MAURY USCG vessel records Sign in
← All vessels

STAVANGER BLOSSOM

STAVANGER BLOSSOM is a tank ship. The Coast Guard has recorded 13 inspections since 2007, most recently in October 2020, along with 5 deficiencies and 4 operational controls.

Records from 2007 to 2020. Most recent: inspection, 20 October 2020.

Built
Not recorded
Last inspected
20 October 2020
Documentation
Not in the documentation file of 10 September 2026
Controls
None recorded without a removal date

Identity

9337389 View on MarineTraffic leaves Maury; a third-party site, nothing from it is stored here
892137
Flag
NORWAY
—
Maury page id
psix-892137

Inspections, by type

…with no type recorded6
Years with a record 5 calendar years (2007–2020)
The 13 inspections in the strip above, split by the kind of activity the US Coast Guard recorded. Years with a record are calendar years in which a record exists, not years in service. What Maury does not do.

This record may be incomplete: the most recent inspection recorded for this vessel was 6 years ago. Maury shows what the Coast Guard recorded, not whether the vessel has been inspected since, is still in service, or what condition it is in. Coast Guard record current through 13 September 2026, retrieved 18 September 2026 from PSIX. Every field on this page was recorded by the Coast Guard. Records for the Tank Ship class in Maury's sources begin in 1980.

Documentation record

Tonnage as PSIX records it56172 - Convention (Subpart B), Gross Ton
32082 - Convention (Subpart B), Net Ton
105641 - Dead Weight, Ton
121482 - Displacement, Ton
This hull's Official Number is not in the NVDC file dated 10 September 2026 as served by NOAA Fisheries, so no documentation record is shown. Absence from that file is a fact about the file, not about the hull.

Radio station licence

No FCC ship-station licence is recorded against this Official Number in the file of 6 September 2026. That is a fact about the licence file, not about the radio.

Inspection history · 13

20 October 2020 PSC B · COC-TVE Renew
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 7080719
25 July 2019 Type not recorded
No type recorded · Sector New York · USCG Northeast District (CGD-NE) · Activity 6761955
17 April 2019 Ballast Water Examination · COC-TVE Renew · ISPS II Exam
Physical examination · Marine Safety Unit Lake Charles · USCG Heartland District (CGD-H) · Activity 6656540
13 July 2009 ISPS II Exam · COC-TVE Renew
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 3533752
13 July 2009 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 3534794
11 July 2009 Type not recorded
No type recorded · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 3531301
12 July 2008 COC-TVE Annual · Ballast Water Examination · ISPS II Exam
Physical examination · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 3258358
8 July 2008 Type not recorded
No type recorded · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 3262090
21 January 2008 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 3133638
21 January 2008 Type not recorded
No type recorded · Sector Los Angeles/Long Beach · USCG Southwest District (CGD-SW) · Activity 3133944
13 September 2007 Deficiency Check
Physical examination · Sector Honolulu · USCG Oceania District (CGD-O) · Activity 3056993
26 June 2007 Deficiency Check
Physical examination · Sector San Francisco · USCG Southwest District (CGD-SW) · Activity 2975002
13 June 2007 COC-TVE Annual · ISPS II Exam
Physical examination · Sector Puget Sound · USCG Northwest District (CGD-NW) · Activity 2960658

Deficiency record · 5

06 - Cargo Operations Including Equipment › N/A - No Subsystem › Other (cargo)
Issued 20 October 2020 Resolved
Electrical or other equipment which may constitute a source of ignition of flammable vapors shall not be permitted in these compartments except as permitted in paragraph 10. PSCO Observed 04 EX light fixtures in pump room with cracked casings, compromising the EX certification of the fixtures.    74 SOLAS (04) II-1/45.9.2
Action required: 17 - Rectify deficiencies prior to departure
Resolved 22 October 2020
Resolution: Repaired / Rectified: The four lights in question were replaced with suitable EX rated lights. The installation of the newly fitted light fixtures was examined and found in order. See Class report for further details.
09 - Working and Living Conditions › 092 - Working Conditions › Ventilation (Working spaces)
Issued 20 October 2020 Resolved
Machinery, associated piping systems and fittings shall be of a design and construction adequate for the service for which they are intended. PSCO observed multiple hols and wastage in the ventiliation near IG system and engineers work shop. 74 SOLAS (04)II-I/26.1
Action required: 50 - Rectify deficiencies w/in 30 days
Resolved 22 October 2020
Resolution: The corroded ducting was examined and a repair plan wats agreed upon. A Condition of Class was issued for repair of the ducting.
09 - Working and Living Conditions › 092 - Working Conditions › Gangway, accommodation-ladder
Issued 20 October 2020 Resolved
All arrangements used for pilot transfer shall efficiently fulfill their purpose of enabling pilots to embark and disembark safely. The appliances shall be kepts clean, properly maintained and stowed. PSCO observed starboard sided accomodation ladder with considerable wastage (10inches X 10inches). 74 SOLAS (14)V/23.2.1
Action required: 16 - Rectify deficiencies w/in 14 days
Resolved 22 October 2020
Resolution: The corroded upper landing of the starboard side accommodations ladder was examined and a repair plan wats agreed upon. A Condition of Authority was issued for repair of the damaged upper landing. See class report for further details.
Deck/Cargo › Inert Gas System › Venting System
Issued 13 June 2007 Resolved
Both High and Low-Low alarm visual indicating lights are not properly operating.
Condition: Unknown
Action required: 705 - Other - as specified
Due 27 June 2007
Resolved 27 June 2007
Resolution: Witnessed Satisfactory test of visual and audible alarm indicators.
Fire Fighting › Combustible Materials › Furniture/Furnishings
Issued 13 June 2007 Resolved
Waste recepticles are made of combustable materials.
Action required: 40 - Rectify deficiencies prior to next US port after sailing foreign
Resolved 13 September 2007
Resolution: Received class report stating that the waste receptacles have been replaced.

Ownership record

The Coast Guard's documentation record for this hull -- the Abstract of Title, with its owners and liens as filed -- is not in PSIX. Ask, and Maury buys it from the National Vessel Documentation Center, files it here with its date, and every reader of this page gets it.