house doors that were tested on the main deck failed a chalk test. Chalk test ALL doors and hatches and make watertight/weathertight.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 July 2022
Resolution: Chalk tested and verified WTD seal, all sat.
07 - Fire Safety › N/A - No Subsystem › Oil accumulation in engine room
Issued 23 June 2022
Resolved
All seals/gaskets must be properly maintained to prevent leaks of combustible liquids. The gaskets for the supercharger-to-block and governor-to-block mating surfaces on both GenSet engines are leaking significantly. Make proper repairs.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 July 2022
Resolution: Observed both generators running with no visible signs of oil leaking after new gaskets were installed.
09 - Working and Living Conditions › 092 - Working Conditions › Electrical
Issued 23 June 2022
Resolved
Electrical components that pose an electrical hazard must be in an enclosure. There are multiple junction boxes and a lighting fixture in the engine room that are missing covers. Make proper repairs.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 July 2022
Resolution: Covers were installed on open junction boxes.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 23 June 2022
Resolved
A remote fuel shutoff valve must be fitted on any fuel line that supplies fuel directly to a propulsion engine or generator prime mover. The valve must be installed directly outside the fuel oil supply tank. The vessel's fuel system has remote fuel shutoff valves, however they are installed before each engines fuel/water separator, not directly outside the fuel oil supply tank. That system was tested. The shutoff valve for the starboard engine failed to actuate. Install shutoff valves for each service line, directly outside the tank.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 July 2022
Resolution: Remote fuel shut-off valves were installed at the tanks and tested satisfactorily from outside the space.
07 - Fire Safety › N/A - No Subsystem › Fire pumps and its pipes
Issued 23 June 2022
Resolved
A fixed fire-pump must be capable of delivering water at a pitot-tube pressure of at least 50 psi. When tested, the fire-pump could deliver water at only 42 psi.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 July 2022
Resolution: A new fire pump was installed and operationally tested, all sat.
07 - Fire Safety › N/A - No Subsystem › Fire fighting equipment and appliances
Issued 23 June 2022
Resolved
Portable fire extinguishers must be inspected IAW NFPA 10. The portable extinguisher in the upper starboard state room is due for its 6 and 12 year inspection.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 July 2022
Resolution: Portable fire extinguisher was serviced by third party.
11 - Life Saving Appliances › N/A - No Subsystem › Stowage and provision of liferafts
Issued 23 June 2022
Resolved
The master must ensure that all life-saving equipment is properly maintained and ready for use at all times. The painter for the inflatable liferaft was not connected to the weak-link.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 July 2022
Resolution: Life raft painter was properly connected to the hydrostatic release unit.
05 - Radio Communications › N/A - No Subsystem › Satellite EPIRB 406MHz/1.6GHz
Issued 23 June 2022
Resolved
All lifesaving equipment must be maintained in accordance with 46 CFR 199.190. The hydro-static release unit for the EPIRB was not marked with an expiration date when installed. Provide proof of when the unit was installed and mark the expiration date IAW 46 CFR 199.190 or replace if necessary.
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 28 July 2022
Resolution: The EPIRB hydrostatic release unit was properly marked with expiration date.
09 - Working and Living Conditions › 092 - Working Conditions › Steam pipes and pressure pipes
Issued 23 June 2022
Resolved
Machinery must be designed and maintained to provide for safety of persons on board. The pressure relief valve for the hot-water heater in the starboard E/R needs to be piped to the bilge.
Action required: 60 - Rectify deficiencies prior to movement
Resolved 28 July 2022
Resolution: The water heater pressure relief valve was piped into the bilges.